Calculation of parameter ranges for robust gain tuning of power system controllers

Cálculo de faixas de parâmetro para o ajuste robusto do ganho de controladores de sistemas de potência

Abstracts

This work proposes a computational tool to assist power system engineers in the field tuning of power system stabilizers (PSSs) and Automatic Voltage Regulators (AVRs). The outcome of this tool is a range of gain values for theses controllers within which there is a theoretical guarantee of stability for the closed-loop system. This range is given as a set of limit values for the static gains of the controllers of interest, in such a way that the engineer responsible for the field tuning of PSSs and/or AVRs can be confident with respect to system stability when adjusting the corresponding static gains within this range. This feature of the proposed tool is highly desirable from a practical viewpoint, since the PSS and AVR commissioning stage always involve some readjustment of the controller gains to account for the differences between the nominal model and the actual behavior of the system. By capturing these differences as uncertainties in the model, this computational tool is able to guarantee stability for the whole uncertain model using an approach based on linear matrix inequalities. It is also important to remark that the tool proposed in this paper can also be applied to other types of parameters of either PSSs or Power Oscillation Dampers, as well as other types of controllers (such as speed governors, for example). To show its effectiveness, applications of the proposed tool to two benchmarks for small signal stability studies are presented at the end of this paper.

Power system dynamics and control; small signal stability; power system stabilizer; automatic voltage regulator; robust control; linear matrix inequality


O presente trabalho propõe uma ferramenta computacional para auxiliar engenheiros de sistemas de potência no ajuste em campo de controladores de amortecimento e reguladores automáticos de tensão. A abordagem proposta gera faixas de valores de parâmetros para o ajuste em campo dos controladores do sistema. As faixas de valores geradas teoricamente garantem a estabilidade para o sistema em malha fechada. Estas faixas de valores são dadas na forma de valores limites para os ganhos estáticos dos controladores de interesse, de maneira que o engenheiro responsável pelo ajuste em campo dos controladores tenha garantia da estabilidade do sistema durante o ajuste do ganho do controlador. Esta característica da abordagem proposta é altamente desejavel do ponto de vista prático, pois a etapa de comissionamento de controladores de amortecimento e reguladores automáticos de tensão sempre envolve algum reajuste dos ganhos dos controlares, devido às diferenças entre o modelo nominal e o comportamento real do sistema. Considerando essas diferenças como incertezas no modelo, a ferramenta proposta é capaz de garantir estabilidade para o modelo incerto usando uma abordagem baseada em desigualdades matriciais lineares. A metodologia proposta pode ser também aplicada para o ajuste de outros tipos de parâmetros de controladores de amortecimento, assim como para o ajuste de outros tipos de controladores (por exemplo, reguladores de velocidade). Dois modelos de sistemas de potência tipicamente utilizados em estudos de estabilidade são considerados para a aplicação e avaliação da ferramenta proposta.

Dinâmica e controle de sistemas de potência; estabilidade a pequenas perturbações; estabilizador de sistemas de potência; regulador automático de tensão; controle robusto; desigualdade matricial linear


SISTEMAS ELÉTRICOS DE POTÊNCIA

Calculation of parameter ranges for robust gain tuning of power system controllers

Cálculo de faixas de parâmetro para o ajuste robusto do ganho de controladores de sistemas de potência

Ricardo Vasques de OliveiraI; Rodrigo Andrade RamosII; Newton Geraldo BretasII

IDepartamento de Engenharia Elétrica - Universidade Tecnológica Federal do Paraná, Via do Conhecimento, Km 1, 85503-390, Pato Branco, PR, Brasil.vasques@utfpr.edu.br

IIDepartamento de Engenharia Elétrica - Escola de Engenharia de São Carlos - USP Av. Trabalhador São-carlense, 400, 13566-590, São Carlos, SP, Brasil. ramos@sc.usp.br, ngbretas@sc.usp.br

ABSTRACT

This work proposes a computational tool to assist power system engineers in the field tuning of power system stabilizers (PSSs) and Automatic Voltage Regulators (AVRs). The outcome of this tool is a range of gain values for theses controllers within which there is a theoretical guarantee of stability for the closed-loop system. This range is given as a set of limit values for the static gains of the controllers of interest, in such a way that the engineer responsible for the field tuning of PSSs and/or AVRs can be confident with respect to system stability when adjusting the corresponding static gains within this range. This feature of the proposed tool is highly desirable from a practical viewpoint, since the PSS and AVR commissioning stage always involve some readjustment of the controller gains to account for the differences between the nominal model and the actual behavior of the system. By capturing these differences as uncertainties in the model, this computational tool is able to guarantee stability for the whole uncertain model using an approach based on linear matrix inequalities. It is also important to remark that the tool proposed in this paper can also be applied to other types of parameters of either PSSs or Power Oscillation Dampers, as well as other types of controllers (such as speed governors, for example). To show its effectiveness, applications of the proposed tool to two benchmarks for small signal stability studies are presented at the end of this paper.

Keywords: Power system dynamics and control, small signal stability, power system stabilizer, automatic voltage regulator, robust control, linear matrix inequality.

