Robust control methodology for the design of supplementary damping controllers for FACTS devices

Abstracts

In this paper, a new procedure to design Supplementary Damping Controllers (SDCs) for Flexible Alternating Current Transmission System (FACTS) devices is proposed. The control design problem is formulated as a search for a feasible controller subject to restrictions in the form of Linear Matrix Inequalities (LMIs). The main objective, from the application viewpoint, is the improvement of the damping ratios associated to inter-area oscillation modes. Unlike other types of formulations existing in the literature, this new formulation is capable of explicitly modeling the constraints on the controller bandwidth, which are crucial to avoid undesired amplification of high frequency noise signals coming into the controller input. To illustrate the efficiency of the proposed procedure, the design of an SDC for a Thyristor Controlled Series Capacitor (TCSC) placed in the New England/New York benchmark test system is carried out. The results show the designed controllers are able to provide adequate damping for the oscillations modes of interest for several different operating conditions.

Inter-area oscillations; linear matrix inequalities; supplementary damping controller; FACTS devices; TCSC


Este artigo propõe um novo procedimento para projeto de controladores suplementares de amortecimento (ou SDCs, do inglês Supplementary Damping Controllers) para dispositivos FACTS. O problema de projeto do controlador é formulado como uma busca por um controlador que satisfaça um conjunto de restrições na forma de desigualdades matriciais lineares (ou LMIs, do inglês Linear Matrix Inequalities). Sob o ponto de vista de aplicação, o objetivo principal de controle é aumentar as taxas de amortecimento das oscilações inter-área. Ao contrário de outras formulações propostas na literatura, esta nova formulação é capaz de modelar, explicitamente, as restrições da banda passante do controlador, evitando assim que ruídos em alta frequencia sejam amplificados a partir do sinal de entrada do controlador. Para ilustrar a eficiência do procedimento proposto foi realizado um projeto de controlador suplementar para dispositivos TCSC instalados no sistema New England/New York. Os resultados mostram que os controladores projetados são capazes de fornecer amortecimento adequado para os modos de oscilação de interesse em diversas condições de operação.

oscilações inter-área; desigualdades matriciais lineares; controlador suplementar de amortecimento; dispositivos FACTS; TCSC


SISTEMAS DE POTÊNCIA

Robust control methodology for the design of supplementary damping controllers for FACTS devices

Roman Kuiava; Rodrigo A. Ramos; Newton G. Bretas

Department of Electrical Engineering - Engineering School of São Carlos - University of São Paulo (USP), São Carlos, Brazil. kuiava@sel.eesc.usp.br, ramos@sel.eesc.usp.br, ngbretas@sel.eesc.usp.br

ABSTRACT

In this paper, a new procedure to design Supplementary Damping Controllers (SDCs) for Flexible Alternating Current Transmission System (FACTS) devices is proposed. The control design problem is formulated as a search for a feasible controller subject to restrictions in the form of Linear Matrix Inequalities (LMIs). The main objective, from the application viewpoint, is the improvement of the damping ratios associated to inter-area oscillation modes. Unlike other types of formulations existing in the literature, this new formulation is capable of explicitly modeling the constraints on the controller bandwidth, which are crucial to avoid undesired amplification of high frequency noise signals coming into the controller input. To illustrate the efficiency of the proposed procedure, the design of an SDC for a Thyristor Controlled Series Capacitor (TCSC) placed in the New England/New York benchmark test system is carried out. The results show the designed controllers are able to provide adequate damping for the oscillations modes of interest for several different operating conditions.

Keywords: Inter-area oscillations, linear matrix inequalities, supplementary damping controller, FACTS devices, TCSC.

RESUMO

Este artigo propõe um novo procedimento para projeto de controladores suplementares de amortecimento (ou SDCs, do inglês Supplementary Damping Controllers) para dispositivos FACTS. O problema de projeto do controlador é formulado como uma busca por um controlador que satisfaça um conjunto de restrições na forma de desigualdades matriciais lineares (ou LMIs, do inglês Linear Matrix Inequalities). Sob o ponto de vista de aplicação, o objetivo principal de controle é aumentar as taxas de amortecimento das oscilações inter-área. Ao contrário de outras formulações propostas na literatura, esta nova formulação é capaz de modelar, explicitamente, as restrições da banda passante do controlador, evitando assim que ruídos em alta frequencia sejam amplificados a partir do sinal de entrada do controlador. Para ilustrar a eficiência do procedimento proposto foi realizado um projeto de controlador suplementar para dispositivos TCSC instalados no sistema New England/New York. Os resultados mostram que os controladores projetados são capazes de fornecer amortecimento adequado para os modos de oscilação de interesse em diversas condições de operação.

Palavras-chave: oscilações inter-área, desigualdades matriciais lineares, controlador suplementar de amortecimento, dispositivos FACTS, TCSC.

1 INTRODUCTION

Inter-area oscillations are a common phenomenon observed in electric power systems world-wide, where groups of synchronous generators are interconnected over long distance transmission lines. Usually, these interconnection lines create a weak electric coupling between the generator groups and must sustain high levels of active power flow during normal operation. As a consequence, the inter-area oscillations will probably exhibit poor damping (or even instability) in the absence of an adequate stabilizing control system (Kundur et al., 2004)(Gama, 1999). Power System Stabilizers (PSSs) have been used for many years to supply additional damping for the low-frequency oscillations in power systems by means of a stabilizing signal added to the excitation systems of the generators (DeMello and Concordia, 1969). In practice, the PSSs are effective to damp local oscillations but, unfortunately, they are not always as effective to damp inter-area oscillations. This mainly occurs due to the difficulties related to tuning and coordination of multiples PSSs which operate in different power systems areas (Handschin, Schnurr and Wellssow, 2003). In these cases, the use of alternative solutions is mandatory.

