Pre-cooling water applied to porous plates of evaporative cooling systems

Efeito do pré-resfriamento da água aplicada em placas porosas de sistemas de resfriamento evaporativo

ABSTRACT:

This study assessed the ways the thermal environment is influenced by pre-cooling the water employed in wetting the porous plates present in the evaporative cooling systems (ECS). The experiment was performed using two physical models constructed on a distorted and reduced scale, which simulated closed agricultural facilities equipped with ECS made up of porous cellulose panels. In one physical model, the plates were made wet using chilled water (ECScw), while in the other they were moistened using natural water, at environment temperature (ECSnw). Both inside the physical models and outside, in the external environment, the air dry-bulb temperature (tdb), black globe temperature (tbg) and air relative humidity (RH) were measured, at 10 sec intervals. Later, the environmental indices, ECSnw cooling effectiveness and ECScw performance factor were assessed. When the porous ECS plates were thoroughly wet using pre-cooled water, lowering of the thermal variables and comfort indices was seen to be greater than when wetting the plates was done using water at room temperature. An empirical equation was proposed to determine the cooling performance factor applied to the ECScw related to water temperature, tdb and air wet-bulb temperature.

Key words:
thermal environment; air cooling; air conditioning; chilled water

RESUMO:

Objetivou-se com o presente trabalho avaliar o efeito do pré-resfriamento da água usada no molhamento de placas porosas de sistemas de resfriamento evaporativo (SRE) sobre o ambiente térmico. O experimento foi realizado em dois modelos físicos construídos em escala reduzida e distorcida que simularam instalações agrícolas fechadas, equipadas com SRE composto por painéis porosos de celulose. Em um modelo físico, o molhamento das placas foi realizado por meio de água resfriada (SRAR) e o outro por meio de água natural à temperatura ambiente (SRAN). Mensurou-se a temperatura de bulbo seco do ar (tbs), temperatura de globo negro (tgn) e umidade relativa do ar (UR) no interior dos modelos físicos e no ambiente externo em intervalos de 10s. Posteriormente, foram calculados índices ambientais, a efetividade de resfriamento do SRAN e fator de desempenho do SRAR. O pré-resfriamento da água usada no molhamento de placas porosas de SRE propiciou maior redução nas variáveis térmicas e índices de conforto em relação ao molhamento com água à temperatura ambiente, sendo proposta uma equação empírica para a estimativa do fator de desempenho de resfriamento aplicada ao SRAR em função da temperatura da água, da tbs e da temperatura de bulbo úmido do ar.

Palavras-chave:
ambiente térmico; resfriamento de ar; condicionamento de ar; água gelada

INTRODUCTION:

The problems involved in controlling the thermal environment inside agricultural facilities has directed research towards the state of ambience (CURI et al., 2014CURI, T. M. R. de C. et al. Geostatistic to evaluete the environmental control in different ventilation systems in broiler houses. Engenharia Agrícola, Jaboticabal, SP, v.34, n.6, p.1062-1074, 2014. Available from: <Available from: https://www.scielo.br/scielo.php?script=sci_arttext&pid=S0100-69162014000600004&lng=en&nrm=iso >. Accessed: May, 11, 2020. doi: 10.1590/S0100-69162014000600004.
https://www.scielo.br/scielo.php?script=...
; WATANABE et al., 2018WATANABE, P. H. et al. Cooling ventilation at forrowing for sows from firstto third parturition. Comunicata Scientiae Horticultural Journal, Bom Jesus, PI, v.9, n.4, p.556-564, 2018. Available from: <Available from: https://www.comunicatascientiae.com.br/comunicata/article/view/1098/592 >. Accessed: Jun. 09, 2020. doi: 10.14295/CS.v9i4.1098.
https://www.comunicatascientiae.com.br/c...
). This control; although, crucial in regions experiencing hot climates, continues to be stressful for breeders.

However, for the achievement of positive outcomes in the agricultural sector, such control becomes imperative, in order to ensure that the animals throughout their production cycle, can be reared in their thermal comfort zone, thus ensuring higher rates of production (SCHIASSI et al., 2015SCHIASSI, L. et al. Behavior of broilers subjected to different thermal environments. Agricultural Engineering , Jaboticabal, SP, v.35, no.3, p.390-396, 2015. Available from: <Available from: https://www.scielo.br/scielo.php?pid=S0100-69162015000300390&script=sci_arttext >. Accessed: May, 11, 2020. doi: 10.1590/1809-4430.
https://www.scielo.br/scielo.php?pid=S01...
; LOPES et al., 2020LOPES, I. et al. Geostatistics applied to the environmental mapping of aviaries. Revista Brasileira de Engenharia Agrícola e Ambiental , Campina Grande, PB, v.24, n.6, p.409-414, 2020. Available from: <Available from: https://www.researchgate.net/profile/Iug_Lopes/publication/341134200Geostatisticsapplied_to_the_environmental_mapping_of_aviaries/links/5eb0645245851592d6b8c20f/Geostatistics-applied-to-the-environmental-mapping-of-aviaries.pdf >. Accessed: Jun. 10, 2020. doi: 10.1590/1807-1929/agriambi.v24n6p409-414.
https://www.researchgate.net/profile/Iug...
).