RESUMO

O presente trabalho propõe uma ferramenta computacional para auxiliar engenheiros de sistemas de potência no ajuste em campo de controladores de amortecimento e reguladores automáticos de tensão. A abordagem proposta gera faixas de valores de parâmetros para o ajuste em campo dos controladores do sistema. As faixas de valores geradas teoricamente garantem a estabilidade para o sistema em malha fechada. Estas faixas de valores são dadas na forma de valores limites para os ganhos estáticos dos controladores de interesse, de maneira que o engenheiro responsável pelo ajuste em campo dos controladores tenha garantia da estabilidade do sistema durante o ajuste do ganho do controlador. Esta característica da abordagem proposta é altamente desejavel do ponto de vista prático, pois a etapa de comissionamento de controladores de amortecimento e reguladores automáticos de tensão sempre envolve algum reajuste dos ganhos dos controlares, devido às diferenças entre o modelo nominal e o comportamento real do sistema. Considerando essas diferenças como incertezas no modelo, a ferramenta proposta é capaz de garantir estabilidade para o modelo incerto usando uma abordagem baseada em desigualdades matriciais lineares. A metodologia proposta pode ser também aplicada para o ajuste de outros tipos de parâmetros de controladores de amortecimento, assim como para o ajuste de outros tipos de controladores (por exemplo, reguladores de velocidade). Dois modelos de sistemas de potência tipicamente utilizados em estudos de estabilidade são considerados para a aplicação e avaliação da ferramenta proposta.

Palavras-chave: Dinâmica e controle de sistemas de potência, estabilidade a pequenas perturbações, estabilizador de sistemas de potência, regulador automático de tensão, controle robusto, desigualdade matricial linear.

1 INTRODUCTION

The reliability and performance of power systems, in transient and steady-state conditions, strongly depend on the design and field tuning of the system controllers (stabilizers, automatic voltage regulators, speed governors, and so on). In most cases, power system controllers, even when designed by methodologies that ensure some level of robustness with respect to variations of the system operating conditions, require additional tuning during the commissioning stage in order to provide an acceptable performance for the closed loop power system. This retuning may be necessary, for example, due to normal changes in the operating conditions of the system. The topology and the typical daily load curve of power systems may naturally change along the time, which lead to the need for a field retuning of the controllers.

The need for the treatment of the mentioned power system characteristics has lead to the development of many approaches for the design and tuning of PSSs and damping controllers (Bomfim et al., 2000; Zanchin and Bazanella, 2003; Abdel-Magid and Abido, 2003; Zanetta and Cruz, 2005; Cai and Erlich, 2005; de Oliveira et al., 2010a; Gurrala and Sen, 2010; Jabr et al., 2010; Furini et al., 2011). However, most design and tuning procedures based on robust control techniques proposed up to now do not consider the need ofa field retuning of the designed controllers.

It is worth mentioning that the engineer who carries out the controller (PSS, AVR, and so on) retuning in field tests is not usually the same engineer who designed it. In this way, the engineer responsible for the controller retuning may not know the theoretical limits within which the controller parameters can be changed to ensure the desired small-signal stability margin for the system. Furthermore, the commissioning of power system controllers is typically an empirical procedure which consists in introducing small changes in the static gain of the controller and carefully monitoring the power station dynamics in the control room until an acceptable response is obtained.

In this context, this work proposes a tool to assist power system engineers in retuning and/or commissioning of PSSs and/or AVRs. This tool provides theoretical limits for the engineer to carry out a safe field retuning, thus avoiding that the new gain settings threaten the power system reliability and stability. Using these theoretical limits, a range of values is provided, in such a way that any value within this range can be used in the retuning of the controller static gain, resulting in guaranteed closed loop stability from the theoretical viewpoint. It is also important to remark that a certain small-signal stability margin may be the chosen criterion for which a theoretical guarantee must be sought, and this is indeed the approach used in this paper, to comply with the typical practice in power system stabilizer design and assessment. This guarantee is obtained using a formulation based on linear matrix inequalities (LMIs).

The methodologies for the tuning of PSS usually supply fixed values for the parameters to be tuned. Abdel-Magid and Abido (2003), Cai and Erlich (2005), and Jabr et al. (2010), for example, have presented procedures to determine fixed values for the parameters of the PSS to be tuned (i.e., fixed settings for the PSS parameter). Different from the typical tuning approaches, this paper proposes a methodology that provides continuous parameter ranges for the field tuning of PSS. Besides, the approach proposed in this paper is also applicable to AVR and other kinds of power system controllers.

The paper is structured as follows. Section 2 depicts the fundamentals employed in the formulation of the proposed tool and Section 3 presents the computational tool itself. The evaluation of the proposed tool is carried out by applying it to two benchmark test systems in Section 4, and Section 5 presents the conclusions taken from this evaluation and from the overall approach presented in this paper.

2 FUNDAMENTALS OF THE PROPOSED TOOL

The development of the computational tool proposed in this work was based on the theory of Affine Parameter-Dependent Lyapunov Functions, particularly those that can be put in the form of LMIs (Gahinet et al., 1996; Oliveira and Peres, 2005). This section presents the fundamentals of this development to enable a better comprehension of the overall mechanism of the proposed tool.

Studies on power system dynamics are usually based on a set of differential-algebraic equations of the form

where is the system state vector, ũ ∈ Rp is the control input vector, ỹ ∈ Rq is the measured output, and zRm is the vector with the algebraic variables. However, when it comes to controller design and small signal stability studies in power systems, models obtained from the linearization of equations (1)-(3) are usually employed.