In recent years, due to development of power electronics, the Flexible Alternating Current Transmission System (FACTS) devices have been successfully used to improve steady-state and dynamic system performance, and became an interesting cost-effective alternative compared to the system expansion (Paserba, 2004). These devices can be used, for example, to improve local voltage stability margins and/or to reduce electrical distances in long transmission lines. As a consequence, the maximum amount of active power that can be transferred among the interconnected systems may be increased. Also, there are several types of FACTS devices that may be used to provide additional damping to inter-area oscillations by inclusion of a Supplementary Damping Controller (SDC) to the device (Paserba, 2003)( Hingorani and Gyugyi, 2000).

From the practical viewpoint, there are several characteristics that both type of damping controllers (PSSs and SDCs for FACTS devices) have to possess. The following list depicts some of them:

(i) the controllers must be robust with respect to the uncertainties in the system operating point, i.e., a satisfactory level of damping must be achieved in several different operating conditions;

(ii) multiple damping controllers operating simultaneously in a system must have a coordinated action;

(iii) the action of the damping controllers must vanish in steady-state, so the controllers do not change the operating point defined by the load flow;

(iv) a control structure based on dynamic output feedback must be used due to difficulties in obtaining measurements of all state variables of the system, and;

(v) it is preferable to use local input control signals, because the use of remote signals would require the implementation of dedicated communication links and complex control schemes, which would increase the cost for implementation of the controller.

The usual practice in power systems is to employ classical phase compensation to design both PSSs and SDCs for FACTS devices. These controllers consist basically of a static gain, a washout filter and a phase compensation network (Gama, 1999)(DeMello and Concordia, 1969). Such quite simple control structure suitably satisfies the practical requirements (iii) to (v). Ad hoc approaches are often used to tune the parameters of these controllers (as, for example, pole placement techniques based on root locus rules and eigenvalue placement using transfer function residues) (DeMello and Concordia, 1969)(Larsen and Swann, 1981). The major difficulties in these design procedures are related to the practical requirements (i) and (ii), i.e., in guaranteeing the robustness of the controller with respect to the uncertainties in the system operation that were not treated in the design stage, and also to ensure an adequate coordination of multiple damping controllers operating simultaneously in the system.

A number of alternative techniques (based on classical and modern control concepts) have been proposed to address the robustness and coordination of multiple damping controllers. Design procedures based on frequency domain methods are presented, for example, in (IEEE Power System Engineering Committee, 1999). Methodologies based on robust control theory were also proposed, and the H¥ mixed-sensitivity formulation (Chaudhuri and Pal, 2004), the combined H¥ control problem with regional pole placement constraints using LMIs (Tsai, Chu and Chou, 2004) and the multi-objective genetic algorithms approach (Bomfim, Taranto and Falcão, 2000), can be cited as examples.

Paper (Ramos, Alberto and Bretas, 2004a) proposes a methodology (which was later on extended in (Ramos, Martins and Bretas, 2003)), based on a robust control technique, to design PSS-type controllers. The design objective of such methodology consists basically in calculating a dynamic output feedback controller described in state space form by matrices AC, BC and CC that stabilize (also fulfilling a specific performance criterion) a set of linearized power system models with matrices A, B and C. This control problem is formulated using the well-know Lyapunov Inequality developed for LTI systems (Boyd et al., 1994). Additionally, constraints in the form of matrix inequalities are included to guarantee both: robustness (using the Polytopic Quadratic Stability concept) and a minimum performance of the closed loop system by means of a Regional Pole Placement technique (Boyd et al., 1994)(Chiali, Gahinet and Apkarian, 1999). As a result, the control formulation is described by a set of BMIs (Bilinear Matrix Inequalities) on the matrix variables. It is possible, however, to transform these BMIs into a set of LMIs by a two-step separation procedure shown in (Oliveira, Geromel and Bernussou, 2000).

The resulting control methodology based on LMIs is presented in (Ramos, Alberto and Bretas, 2004a) for the design of PSS-type controllers. Unfortunately, this control methodology is not general enough to be applied in the design of SDCs for FACTS devices. In reference (Xue, Zhang and Godfrey, 2006) a different two-step separation procedure is applied, and the resulting procedure is able to handle the problem of SDC design for FACTS devices. It is also argued in (Xue, Zhang and Godfrey, 2006) that the ideas used in (Ramos, Alberto and Bretas, 2004a) and (Oliveira, Geromel and Bernussou, 2000) may not be applicable to this problem.

This paper proves the converse, i.e., that the ideas in (Ramos, Alberto and Bretas, 2004a) and (Oliveira, Geromel and Bernussou, 2000) can indeed be applied to derive a procedure capable of handling the design of supplementary controllers in general (that is, either PSS-type controllers or SDCs for FACTS devices). Furthermore, it also includes an explicit formulation to ensure that the bandwidth of the resulting controllers is acceptable in practice, which is very important to avoid the amplification of high frequency noise signals in the controller input. These two features constitute the main contribution of this paper.