This sector has witnessed a gradual transition from the popularly termed conventional open breeding systems and the employment of artificial temperature control only when required, to systems enclosed by curtains or masonry that, besides the climate control processes, provide the advantages of lowering the internal temperature of the animal growth environments.

Evaporative techniques, using nebulization or moistened porous plates have been proven as the most effective and economically feasible options in closed aviaries to decrease the internal temperatures (DAMASCENO et al., 2010DAMASCENO, F. A. et al. Evaluation of broiler welfare in two air-conditioned commercial sheds. Science and Agrotechnology, Lavras, MG, v.34, no.4, p.1031-1038, 2010. Available from: <Available from: https://www.scielo.br/scielo.php?pid=S1413-70542010000400033 &script=sci_arttext >. Accessed: May, 11, 2020. doi: 10.1590/S1413-70542010000400033.
https://www.scielo.br/scielo.php?pid=S14...
). The wet porous plates, more than the nebulization method, have higher air-cooling capacity, which may differ, based on the various materials used in their construction (TINOCO et al., 2002TINÔCO, I. F. F. et al. Evaluation of alternative materials used in the manufacture of porous plates for adiabatic evaporative cooling systems. Brazilian Journal of Agricultural and Environmental Engineering, v.6, no.1, p.147-150, 2002. Available from: <Available from: http://dx.doi.org/10.1590/S1415-43662002000100026 >. Accessed: Oct. 15, 2019. doi: 10.1590/S1415-43662002000100026.
http://dx.doi.org/10.1590/S1415-43662002...
; PANAGAKIS and AXAOPOULOS, 2006PANAGAKIS, P.; AXAOPOULOS, P. Simulation comparison of evaporative pads and fogging on air temperatures inside a growing swine building. American Society of Agricultural and Biological Engineers, v.49, n.1, p.2019-2015, 2006. Available from: <Available from: https://elibrary.asabe.org/abstract.asp?aid=20240 >. Accessed: Apr. 19, 2021. doi: 10.13031/2013.20240.
https://elibrary.asabe.org/abstract.asp?...
).

From the commercial perspective, cellulose is the most prominent of the different materials used to manufacture the evaporative cooling plates. However, good alternative substitutes for these pads, are expanded clay and vegetable fibers, to ensure higher performance or lower expenditure (TINÔCO et al., 2002TINÔCO, I. F. F. et al. Evaluation of alternative materials used in the manufacture of porous plates for adiabatic evaporative cooling systems. Brazilian Journal of Agricultural and Environmental Engineering, v.6, no.1, p.147-150, 2002. Available from: <Available from: http://dx.doi.org/10.1590/S1415-43662002000100026 >. Accessed: Oct. 15, 2019. doi: 10.1590/S1415-43662002000100026.
http://dx.doi.org/10.1590/S1415-43662002...
; ROSA et al., 2011ROSA, J. F. et al. Analysis of the cooling efficiency of porous panels filled with expanded clay compared to cellulose, using a wind tunnel. Engineering in Agriculture, Viçosa, MG, v.19, no.6, p.516-523, 2011. Available from: <Available from: https://periodicos.ufv.br/reveng/article/view/96/80 >. Accessed: Dec. 28, 2019. doi: 10.13083/reveng.v19i6.107.
https://periodicos.ufv.br/reveng/article...
).

As the air temperature increases and the air humidity outside the premises decreases, the cooling effectiveness also rises. However, works that assessed the temperature of the water used to wet the porous plates employed in animal husbandry to facilitate better thermal indices are very few in the literature.

Therefore, the goal of this research was to determine the effect on the thermal environment, which pre-cooling the water utilized to wet the porous plates of the evaporative cooling systems could exert (ECS).

MATERIALS AND METHODS:

The experiment was carried out using two identical physical models constructed on a site, at the geographic coordinates of 21º13’ 45.2’S latitude; 44º58’32.85’’W of longitude and 918 m of altitude. Experiencing the Cwa type of climate (based on the Köppen classification), the place revealed rainy and temperate weather conditions (mesothermal), with dry winters and rainy summers, subtropical, with higher than 22 °C temperature during the warmest month (DANTAS et al., 2007DANTAS, A. A. A. et al. Climatic classification and tendencies in Lavras region, MG. Ciência e agrotecnologia, Lavras, v.31, n.6, p.1862-1866, 2007. Available from: <Available from: http://dx.doi.org/10.1590/S1413-70542007000600039 >. Accessed: Oct. 10, 2019. doi: 10.1590/S1413-70542007000600039.
http://dx.doi.org/10.1590/S1413-70542007...
).