The equation resulting from the linearization of (2) is typically eliminated by substituting it into the equations resultant from (1) and (3). The resulting linearized model of a power system can be represented by

In (4)-(5), xRn corresponds to the deviation from an equilibrium point xe of (1) and (3). In a similar way, uRp and yRq represent the deviations from ũe and ye, respectively. Linear controllers for power systems can be represented by models in the form

where xcRs is the vector with the controller state variables. The closed-loop model of the controlled power system, obtained from the connection of (4)-(5) with (6)-(7), considering the controller parameter dependence, can be represented by

where x = [x xc]T and

In (8), ρ ∈ Rk is a vector with the controller parameters to be tuned. The controller parameters are considered to be time invariant (i.e., = 0) in this work, given that the static gains of power system controllers are usually fixed after the commissioning stage. Matrix (ρ) is affine parameter-dependent, that is,

where are constant matrices. Since each ρ, for i = 1,...,k, is associated with one of the controllers to be commissioned or retuned, the coefficients of the matrix describe the manner in which the i-th parameter affects the dynamics of the whole system.

The developments in this paper are based on the assumption that each parameter ρi belongs to a known range defined by its extreme limits pi. and , that is,

where pi. is the lower bound and is the upper bound for the range of values of parameter ρi. Both bounds are specified in advance in order to define an acceptable uncertainty range for the parameter of the controller to be tuned. These specified bounds for the parameter vector describe an hyper-rectangle in Rk , whose the vertices are given by

A quadratic Lyapunov function for (8) may be written as

where P(ρ) is also an affine function given by

Sufficient conditions for stability of (8) can be written in the form of LMIs. Defining

where ρavg is the average value of the parameter vector, it is possible to state (Gahinet et al., 1996) that the system (8) is affinely quadratically stable if is stable and

for all 0 and i = 1, ...,k. From (10) and (14), inequality (17) may be rewritten as

for i = 1, ...,k. It is worth mentioning that the scalar µ is included in the LMI formulation to reduce control formulation conservatism and to avoid numerical problems in the solver employed to resolve the LMIs.

From the controller tuning viewpoint, it is mandatory that the variations in the operating conditions of the system are taken into account. Therefore, to comply with the typical practice in power systems, a number of linearized models (which can be extracted from the daily load curves, for example) in the form of (8) are employed in the formulation so the changes in the operating conditions are properly addressed. Taking multiple operating conditions into account, the system (8) can be rewritten in the form

where j = 1; · · · ;L,

and L is the number of operating conditions considered to generate the parameter range.

Furthermore, the typical practice in small-signal stability analysis and control of power systems dictates that a certain small-signal stability margin must be respected in the overall closed loop system (Gomes et al., 2003), to avoid that eigenvalues with very low damping ratio pose a threat to system stability with respect to variations in the operating conditions. The proposed tool can comply with this practice by means of the regional pole placement technique (Chilali et al., 1999; de Oliveira et al., 2010a). Using this technique, LMIs (16)-(18) are transformed into

for i = 1,...,k and j = 1,..., L. In (23), θ = cos-1ζ0, with ζ0 being the minimal damping ratio for the response modes of all power system models.

If a feasible solution to LMIs (22)-(24) is found, the resulting parameter range ensures that the eigenvalues of all the considered power system models (with the inclusion of the tuned controllers) will present damping ratios higher than ζ0.

3 DESCRIPTION OF THE PROPOSED COMPUTATIONAL TOOL

Classical phase compensation is the approach usually employed by the industry to design PSSs. The traditional structure of a phase compensator is shown in the block diagram in Fig. 1,with the washout block added to ensure zero gain in steady-state conditions. In Fig. 1, the subscript i denotes the i-th controller to be commissioned or retuned.


In this paper, two lead-lag blocks were used for each retuned PSS, which corresponds to Fig. 1 with nc = 2. In this work, yi corresponds to the speed deviation of the i-th system generator and ui is the i-th stabilizing signal applied to the reference of the AVR. This stabilizing control loop is a decentralized control loop, since it adopts a local measurement.

In order to include such a controller in the formulation (22)-(24) (more specifically in matrix

(ρ)j), the block diagram model showed in Fig. 1 was converted to its corresponding state-space model (6)-(7) (Further details about such model conversion may be found in de Oliveira et al. (2010a)).

The AVR has a significant impact on the small signal stasbility margin of power systems (Kundur, 1994; Machowski et al., 2008; Ramos, 2009). In this way, the tuning of this kind of regulator is quite important for the stability and reliability of power systems. In this study, the AVR is assumed as a first-order regulator, whose block diagram is given in Fig. 2. In this figure, Ke is the AVR static gain, Te is the AVR time constant, EFD is the voltage applied to the field circuit, Vt is terminal voltage, Vref is the reference voltage for the AVR, and u is the stabilizing signal from the PSS.


The computational tool proposed in this paper is based on the application of the fundamentals described in the previous section to the problem of generating a range of values for the Kpss_i and/or Ke_i static gains to be employed in the commissioning or retuning of the controllers. The parameter vector, presented in the formulation (22)-(24), is composed by the static gains of the controllers (ρi = Kpss_i or ρi = Ke_i).

These parameters were chosen because some operating conditions of power systems demand a retuning of the static gain of PSSs and/or AVRs to improve the system small-signal stability margin and avoid detrimental sustained oscillations in the operation of the corresponding generators.