The paper is structured as follows: section 2 reviews the fundamentals of the control methodology proposed in (Ramos, Alberto and Bretas, 2004a), and shows why it is not applicable to the design of SDCs for FACTS devices; section 3 presents the proposed control technique, which is based on the ideas developed in (Ramos, Alberto and Bretas, 2004a); section 4 summarizes the complete design procedure; results of the tests performed using the proposed procedure are presented in section 5, and section 6 presents the conclusions and the final comments.

2 THE PREVIOUSLY PROPOSED CONTROL METHODOLOGY

This chapter presents a review of the main fundamentals about the previously proposed control methodology, which was developed in (Ramos, Alberto and Bretas, 2004a) for designing PSS-type controllers.

2.1 System and Controller Models

The power system model is represented in (Ramos, Alberto and Bretas, 2004a) by a set of nonlinear differential and algebraic equations in the form

where x(t) ∈ ℜn is a vector composed of the system state variables, z(t) ∈ ℜm is a vector of algebraic variables, u(t) ∈ ℜp is a vector with the system control input, and y(t) ∈ ℜq is the vector with the system outputs.

Usually, the analyses of local and inter-area oscillations and design of damping controllers for power systems are carried out by means of linear models (Chaudhuri and Pal, 2004). The process often involves linearizing the system equations (1)-(3) around a specific equilibrium point. The vector of algebraic variables z is eliminated by isolating it and substituting the result in the linearized equation obtained from (1). Using this process, a linear representation of the system in the vicinity of the equilibrium point is obtained, which can be described in state space form by

A control structure based on dynamic output feedback is adopted in (Ramos, Alberto and Bretas, 2004a). Such control structure is necessary due to difficulties in obtaining measurements of all model state variables in the real system. The proposed controller based on dynamic output feedback is represented by

where xC (t) ∈ ℜn is a vector with the controller states. The dynamic behavior of the controller, as a function of the plant output y(t), is described by (6). The control input for the system u(t) is produced by (7) with the application of the matrix gain CC to the states generated by the controller.

2.2 Control Problem Formulation

From the connection of the power system model (4)-(5) with the damping controller model represented by (6)-(7), the closed-loop system is given by

where

and (t) ∈ ℜ2n is a vector with the states of both the system and the controllers. Notice that AC, BC, and CC are the matrix variables to be determined by the design procedure.

Using the Lyapunov stability theory for linear systems, the problem of stabilizing the system (4)-(5) by the output feedback controller (6)-(7) can be solved (Skelton, Iwasaki and Grigoriadis, 1998) if the controller matrices AC, BC, CC and a matrix = T > 0 (with appropriate dimensions) are found, such that

This idea constitutes the core of most design procedure based on Lyapunov stability theory for linear systems. However, this simple formulation is not adequate to the design of damping controllers for power systems, because:

(i) The controller designed using (10) may not provide a satisfactory damping to the oscillation modes of interest since no performance index is considered in that formulation;

(ii) since the linear approximation (4)-(5) is valid only in a vicinity of a particular operating point, the robustness of the controller with respect to the variations in the operating conditions of the system is very limited;

(iii) inequality (10) is a Bilinear Matrix Inequality (BMI) on the problem matrix variables ( AC, BC, and CC and ), whose solution may require a large computational effort.

Each of these problems was addressed in (Ramos, Alberto and Bretas, 2004a) using suitable extensions of the core idea expressed in (10). The next subsections present a brief overview of these extensions.

2.3 Performance Index

In (Ramos, Alberto and Bretas, 2004a), a performance criterion (in the form of a minimum damping ratio to be achieved for all modes of the closed loop system) is included in the control formulation to ensure an acceptable performance for the controlled system. This inclusion is done using the Regional Pole Placement (RPP) technique (Chiali, Gahinet and Apkarian, 1999), which consists in the definition of a region for pole placement in the complex plane where the performance criterion is fulfilled. This region is defined by ζ > ζ0 , and it can be viewed in Fig. 1, where ζ0 is the desired minimum damping ratio for the poles of the closed loop system.


The pole placement criterion expressed in Fig. 1 can be fulfilled if matrices AC, BC, CC and = T > 0 are found such that the BMI (Ramos, Alberto and Bretas, 2004a)

is satisfied, where θ = cos- 1(ζ0 ) and matrices and were previously defined.

2.4 Performance Robustness

The uncertainties in the power system model with respect to the variations of the operating conditions were treated in (Ramos, Alberto and Bretas, 2004a) using the polytopic modelling technique (Boyd et al., 1994)(Ramos, Bretas and Alberto, 2002). In this technique, instead of using a single Linear Time Invariant model, the system is modeled by a Polytopic Linear Differential Inclusion in the form

where (a) ∈ Ω and Ω is a closed subset of a matrix space with dimension2n × 2n, which is formed by the convex combination of a set of predefined matrices i. Notice that each i comes from a closed loop representation of the power system in the form (9), which is related to a linearized model around a particular operating condition. Such operation point may be chosen, for example, from the load curve of the system, complying with the typical practice in the industry. Set Ω can be written as

It can be observed in (13) that set Ω is a polytope in the matrix space and matrices

i are the vertexes of this polytope, being L the number of operating points used for the construction of the polytope.

Using both polytopic modelling and RPP technique in the design procedure, associated with the quadratic stability theory (Boyd et al., 1994), an adequate damping of the oscillation modes of the system is guaranteed. This is achievied not only for the operating points used as vertexes in the construction of the polytopic model, but also for all the operating points that can be generated from the convex combination of these operating points (Ramos, Bretas and Alberto, 2002)(Barmish, 1985). Such statement is satisfied solving the following BMIs on the matrices variables AC, BC, CC and (which must be symmetric):

where

i = ,i = 1,...,L and θ = cos-1(ζ0).

The matrix inequalities (14)-(15) are BMIs on the problem matrix variables AC, BC, CC and . However, such matrices inequalities can be transformed to a set of LMIs using a two-step separation procedure (Oliveira, Geromel and Bernussou, 2000). This procedure consists basically in a parameterization and a change of some matrix variables of the control formulation (14)-(15), allowing the solution of the inequalities by two sequential steps. The first one involves a choice of matrix CC and the second one consists in finding matrices AC and BC using the previous choice of CC.

However, as originally proposed in (Ramos, Alberto and Bretas, 2004a), this design procedure was conceived to work over polytopic models whose vertices were comprised by linear models in the form (4)-(5), leading to the closed loop formulations in the form (8). These closed loop formulations are not suitable for the problem of SDC design for FACTS devices, because the linearized models of power systems containing these devices usually exhibit a direct feedthrough matrix D in the output equation. For this reason, it was argued in (Xue, Zhang and Godfrey, 2006) that the ideas supporting the procedure proposed in (Ramos, Alberto and Bretas, 2004a) may not be applied to design SDCs for FACTS devices. The next section proves this statement wrong, and proposes a new formulation (which uses the main ideas from (Ramos, Alberto and Bretas, 2004a)) which is not only capable of designing such controllers, but is also capable of handling constraints on the controller bandwidths, which are very important from the practical point of view.

3 THE PROPOSED NEW CONTROL FORMULATION

In order to be able to handle the design of SDCs for FACTS devices, the new control formulation proposed in this paper deals with generalized power system models with matrices A, B, C and also a non-zero matrix D.

For that, consider again the linearized power system model described by (4)-(5). The time derivative of active power measurements is used as input control signal. This signal exhibits a great observability of the inter-area oscillations of interest and, additionally, its derivative effect prevents the controller from acting in steady-state (Ramos, Alberto and Bretas, 2004a)(Ramos, Alberto and Bretas, 2004b). Therefore, the practical requirement (iii) in the list presented in section I is fulfilled. The time derivative of the output y(t) can be written as

where = CA and = CB are matrices with dimensions determined by A, B and C. Besides, is a non-zero matrix for the FACTS devices due to the sensibility of the line active power flow to variations in the FACTS controllable parameters (as for example, the equivalent reactance for a TCSC device). It is important to point out that the definition of the new output as the time derivative of the previous one does not require the implementation of an ideal derivative block. As explained in (Ramos, Alberto and Bretas, 2004b), this derivative action can be later incorporated into the controller transfer function to compose a washout block, which is typical of PSSs and SDCs for FACTS devices.

With this new definition for the output, the dynamics of the controller can now be described by

From the connection of the power system model (4) and (16) with the damping controller model (17)-(7), the vertices of the polytope for the controlled system with general power system models described by the set (A, B, , ) will be given by

for i = 1, ..., L.

Furthermore, as mentioned earlier, an additional practical requirement is included in the control formulation to ensure that the controller bandwidth remains within acceptable limits. With this inclusion, the new region of the complex plane used for the pole placement is shown in the Fig. 2 as region D, which is delimited by a circle with radius r and a conic sector defined by angle θ. So, such region ensures a minimum damping ratio ζ0 = cosθ (ensuring the oscillation modes are adequately damped) and a maximum natural oscillation frequencyw = rsinθ (ensuring that the closed loop system has acceptable bandwidth) for the poles of the polytopic closed loop model.


The matrices inequalities related to the polytopic modelling (considering the generalized power system model) and the RPP technique with the constraints shown in Fig. 2, are given by (Chiali, Gahinet and Apkarian, 1999)

where

i = , i = 1,...,L, θ = cos - 1(ζ0 ) and r is a scalar.

So, if matrices AC, BC, CC of the proposed controller and also a matrix = T > 0 (defining an appropriate Lyapunov function) are found, such that (19) to (21) are satisfied, the poles of the controlled system are confined into the region D of the complex plane, not only for the operating points used in the construction of the polytopic system, but also, for all the operating points that can be generated from the convex combination of the L adopted operating points.

The next section shows how to use the two-step procedure in (Oliveira, Geromel and Bernussou, 2000) to transform the set of BMIs (19)-(21) into a set of LMIs which corresponds to the generalized control formulation proposed in this paper.

3.1 The Two-step Separation Procedure

The concepts and procedures described in this section are derived from the ideas presented in (Oliveira, Geromel and Bernussou, 2000). The first stage of the separation procedure consists in setting up a state feedback gain that stabilizes the polytopic system with the pole placement objectives discussed previously. For that, it is possible to find a state feedback gain Kf = LY- 1 solving the following LMIs in the matrices variables L and Y (Ramos, Alberto and Bretas, 2004a):

where i = 1,...,L and r is a scalar. Then, the first step of the separation procedure is concluded defining C : = Kf as being the output matrix of the proposed damping controller.

For the second step of the separation procedure, considers the BMIs (19) to (21). It is possible to partitioned the symmetric matrix and its inverse - 1 according to the dimensions of the system and the controller, as follows

where X, XC, Y, YC, U ∈ ℜnxn. Now, let T ∈ ℜ2n×2n a matrix defined by

where the dimensions of the submatrices are implicitly determined by .