As previously mentioned, the range of parameter values generated by the proposed tool ensures that the eigenvalues of each of the considered power system models with the retuned controllers will exhibit damping ratios higher than a pre-specified value (ζ0). To illustrate this feature, Fig. 3 presents a hypothetical range of Kpss values guaranteeing a damping ratio higher than 5% (Range A) for the eigenvalues of power system models in medium and high loading conditions. If a damping ratio higher than 10% is sought for the same conditions, usually the corresponding range of Kpss values (Range B) will be smaller than the previous one, as also illustrated in Fig. 3 (although this is not a rule, given the nonlinear nature of the power system model). According to Fig. 3, any value of Kpss = ρbelonging to the range A , for example, provides a PSS tuning which ensures a damping ratio higher than 5% for the eigenvalues of the power system models in the adopted loading conditions. The lower and upper bounds for the parameter range (, respectively) are generated by the tool proposed in this paper.


This proposed formulation allows two retuning strategies: the retuning of only one controller gain at a time or the simultaneous retuning of multiple controller gains. In the former strategy, the parameter range is calculated only for one controller, considering a multimachine system model with all the other controllers unchanged. This is the most common situation, where the controller of a single plant is being commissioned or retuned while the others are under operation, and is also the situation illustrated in Fig. 3.

The proposed formulation also allows the simultaneous calculation of parameter ranges for the retuning of multiple controllers at once. This corresponds to a less usual situation in which two or more controllers have to be commissioned at the same time. Fig. 4 illustrates hypothetical parameter ranges generated for two PSS gains to be retuned at once. Any value of Kpss belonging to parameter box A, for example, results in the fulfillment of a 5% minimum damping ratio criterion for all eigenvalues of each of the considered power system models.


As described in the previous section, these parameter ranges or boxes are calculated by means of an algorithm which involves LMIs (22)-(24). Roughly speaking, the algorithm consists in finding a feasible solution to the mentioned LMIs after setting the bounds for ρi parameters , choosing the system operating points of interest, and defining the desired minimum damping ratio for the eigenvalues of all power system models.

The algorithm begins with the choice of the controllers to be tuned, system operating conditions of interest, and desired minimum damping ratio. Given that commissioning or retuning of PSS/AVR gains are the problems being addressed in this paper, the nominal values of the parameter to be tuned (KPss0_i = ρi{o}/Ke0_i= ρi{O}) are given in advance by the outcome of the PSS/AVR design problem. The limits for ρi parameters are determined by means of small parameter changes (Δρ) as the algorithm iterates. The algorithm employs positive and negative changes with magnitude Δρ with respect to the nominal value of the ρi parameter (ρi{o}) in order to determine the new limits of the safe parameter range The value of Δρ may be chosen as a percentage of the nominal value of the ρi parameter.

The algorithm iterates until the solver employed to resolve the LMIs (22)-(24) fails to find a feasible solution to the problem. It is worth mentioning that for the vast majority of LMI solvers available to carry out this algorithm, failure to reach a solution to LMIs (22)-(24) does not necessarily imply the non-existence of a feasible solution for them.

As an empirical strategy to explore the nature of the PSS and AVR retuning problem, in order to search for a wider range of safe parameter values, the algorithm initially applies negative changes with respect to the nominal value of the ρi parameter. After finding a lower bound on the parameter range , positive changes are applied until the upper bound of the parameter range is found in a similar manner. The algorithm searches for the lower bound of the parameter range first due to the practical importance of this bound in the PSS adjustment, since the border between the acceptable and unacceptable small-signal stability margin for the system is usually reached with the lowest acceptable value of the PSS gain. On the other hand, the upper bound of the parameter range is usually chosen with the objective of avoiding saturation of the controller output and un-desired amplification of high-frequency dynamics. Fig. 5 illustrates this strategy. This example considers the retuning of only one PSS gain and a desired minimum damping ratio of 10%. In Fig. 5, ρi{0} is the nominal value of the parameter (i.e., nominal value of the static gain of the i-th PSS to be tuned), is the lower bound of the generated parameter range, is the upper bound of the generated parameter range. In other words, and are the lowest and highest values for the static gain that formally assure a damping ratio of 10% for the response modes of the power system with the tuned controllers.


Under the previously stated context, the computational tool for PSS and AVR gain retuning proposed in this paper consists in the following algorithm:

Step 1: Choose the controllers to be tuned, the operating conditions of interest, and the minimum damping ratio for the close loop system with the tuned controllers;

Step 2: Initialize the parameter bounds using the nominal value of the parameter ();

Step 3: Set k:=0 and choose the value of Δρ to be employed in the calculation of the parameter bounds and ;

Step 4: Set k=k+1 and determine the k-th update on the parameter bounds by (note that the upper bound is kept constant in this step);

Step 5: Minimize μ subject to LMIs (22)-(24);

Step 6: If a feasible solution was found in Step 5, return to Step 4; Otherwise, set ;

Step 7: Set k=k+1 and determine the k-th parameter bounds by (note that the lower bound is kept constant in this step);

Step 8: Minimize μ subject to LMIs (22)-(24);

Step 9: If a feasible solution was found in Step 8, return to Step 7;

Step 10: Set and stop; The resulting range of parameter values to be employed in the commissioning or retuning of the controllers is given by .

4 TESTS AND RESULTS

A number of tests have been performed to validate and evaluate the outcomes of the proposed tool. The tests were carried out based on two power system models which are benchmarks for small signal stability studies (Kundur, 1994; Rogers, 2000). After evaluating the convergence properties of the proposed algorithm, the robustness of the resulting ranges of parameter values with respect to the desired small-signal stability margin were validated by means of linear and non-linear analyses.

In the system representation used for these tests, the generators were described by a two-axis model (Kundur, 1994; Anderson and Fouad, 2003; Machowski et al., 2008). As aforementioned, the AVR is discribed by a first-order model. The transmission system was modeled as a passive circuit and the system loads were represented by constant impedances. The state-space model of the synchronous generator, with its AVR, as well as the model of the PSS are presentedin the appendix. However, it is important to emphasize that the proposed approach is general enough to cope with other kinds of system models, with no modifications in the overall algorithm of the computational tool.

In the test, due to practical considerations, the algorithm is finalized when the upper bound of the parameter range reaches values higher than 50 p.u. for the PSS gains and higher than 400 p.u. for the AVR gains, since high values of static gains may lead to the saturation of the controller output and undesired amplification of high-frequency dynamics. In the calculation of the parameter ranges for the PSSs, the magnitude of Δρ was chosen as 4 p.u. for the algorithm iterations.

The first adopted test system corresponds to a simple multi-machine power system which was chosen with the purpose of clarifying the application of the proposed tool. Its single line diagram is shown in Fig. 6 and its complete data can be obtained in Kundur (1994).


PSSs were placed only in the generators G1 and G3, which, according to a residue analysis (Pagola et al., 1989; Martins and Lima, 1990), is enough to properly damp the power system electromechanical modes. Table 1 shows the eigenvalues related to the electromechanical modes of the test system 1, in the base case condition, with the two PSSs. The PSSs placed in the test system 1 were taken from the literature and therefore details regarding the design of these controllers may be obtained in Kundur (1994). The eigenvalues of test system 1 in open-loop (without the PSSs) and the transfer functions of the system PSSs can be found in the appendix. It is important to emphasize that the design of PSS is not the aim of this work, since the proposed approach was formulated to generate robust parameter ranges for the field tuning of PSS previously designed by some design methodology.

A modal analysis (Perez-Arriaga et al., 1982; Verghese et al., 1982) of the test system 1 has revealed that the least damped mode (inter-area mode) can be damped by retuning either the PSS placed in generator G1 or G3. Based on this analysis, the approach was initially applied to generate a range of parameter values just for the PSS placed in generator G3. Three operating conditions were taken into account in this test: a base case operating condition (given by Kundur (1994)) and two other ones corresponding to variations of ±10% in the base case loads. These conditions are a simplified representation of the system operating under low, medium and high load conditions, for example. The active power variation was distributed among all system generators, weighted by their corresponding inertia constants.

A damping ratio of 5% was initially sought as desired small-signal stability margin for the power system with the retuned controller. The algorithm took 9 iterations and the resulting range of parameter value is depicted in Fig. 7. Each iteration, corresponding to the solution of LMIs (22)-(24), was carried out using the solver 'mincx', available in the LMI Toolbox of MATLAB (Gahinet et al., 1995), and the whole iterative process took about 18 minutes in a computer equipped with an i7 3.0 GHz processor and 8GB of RAM memory. This same computer is also employed in all the subsequent tests.


In the sequence, the parameter range was recalculated considering a damping ratio of 10% for the response modes of the power system with the retuned controller. The algorithm took about 10 minutes (corresponding to 5 iterations) to provide a solution. The resulting parameter range is also depicted in Fig. 7, considering also the algorithm evolution. Since the nominal value of the parameter (ρ1{o}= 20) is not enough to provide a damping ratio higher than 10% for the system response modes, the algorithm was initialized with the maximum allowable value of gain (ρ1{o}= 50). According to the parameter ranges presented in Fig. 7, it is possible to see that the engineer responsible for the PSS tuning may employ static gain values from 16 to 50 p.u. (30 to 50 p.u.) with the assurance that the system will present response modes with damping ratio higher than 5% (10%) for the response modes of the power system.

Fig. 8 shows the eigenvalues related to the closed-loop model of test system 1 with the retuned PSS, in the base case operating condition, considering five different values of static gain belonging to the parameter range that ensures damping ratio higher than 5% (gains belonging to parameter range A presented in Fig. 7). In Fig. 8, it is possible to verify that the five different values of static gain belonging to the generated parameter ranges have assured a damping ratio higher than 5% for the response modes of the power system.


These five gain values, together with other ten gain values, were also evaluated considering the other employed operating conditions. As expected, all the considered gain values provided the small-signal stability margin specified in the control problem formulation, in all operating conditions considered.

It is worth mentioning that depending on the amount of PSSs placed in the system and which PSSs will be tuned, a given small-signal stability margin may not be achieved by a retuning procedure. In such case, new PSSs or simultaneous retuning of various system PSSs may be required to accomplish the desired small-signal stability margin.

The approach was also employed to simultaneously generate the parameter ranges for the two PSSs of test system 1. This evaluation took into account the same operating conditions and minimum damping ratios (5% and 10%) employed in the previous test. The parameter ranges were determined by the algorithm in 9 iterations for damping ratio of 5% (for which the overall process took about 2 hours and 12 minutes) and 5 iterations for damping ratio of 10% (for which the overall process took about 1 hours and 6 minutes). The resulting parameter boxes are presented in Fig. 9. Analyzing the resulting parameter box A (box B) in Fig. 9, it is possible to see that the gains of the PSSs placed in generators G1 and G3 may be simultaneously set between 16 and 50 p.u. (30 and 50 p.u.) with the assurance of damping ratio higher than 5% (10%) for response modes of the power system with the retuned PSSs.