Moreover, the following changes of variables are carried out

where the dimensions of the matrices F, P and S are implicitly determined by the transformations.

Now, the BMIs (19)-(21) can be transformed into a set of LMIs. For that, multiply these BMIs on the right and the left by = diag[T, T], introduce the new variables F, P, S and simplifies the expression by algebraic manipulations, remembering that

-1 = I. Solving the set of LMIs obtained by such development in the matrices variables F, P, S and X, the matrices AC and BC of the proposed damping controller can be calculated by (27), where U = P - X. The set of LMIs are given by

where

ki = i + i
C, (i = 1,...,L), with C calculated a priori by (22)-(3.1).

The next section presents the complete design procedure based on the developments described previously.

4 THE DESIGN PROCEDURE

The design procedure is divided in three stages: (i) construction of the polytopic model; (ii) calculation of the state feedback gain matrix of the controller (CC) and; (iii) calculation of the matrices that describe the controller dynamics (matrices AC and BC ). Each stage is described in this section.

4.1 Construction of the Polytopic Modelling

The first step of the controller design procedure consists in choosing some typical operating points of the system to obtain the matrices

i (i = 1,...,L) that define the vertexes of the polytopic model. The steps for carrying out the first stage are:

(i) Build the power system model as a set of nonlinear differential and algebraic equations in the form (1)-(3);

(ii) Linearize the system equation (1)-(3) around L equilibrium points and after the network reduction (which is required to eliminate the vector of algebraic variables z), the L linear systems are obtained in the space state form which will constitute the vertexes, as in (12), of the polytope Ω.

4.2 Calculation of the State Feedback Gain Matrix of the Controller (Matrix CC)

After the first stage, the purpose of the two following stages is to design a supplementary damping controller based on dynamic output feedback structure and defined by matrices AC, BC and CC. This controller must stabilize the polytope Ω while fulfilling a minimum damping ratio and a maximum natural oscillation frequency for all modes of the closed loop polytopic model. In this design stage, the state feedback gain matrix of the controllers (CC) is determined by means of the solution of a set of LMIs written for the polytope vertexes. These steps can be carried out in the following way:

(i) Define the minimum damping ratio ζ0 = cosθ and a maximum frequencywm = rsinθ. Therefore, a region in the complex plane defining the minimum acceptable performance index is specified for all the oscillation modes of the polytopic system (according to Fig. 2);

(ii) build the computational representation of the matrix variables L and Y. The matrix Y must be symmetric with dimension n × n and the matrix L must be rectangular with dimension p × n. The set of LMIs (22)-(24) must be structured and solved for the variables L and Y;

(iii) after determining the variables L and Y, the state feedback gain matrix CC can be calculated by C = LY- 1.

In the next stage, the matrices AC and BC are calculated with the previously designed matrix CC.

4.3 Calculation of the Matrices AC and BC

In the last stage, the matrices AC and BC are calculated by means of the solution of a new LMI set established in the polytope vertexes. To do so, the following steps must be executed:

(i) Build the computational representation of the new matrices variables F, P, S and X, with dimensions n×n, n×n, n×q and n×n, respectively, and solve the set of LMIs (28)-(30) in these variables;

(ii) After finding F, P, S and X, the matrices AC and BC can be calculated by AC = U-1ST and BC = U-1F, where U = P - X.

After concluding the three design stages, the matrices AC , BC and CC which define the structure of the SDC for the FACTS device are obtained. Such controller can also be represented in the transfer function form obtained by

With the purpose of implement the transfer function (27) without using the time derivative of the output Δy obtaining the desired time derivative of the line active power (without the inclusion of an ideal derivative block) as input control signal, it is possible to rewrite (31) in the zeros/poles/gain form, as the following relation shows (Ramos, Martins and Bretas, 2005):

where K is the gain, while p and z are, respectively, the number of poles and zeros of the controller. The parameter Tw is equal to -1/ph, where ph must be chosen as the real pole placed closest to the origin by the controller design procedure. Since that Δu = (s = s(sy, we can implement the designed controller from the active power measurements by:

5 TESTED SYSTEM

To demonstrate the effectiveness of our proposed procedure, tests were carried out on a 16-machine, 5-areas system, shown in Fig. 3. This is a reduced order model of the New England and New York interconnected system. The first nine machines (G1 to G9) are the generators associated with the New England Test System (NETS), while G10 to G13 are the generators of the New York Power System (NYPS). Also, G14 to G16 are representing three equivalent areas neighboring connected to the NYPS.


In the adopted multimachine model, all the generators were described by a sixth order model that considers the swing equations and the transient and subtransient effects in d and q axes (Anderson and Fouad, 1994).

Also, the machines were equipped by a first order model of a static type AVR (thyristor controlled without transient gain reduction) with a gain equal to 50 and a constant time of 0.01s. The transmission system was modeled as a passive circuit by means of algebraic equations and the system loads were modeled as constant impedances. The data for bus, lines and machines were taken from (Pal and Chaudhuri, 2005).

The generators G2, G3, G5, G7, G9, G10, G11, G12,G14 and G15 are equipped with a speed input PSS- type controller to ensure adequate damping of its local modes. Such damping controllers were designed by a classical control technique based on eigenvalues placement using transfer function residues (IEEE Power System Engineering Committee, 1999).