Linear analyses were carried out considering twenty points (forty gain values) belonging to the parameter boxes presented in Fig. 9. In all evaluated cases, the gain values provided a damping ratio better than the minimum damping ratio specified in the control problem formulation, in all considered operating conditions. Fig. 10 presents the poles related to the electromechanical modes of the system in five different operating conditions, considering only one point belonging to parameter box B (Kpss1=37 and Kpss2=32). The analysis presented in Fig. 10 shows that, after the retuning of the PSSs placed in generators G1 and G3, the test system 1 kept the small-signal stability margin specified in the control problem formulation for the five different operating conditions.


Nonlinear analyses, considering the power system before and after the PSS tuning, were also performed in order to validate the linear ones. Fig. 11 presents nonlinear response corresponding to the speed of generator G4, in a case where the loads were increased by 7.5% with respect to their base case levels. The retuning of the PSSs at generators G1 and G3 has improved the damping of the response modes observed in rotor speed of generator G4.


Different from the studies carried out in de Oliveira et al. (2010b), in this work the methodology is also applied to tune AVRs. After generating parameter ranges just for PSSs, the approach was employed to generate parameter ranges just for AVRs (with nominal PSSs in operation, but with their parameters unchanged) and also for AVRs and PSSs, simultaneously. This evaluation took into account a minimum damping ratio of 5% and the same operating conditions employed in the previous test. Since the AVR gains are usually higher than the PSS gains, the calculation of the parameter ranges for the AVR consider gain deviations of 20 p.u. for the algorithm iterations (i.e., Δρ=20 p.u.). The nominal parameters of the AVRs employed in the model of test system 1 are Ke=200 p.u. and Te=0.01 s. Fig. 12 presents the parameter box determined for the simultaneous tuning of the AVRs placed in generators G1 and G3. The parameter box generated for the simultaneous tuning of the AVR and PSS placed in generator G3 is presented in Fig. 13. Fig. 14 shows the eigenvalues related to the closed-loop model of test system 1, in the base case operating condition, after the retuning of the AVR and PSS (different values of static gains belonging to the parameter box presented in Fig. 13 were considered).




Analyzing Fig. 12, it is possible to see that any values of Ke_1 and Ke_2 between 136 and 320 p.u. (i.e., any values belonging to resulting parameter box) assure the desired small signal stability margin for the power system (damping ratio higher than 5%) in all the considered operating conditions. It must be highlighted at this point that the lower limits in Fig. 12 were defined by nonlinear simulations that ensured a minimum steady-state error of 1% for the terminal voltages of both generators (otherwise, smaller gains could ensure the desired damping but not be practical, in the sense that they do not provide a satisfactory voltage regulation). The parameter box presented in Fig. 13 shows that the static gain of the PSS and AVR placed in generator G3 may be simultaneously set from 12 to 50 p.u. and from 160 to 220 p.u., respectively (i.e., 12 < Kpss< 50 and 160 < Ke< 220), with assurance of damping ratio higher than 5% for response modes of the power system with the retuned controllers. In Fig. 14, it is possible to notice that the different values of static gains belonging to the parameter box presented in Fig. 13 (PSS and AVR gains) assured the small-signal stability margin specified in the control problem formulation.

It is important to observe that the algorithm usually finds a conservative range due to the control formulation conservatism and numerical characteristics in the solver employed to resolve the LMIs. However, the parameter range found by the proposed tool always ensures the robustness and the specified small-signal stability margin for the power system with the retuned controllers.

In a second sequence of tests, the effectiveness of the proposed tool is evaluated in a larger power system corresponding to the reduced-order model of the New England system (Rogers, 2000). This system is constituted by 39 buses and 10 generators. The single line diagram of this system is shown in Fig. 15. Generator G10, shown in Fig. 15, is an equivalent of the New York system. The eigenvalues corresponding to the 9 electromechanical modes of test system 2 in open- loop (without the PSSs) are presented in the appendix.


Again, a base case and two other operating points, related to variations of ±10% in the values of the base case loads, were employed in these tests. A residue analysis has shown that 8 PSSs are enough to properly damp the electromechanical oscillations and provide a good small signal stability margin for the system. The absolute values of the residues related to the open-loop transfer function of test system 2, for each electromechanical mode, are presented in the appendix. The residues were calculated considering the transfer function between ui (i-th stabilizing signal) and yi (speed deviation of the i-th generator). As result of this residue analysis, controllers were placed in generators G1, G2, G3, G4, G6, G7, G8 and G9 of test system 2.

The PSSs for test system 2 were designed taking into account the operating point regarding the base case. The design was based on the residue technique (Sadikovic et al., 2005; Furini et al., 2011), which takes into account the coordination between the designed controllers. The PSSs were sequentially designed, which means that each of the controllers is designed one at a time. It is worth mentioning again that the design and placement of PSSs are not the focus of this work. The parameters of the PSSs placed in this test system are also presented in the appendix.

A linear analysis of the system before the PSS tuning showed that it exhibits 9 electromechanical oscillation modes, and 2 of these modes present damping ratio lower than 10% in two of the adopted operating conditions. The PSSs were intentionally designed to provide a damping ratio lower than 10% for two electromechanical modes of the test system 2 in order to highlight the characteristics and effectiveness of the proposed tool. The poles related to the electromechanical modes of the system with the 8 PSSs, in the three operating conditions considered, are presented in Fig. 16. The least damped modes, considering the three operating conditions, are located between the two dashed lines of Fig. 16.