Since our main purpose is to design SDCs for FACTS devices, we chose one type of such devices that is regarded as a highly effective solution to improve damping of inter-area oscillations (a task that PSS sometimes cannot perform with similar effectiveness): the well-know Thyristor Controlled Series Capacitor (TCSC). In our application, the TCSC is represented by a first order linear model (Del Rosso, Canizares and Dona, 2003) (which is a typical model used in small-signal stability studies). The block diagram of the adopted TCSC with an SDC is given in Fig. 4.


In Fig. 4, ΔXTCSC is the deviation of the equivalent TCSC reactance with respect to the nominal value, ΔXref is the reference for the desired reactance deviation (from its nominal value) in steady state, ΔXsup is the stabilizing signal from the proposed supplementary controller and TTCSC is the device time constant.

Two TCSC devices were placed in the system with the purpose of improving the stability of inter-area oscillation modes, as well as increasing the active power transfer capacity among the power systems areas. One of them was installed in the line connecting buses #60 and #61 and the other in the line connecting buses #18 and #49. Hence, the one is responsible to raise the active power transfers capacity between areas #2 and #5. The compensation of both TCSCs (in steady-state) corresponds to 50% of the impedance of their respective lines.

All the small-signal stability analyses in this paper were carried out for a daily load curve, which is shown in Fig. 5. The stability of local and, especially, inter-area modes were investigated in twenty-four operating points, each one equivalent to an hour of the day. The data for a particular load level (which was assumed, in this paper, as the operating conditions at 3 p.m) were taken from (Pal and Chaudhuri, 2005). The other operating points were obtained using percentual variations (as shown in Fig. 5) of the system loads with respect to the operating conditions at 3 p.m. The generators were redispached in each of these points, sharing portions of total load variation in a direct proportion of their respective inertia constants. It was also assumed (to comply with the usual practice in power systems) that each area is responsible for supplying its own load variations and, therefore, the active power flows among the areas were kept constant for all operating conditions.


The eigenvalue analysis shows (for all considered operating conditions) that the system without the inclusion of SDCs for the TCSCs have all the local modes and also two inter-area modes adequately damped (corresponding to a damping ratio greater than 5%, which is typically accepted as an indicator of satisfactory power system dynamic behavior). These results for the inter-area modes are shown in Table 1. As it can be seen, modes 3 and 4 are the well damped ones. On the other hand, mode 1 exhibits an unacceptable damping ratio in the operating conditions from 7 a.m to 10 p.m, while mode 2 is poorly damped for all the analyzed daily load curve points. The frequency of each oscillation mode is approximately (since it changes with variations in the operating conditions) 0.74 Hz, 0.55 Hz, 0.80 Hz and 0.42 Hz, for modes 1, 2, 3 and 4, respectively.

The participation factors analysis shows that mode 1 is most observable in the generators located in areas #1 and #2, while modes 2 to 4 are related to generators located in areas #2, #3, #4 and #5. Therefore, the TCSC equipped with a SDC and installed between areas #1 and #2 is responsible to improve the stability of mode 1. Similarly, the TCSC installed in area #2 and also equipped with a SDC must supply an additional damping to the mode 2. Both SDCs were designed (but not simultaneously) by the proposed control methodology.

The power system model has 140 states. In order to reduce the dimensions of the power system models used to design the proposed controllers, two simplified models were developed. The first one corresponds to the NETS model connected to a single equivalent generator (which is an equivalent representation of areas #2, #3, #4 and #5) and it was used to design the SDC for the TCSC installed between buses #60 and #61. This simplified model, i.e, the NETS model with the single equivalent generator, has 77 states and it is denoted in this paper by reduced model A. Similarly, the other simplified power system model corresponds to the NYPS model connected to a single equivalent generator representing area #1, and it was used to design the SDC added to the TCSC installed between areas #2 and #5. This model has 66 states and it is denoted by reduced model B.

To illustrate the accuracy among the full order model (with 140 states) and the reduced models A and B, Table 2 shows the inter-area modes calculated for each of these models in the operating conditions at 3 p.m. Notice that only mode 1 is observed in the reduced model A, since the dynamics among the generators of areas #2, #3, #4 and #5 are not being considered by such model. Comparing the inter-area modes calculated by each power system model, it is possible to verify that the reduced models A and B offer an acceptable approximation of the system dynamics of interest.

The proposed controllers were not designed simultaneously1 1 Although from a theoretical viewpoint there is no restriction for the simultaneous design of both controllers in this case using block-diagonal structures for the controller matrices, it was tried this simultaneous approach with several different block-diagonal choices but none of them produced satisfactory results. For this reason, it was chosen to apply this sequential design approach, which ended up producing better results in this case. , i.e., the SDC for the TCSC installed between areas #1 and #2 was designed using the reduced model A, while the SDC for the TCSC located between areas #2 and #5 was designed using the reduced model B. For both SDCs, the time derivatives of local active power measurements were used as input control signal. The operating points at 3 p.m and 4 p.m were used for the construction of the polytopic model adopted for the reduced model A, while operating points at 5 p.m and 6 p.m were used for the polytopic model of reduced model B. A minimum damping ratio of 5% (ζ0=0.05) and a maximum natural oscillation frequency of r = 20 rad/s was defined as an acceptable performance index for the controlled polytopic system.

The "feasp" solver, available in Matlab LMI Control Toolbox (Gahinet et al., 1995) was used to solve the set of LMIs related to the control problems. The time taken to generate the controllers was approximately 8 hours and 25 minutes for the SDC added to the TCSC installed between areas #1 and #2 and 4 hours and 37 minutes for the other SDC. Both set of LMIs were solved in a computer with a Pentium Dual Core 3.2 GHz processor and 2 GB of RAM.