A modal analysis of the test system 2 has showed that controller placed in generator G4 presents the best controllability index to improve the damping of the two least damped modes. Based on this analysis, it was found that the state variables of the PSS at generator G4 had the highest participation factors with respect to the least damped modes and, therefore, the PSS of G4 was chosen as the one for retuning in this application of the proposed tool. The participation factors of the generator speed, in the least damped mode of the test system 2 (λ =-0,84+j10,93), are presented in the appendix. Damping ratios of 5% and 10% were sought as desired small-signal stability margins for the power system with the retuned PSS. The parameter ranges were determined by the algorithm in 12 iterations for a minimum damping ratio of 5% (for which overall iterative process took about 29 hours and 44 minutes) and 6 iterations for a minimum damping ratio of 10% (for which the process took about 14 hours and 52 minutes). The resulting parameter ranges are presented in Fig. 17. Analyzing Fig. 17, it is possible to see that the engineer in charge of the tuning of PSS placed in generator G4 may set the controller gain between 4 and 50 p.u. (26 and 50 p.u.) with the assurance that the system will present response modes with damping ratio higher than 5% (10%).


The robustness of the resulting parameter ranges was validated by means of linear and non-linear analyses. Fig. 18 shows the eigenvalues associated to the closed-loop models of the test system, for 4 different values of the PSS gain of generator G4 that are within the two ranges shown in Fig. 17. It can be seen that the desired small-signal stability margins of 5% and 10% are both satisfied when using these gains. Similar results were obtained for the system operating at low and high load levels, with respect to the base case.


Non-linear simulations before and after the retuning of the PSS of generator G4, were also carried out in order to validate the results observed in linear analysis. The speed response of generator G4 is presented in Fig. 19, in a case where the loads were increased by 7.5% with respect to their base case levels. The PSS retuning has significantly improved the damping of the modes of this speed response, which can be observed in Fig. 19.


It is important to emphasize that the highest values of gain in these ranges may not be practically acceptable, due to possible saturation of the PSS output for typical small perturbations. However, it is up to the engineer in charge of controller retuning to choose, among the values of gain provided by the proposed tool, the one that best suits other practical needs, such as for example, the avoidance this kind of saturation. The biggest advantage of the proposed tool is the fact that the engineer may confidently choose any gain value within the provided range with guaranteed theoretical closed-loop stability, so he/she does not have to rely entirely on his/her judgment.

5 CONCLUSIONS

This paper presented a computational tool capable of generating a range of parameter values to assist the engineers in charge of controller commissioning or retuning, in such a way that a guarantee of closed loop stability is provided for any gain adjustment made within this range. The main advantage of the application of this tool is the confidence it provides to the responsible engineer when approving a gain adjustment, during the commissioning stage, which is different from the one determined at the design stage based on the nominal model.

If the changes in the topology and/or operating conditions of the system (that can be extracted from the daily load curves and contingency lists for stability analysis, which are readily available at power system utilities) are adequately modeled in the proposed tool, the engineer in charge of controller commissioning does not have to rely entirely on his/her empirical knowledge about the system to perform the gain retuning in the field. It is also important to remark that, due to the possibility of application of the same technique to any parameter variation in the model, the same tool can be used to retune the phase compensation parameters of a PSS in order to provide a range of guaranteed small signal stability margin.

The results obtained with the tests have showed that the proposed tool successfully generated ranges of static gain values for PSSs and AVRs that ensure stability robustness and the fulfillment of a minimum damping ratio criterion for the closed loop power system.

Future directions of this work include the application of this methodology to the tuning of other kinds of power system controllers. Different LMI formulations will also be investigated in order to reduce the computational effort required to solve the control problem. Furthermore, the investigation of some model order reduction techniques, in order to find out the most suitable ones to be used in conjunction with this algorithm, is also a future direction of this research.

A APPENDIX

The model of the i-th synchronous generator with its AVR is given by:

where δ is the generator power angle, w is the rotor angular speed, w0 is the synchronous machine speed, E'd is the direct axis transient voltage, E'q is the quadrature axis transient voltage, Iq is the quadrature axis current, Id is the direct axis current, EFD is the voltage applied to the field circuit by the AVR, Vt is terminal voltage, Vref is the reference voltage for the AVR, and Vpss is the stabilizing signal from the PSS.

The PSS model is given by the following differential equations:

In (A.6)-(A.8), x1, x2, and Vpss are the state variables related to the PSS model. Additional details regarding the system model and its respective parameters can be obtained in Kundur (1994), Anderson and Fouad (2003), and Machowski et al. (2008).

The eigenvalues related to the electromechanical modes of the test system 1 without PSSs are presented in Table A.1 and the transfer function corresponding to the PSSs placed in test system 1 is given by

The absolute values of the residues related to the open-loop transfer function of test system 2, for each electromechanical mode, are presented in Tables A.2 and A.3.

The absolute values of the participation factors of the generator speed in the least damped mode of the test system 2 are presented in Table A.4. The speed of the generator was chosen due to the fact that the electromechanical oscillations usually have a strong participation on this variable.

The parameters of the existing PSSs in the test system 2 before retuning are presented in Table A.5. Note that, after the retuning suggested by the proposed tool, any Kpss in the range between 4 p.u. and 50 p.u. can be used, and the system will still present a 5% minimum damping as a small-signal stability margin. The engineer in charge of the PSS retuning can then confidently choose, using his/her own judgment, the best value of gain within this range that suits other practical requirements as well, such as the avoidance of saturation of PSS outputs when responding to typical perturbations, for example.

ACKNOWLEDGEMENTS

The authors acknowledge FINEP, CAPES, CNPq, FAPESP, and Fundação Araucária for scholarships and funding.

Artigo submetido em 26/01/2011 (Id.: 1257)

Revisado em 15/07/2011, 28/09/2011

Aceito sob recomendação do Editor Associado Prof. Takashi Yoneyama

  • Abdel-Magid, Y. and Abido, M. (2003). Optimal multiobjective design of robust power system stabilizers using genetic algorithms, IEEE Transactions on Power Systems 18(3): 1125-1132.
  • Anderson, P. and Fouad, A. (2003). Power System Control and Stability, IEEE Press, New York - NY.
  • Bomfim, A., Taranto, G. and Falcao, D. (2000). Simultaneous tuning of power system damping controllers using genetic algorithms, IEEE Transactions on Power Systems 15(1): 163-169.
  • Cai, L.-J. and Erlich, I. (2005). Simultaneous coordinated tuning of pss and facts damping controllers in large power systems, IEEE Transactions on Power Systems 20(1): 294-300.
  • Chilali, M., Gahinet, P. and Apkarian, P. (1999). Robust pole placement in lmi regions, IEEE Transactions on Automatic Control 44(12): 2257-2270.
  • de Oliveira, R. V., Ramos, R. A. and Bretas, N. G. (2010a). An algorithm for computerized automatic tuning of power system stabilizers, Control Engineering Practice 18(1): 45-54.
  • de Oliveira, R. V., Ramos, R. A. and Bretas, N. G. (2010b). Ferramenta para ajuste robusto de controladores de amortecimento para sistemas eltricos de potncia, Anais do XVIII Congresso Brasileiro de Automtica, Bonito, MS, Brasil, pp. 1894-1900.
  • Furini, M., Pereira, A. and Araujo, P. (2011). Pole placement by coordinated tuning of power system stabilizers and facts-pod stabilizers, International Journal of Electrical Power & Energy Systems 33(3): 615-622.
  • Gahinet, P., Apkarian, P. and Chilali, M. (1996). Affine parameter-dependent lyapunov functions and real parametric uncertainty, IEEE Transactions on Automatic Control 41(3): 436-442.
  • Gahinet, P., Nemirovski, A., Laub, A. J. and Chilali, M. (1995). LMI control toolbox user's guide, The Math-works Inc.
  • Gomes, S., J., Martins, N. and Portela, C. (2003). Computing small-signal stability boundaries for large-scale power systems, IEEE Transactions on Power Systems 18(2): 747-752.
  • Gurrala, G. and Sen, I. (2010). Power system stabilizers design for interconnected power systems, IEEE Transactions on Power Systems 25(2): 1042-1051.
  • Jabr, R., Pal, B., Martins, N. and Ferraz, J. (2010). Robust and coordinated tuning of power system stabiliser gains using sequential linear programming, IET Generation, Transmission Distribution 4(8): 893-904.
  • Kundur, P. (1994). Power system stability and control, EPRI Editors, McGraw-Hill, New York, NY.
  • Machowski, J., Bialek, J. W. and Bumby, J. R. (2008). Power System Dynamics - Stability and Control, John Wiley & Sons, Chichester, UK.
  • Martins, N. and Lima, L. (1990). Determination of suitable locations for power system stabilizers and static var compensators for damping electromechanical oscillations in large scale power systems, IEEE Transactions on Power Systems 5(4): 1455-1469.
  • Oliveira, R. C. and Peres, P. L. (2005). Stability of polytopes of matrices via affine parameter-dependent lyapunov functions: Asymptotically exact lmi conditions, Linear Algebra and its Applications 405(1): 209-228.
  • Pagola, F., Perez-Arriaga, I. and Verghese, G. (1989). On sensitivities, residues and participations: applications to oscillatory stability analysis and control, IEEE Transactions on Power Systems 4(1): 278-285.
  • Perez-Arriaga, I., Verghese, G. and Schweppe, F. (1982). Selective modal analysis with applications to electric power systems, part i: Heuristic introduction, IEEE Transactions on Power Apparatus and Systems PAS-101(9): 3117-3125.
  • Ramos, R. A. (2009). Stability analysis of power systems considering avr and pss output limiters, International Journal of Electrical Power & Energy Systems 31(4): 153-159.
  • Rogers, G. (2000). Power system oscillations, Kluwer, Norwell-MA.
  • Sadikovic, R., Korba, P. and Andersson, G. (2005). Application of facts devices for damping of power system oscillations, IEEE Russia Power Tech, 2005, pp. 1 -6.
  • Verghese, G., Perez-Arriaga, I. and Schweppe, F. (1982). Selective modal analysis with applications to electric power systems, part ii: The dynamic stability problem, IEEE Transactions on Power Apparatus and Systems PAS-101(9): 3126-3134.
  • Zanchin, V. and Bazanella, A. (2003). Robust output feedback design with application to power systems, 42nd IEEE Conference on Decision and Control, 2003. Proceedings., Vol. 4, pp. 3870-3875.
  • Zanetta, L.C., J. and Cruz, J. J. D. (2005). An incremental approach to the coordinated tuning of power systems stabilizers using mathematical programming, IEEE Transactions on Power Systems 20(2): 895-902.

Publication Dates

  • Publication in this collection
    21 June 2012
  • Date of issue
    June 2012