One of the difficulties associated with the proposed design methodology is its requirement, due to the nature of the control problem formulation, that the order of the designed SDC must be equal to the order of the power system model. In the presented application, since the reduced power system models A and B have, respectively, 77 and 66 states, the resulting SDCs had also order 77 and 66. However, high order controllers are difficult to implement in practice and, for this reason, it is desirable to reduce the dimensions of the controllers designed by this proposed methodology.

To achieve the goal of producing a low order controller, the proposed procedure was combined with a final step of model order reduction. After a high order controller was designed, the balanced truncation method (Pal and Chaudhuri, 1995) was applied, reducing the dimension of the SDCs from order 77 and 66 to only order 5 for both controllers.

It is important to emphazise that the application of the balanced truncation method may modify the original poles and zeros obtained by the design procedure. This means that the poles and zeros of the reduced order controller may not satisfy the region for pole placement (Fig. 2). In this case, it is important to verify if the bandwidth of the reduced order controller remains within acceptable limits. The validation of the effectiveness of the reduced order SDCs was carried out by comparison of the frequency responses of the full and reduced order controllers and by quadratic stability analysis with regional pole placement constraints (using the formulation given by (21)-(22) and considering the same polytopes adopted in design stage). The transfer functions of the reduced order SDCs are presented in the appendixappendix.

The damping ratios of the inter-area modes for the system with the inclusion of the SDCs for the TCSCs in all twenty-four operating conditions corresponding to the daily load curve analyzed previously are shown in Table 3. These results were obtained considering the full order model of the power system, in which generator 13 was taken as the angular reference for the system model.

Such results were also compared with conventional SDCs based on phase compensation (Pal and Chaudhuri, 2005). The structure of these SDCs consists basically of a static gain, a washout filter and a phase compensation network (formed by two lead-lag blocks). The compensation angle used to determine the lead-lag parameters was determined using the transfer function residues calculated for the base case (Pal and Chaudhuri, 2005). The damping ratios of the inter-area modes for the system with the inclusion of the conventional SDCs for the TCSCs are shown in Table 4.

It was verified that the performance index obtained by the TCSCs equipped with the proposed SDCs is better than the minimum acceptable performance specified in the design stage. Notice that modes 1 and 2 present now a damping ratio varying from 11.9% to 16.66% and 9.53% to 10.97%, respectively. Additionally, the TCSC installed between areas #2 and #5 and equipped with the proposed SDC well improved the damping ratio of mode 4 as well. On the other hand, comparing the results shown in Tables 3 and 4, it can be seen that the performance index achieved by the conventional SDCs is smaller than the one obtained from the proposed SDCs. Indeed, for the operating conditions from 5 to 8 p.m., the damping ratios achieved by the conventional SDCs is smaller than 5%, and it is very difficult to manually tune these SDCs to achieve greater damping ratios under these conditions.

The results of the nonlinear simulation in three different operating conditions (at 6 p.m, 1 p.m and 3 a.m) with the proposed SDCs (and the conventional SDCs) are shown in Figs 6, 7 and 8. These simulations were carried out to validate the results of the linear analyses and the robustness requirement. The perturbation used to stimulate the inter-area modes was a three-phase solid fault in one of the lines connecting buses 47 and 48. The fault conditions were simulated after 2s for a duration of 80 ms (≈ 5 cycles in a 60 Hz system) followed by opening of the faulted line.




According to Figs. 6, 7 and 8, the TCSCs equipped with the designed SDCs presented a betted performance in comparison with the conventional SDCs. Notice that the performance of the proposed controllers was satisfactory for operating conditions that were not considered in the design stage (1 p.m and 3 a.m). This is a good indication of the robustness of the proposed controllers with respect to variations in the operating conditions. Additionally, the stabilizing signal provided by the SDC added to the TCSC placed between areas #1 and #2 was able to reduce the maximum valor of the active power at line #60-61 in the first oscillation occurred after the perturbation.

6 CONCLUSION

A robust control methodology structured in the form of linear matrix inequalities (LMIs) was presented for the design of SDCs for FACTS devices, with the purpose of improving the stability of inter-area oscillation modes. This required the development of a new formulation, based on the ideas explored by the authors in previous works, that is now capable of treating the models that arise when FACTS devices are placed in the power system. This new formulation is general enough to allow the design of either SDCs for FACTS devices or PSS-type controllers and also includes a further step of model order reduction, addressing the problem of controller order, which was until now a drawback of the previous proposition.

It is important to stress out that this paper proves that it is indeed possible to apply the ideas explored by the authors in their previous papers to the design of SDCs for FACTS devices, since this possibility was questioned in the past, as previously mentioned in the paper. Moreover, the treatment of the restrictions in the controller bandwidth is another advancement that comprises the set of contributions of this paper.

Given that the closed loop poles and zeros produced by the method may change when the controller order reduction is applied, the development of new procedures that enable the design of low-order controllers without requiring balanced truncation is one of the future directions of this research. Another predicted development is the imposition of bandwidth restrictions only to the controller transfer function, instead of the whole closed loop system, which may improve the feasibility of the control problem formulation.

Artigo submetido em 01/04/2008 (Id.: 00865)

Revisado em 10/11/2008, 30/12/2008

Aceito sob recomendação do Editor Associado Prof. Julio Cesar Stacchini

Souza

The transfer functions of the reduced model of the designed SDCs are given by

- SDC for TCSC installed between areas #1 and #2:

- SDC for the TCSC installed between the areas #2 and #5:

The transfer functions of the conventional SDCs are given by

- Conventional SDC for TCSC installed between areas #1 and #2:

- Conventional SDC for the TCSC installed between the areas #2 and #5:

  • Anderson, P. M. and Fouad, A. A. (1994). Power System Control and Stability, IEEE Press, Piscataway, USA.
  • Barmish, B.R. (1985). Necessary and Sufficient Conditions for Quadratic Stabilizability of an Uncertain System, Journal of Optimization Theory and Applications 46(4): 399-408.
  • Boyd, S., El Gahoui, L., Feron E., et al (1994). Linear Matrix Inequalities in System and Control Theory, SIAM, Philadelphia, USA.
  • Bomfim, A. L. B., Taranto, G. N. and Falcao, D. M. (2000). Simultaneous Tuning of Power System Damping Controllers using Genetic Algorithms, IEEE Transactions on Power Systems 15(1): 163-169.
  • Chaudhuri, B. and Pal, B. (2004). Robust Damping of Multiple Swing Modes Employing Global Stabilizing Signals with a TCSC, IEEE Transactions on Power Systems 19(1): 499-506.
  • Chiali, M., Gahinet, P. and Apkarian, P. (1999). Robust Pole Placement in LMI Regions, IEEE Transactions on Automatic Control 44(12): 2257-2270.
  • Del Rosso, A. D., Canizares. C. A. and Dona, V. M. (2003). A Study of TCSC Controller Design for Power System Stability Improvement, IEEE Transactions on Power Systems 18(4): 1487-1496.
  • DeMello, F. P. and Concordia, C. (1969). Concepts of Synchronous Machine Stability as Affected by Excitation Control, IEEE Transactions on Power Apparatus and Systems 88(4): 316-329.
  • Gahinet, P., Nemirovski, A., Laub, A. J., et al. (1995). LMI Control Toolbox User's Guide, The Mathworks Inc, Natick, USA.
  • Gama, C. (1999). Brazilian North-South Interconnection Control-application and Operating Experience with a TCSC, IEEE PES Winter Meeting 2: 1103-1108.
  • Handschin E., Schnurr N. and Wellssow W.H. (2003). Damping Potential of FACTS Devices in the European Power System, IEEE PES General Meeting 4
  • Hingorani, N. G. and Gyugyi L. (2000). Understanding FACTS: Concepts and Technology of Flexible AC Transmission Systems, IEEE Press, New York, USA.
  • IEEE Power System Engineering Committee (1999). Eigen analysis and Frequency Domain Methods for System Dynamic Performance, IEEE special publication 90TH0292-3-PWR.
  • Kundur, P., Paserba, J., Ajjarapu V., et al. (2004). Definition and Classification of Power System Stability, IEEE Transactions on Power Systems 19(2): 1387-1401.
  • Larsen, E. V. and Swann, D. A. (1981). Applying power systems stabilizers, parts i, ii, iii, AIEE Transactions on Power Apparatus and Systems, 100(6): 3017-3046.
  • Oliveira, M. C, Geromel J. C. and Bernussou, J. (2000). Design of Dynamic Output Feedback Decentralized Controllers via a Separation Procedure, International Journal of Control 73(5): 371-381.
  • Pal, B. and Chaudhuri, B. (2005). Robust control in power systems, Springer Science+Business Media, New York, USA.
  • Paserba, J.J. (2004). How FACTS Controllers Benefit AC Transmission Systems, IEEE PES General Meeting 2: 1257-1262.
  • Ramos, R. A., Alberto, L. F. C. and Bretas, N. G. (2004a). A New Methodology for the Coordinated Design of Robust Decentralized Power System Damping Controllers, IEEE Transactions on Power Systems 19(1): 444-454.
  • Ramos, R. A., Alberto, L. F. C. and Bretas, N. G. (2004b). Decentralized Output Feedback Controller Design for the Damping of Electromechanical Oscillations, International Journal of Electrical Power & Energy System 26(3): 207-219.
  • Ramos, R. A., Martins, A. C. P. and Bretas, N. G. (2005). An Improved Methodology for the Design of Power System Damping Controllers, IEEE Transactions on Power Systems, 20(4): 1938-1945.
  • Ramos, R. A., Bretas, N. G. and Alberto, L. F. C. (2002). Damping Controller Design for Power Systems with Polytopic Representation for Operating Conditions, IEEE PES Winter Meeting 1
  • Skelton, R. E., Iwasaki, T. and Grigoriadis, K. (1998). A Unified Algebraic Approach to Control Design, Taylor & Francis, London, England.
  • Tsai, H. C., Chu, C. C. and Chou, Y. S. (2004). Robust Power System Stabilizer Design for an Industrial Power System in Taiwan using Linear Matrix Inequality Techniques, IEEE PES General Meeting 2
  • Xue, C. F., Zhang, X. P. and Godfrey, K. R. (2006). Design of STATCOM Damping Control with Multiple Operating Points: a Multimodel LMI Approach, IET Generation, Transmission and Distribution, 153(4): 375-382.

appendix

  • 1
    Although from a theoretical viewpoint there is no restriction for the simultaneous design of both controllers in this case using block-diagonal structures for the controller matrices, it was tried this simultaneous approach with several different block-diagonal choices but none of them produced satisfactory results. For this reason, it was chosen to apply this sequential design approach, which ended up producing better results in this case.