Physical models and experimental treatments

The two physical models, identical in their construction properties, are typical of the enclosed agricultural facilities in animal husbandry (Figure 1). The physical models were constructed on the scales mentioned: width (W), length (L) and height (H) of 1:10, 1:25 and 1:2, respectively, thus ensuring the internal dimensions of 1.5 m (W) x 6 m (L) x 1.5 m (H). The physical models had roof ridges oriented in the true East-West direction. The main aim of the physical models, constructed in a suitable site, was to facilitate the placement of evaporative porous plates and exhaust fans, ensuring free airflow through them.

Figure 1
Experimental setup in perspective (a), Floor Plan (b) and Section AB (c) of the physical model of aviaries constructed with a cellulose board cooling system using natural water (ECSnw) and chilled water (ECScw). The dots in Section AB indicate the measurement positions of the temperatures on the air dry-bulb and black globe (tdb and tbg, respectively) and air relative humidity (RH). Detailing without scale.

The first physical model had a cellulose pad cooling system using natural water (ECSnw), while the second had the cellulose pad cooling system but with chilled water (ECScw) being used instead.

Acclimatization systems installed on physical models

Each physical model had, at one end, a porous commercial cellulose pad (1 m wide x 1 m high x 0.15 m thick) installed, while at the other end three exhausts (flow rate of 4200 m³ h-1 each) were provided. This acclimatization system is normally employed in the agricultural sector, as in the wind tunnel type commercial aviaries. The evaporative cooling system was designed based on VANTRESS (2018VANTRESS, Cobb. Cobb broiler management guide. Cobb-Vantress, Siloam Springs, AR, USA, 2018.).

In the ECScw, the water-cooling system installed included a hermetic compressor, air condenser (0.56 W), thermal box (77 L capacity) and a pump (0.37 kW and 2400 L h-1). Water flow rates of 0.17±0.004 L s-1 and 0.17±0.003 L s-1, respectively for the ECScw and ECSnw, were pumped to the upper part of the cellulose pad. Water volume in excess was returned to the reservoir to be reused. In the ECScw physical model, water cooling was controlled using the digital thermostat model TIC-17RGTi), manufactured by Full Gauge Controls (±1 °C accuracy).

Measurements and instrumentation

To analyze the cooling capacity of the air flow through the moistened porous plates, the internal and external thermal environments were evaluated, for each physical model.

Inside the physical models, constructed on a reduced scale, five recording thermo-hygrometers were positioned, model U12-001, manufactured by Onset, to ensure the measurement of the air dry-bulb temperature (tdb, °C) and air relative humidity (RH, %), with ±0.35 °C and ±2.5% accuracy for the RH values in the 10 to 90 % range, respectively. The black globe temperature (tbg, °C) was measured at the center of the porous plate alone (Figure 1), while an external temperature sensor, model TMC6-HD, manufactured by Onset, was positioned in the center of a black plastic globe, 3.6 cm in diameter (SANTOS et al., 2005SANTOS, P. A. D. et al. Thermal environment inside small scale poultry house models with natural and artificial roof ventilation. Agricultural Engineering, Jaboticabal, v.25, no.3, p.575-584, 2005. Available from: <Available from: http://dx.doi.org/10.1590/S0100-69162005000300002 >. Accessed: Jun. 15, 2019. doi: 10.1590/S0100-69162005000300002.
http://dx.doi.org/10.1590/S0100-69162005...
), and painted with matte black paint on the outside. This external temperature sensor was hooked up to the external channel of the recording thermo-hygrometer. The responses from the thermometers installed in the plastic black globe were confirmed against a standard black globe thermometer, built using a copper plate 15 cm in diameter and 0.5 mm thick, painted in matte black color.

Five thermo-hygrometers were fitted 30 cm from the porous plate, one each at 20 cm from both ends and one in the center. The thermo-hygrometers were placed 30 cm from the porous plates to ensure that the condition of the air immediately post cooling after passing through the wet porous plates, is not wet with the water droplets from the plates. Apart from the external channels of these logging instruments, the wetting water temperatures (twater) of the cellulose plates inside both the ECScw and ECSnw reservoirs were also recorded. Using the recording thermo-hygrometer in the external environment, the tdb, tbg and RH were determined. All the specified measurements cited earlier were taken at 10 second intervals.

Using a Highmed manufactured model HM-385, hot-wire anemometer (accuracy ±5% +0.1 m s-1) the values of Vair were noted in nine distinct positions, within each physical model (Figure 1) at 75 cm height, always at the commencement of each experiment day.

Measurements of the surface temperature of the external surface of the moistened cellulose panels (tps) were taken at 1-minute intervals, with an infrared thermographic camera, model Ti 55 manufactured by Fluke (accuracy of 0.05 ºC).

To record the thermal values inside the reduced models provided with ECS, the temperature-humidity index (THI) (THOM, 1958THOM, E. C. Cooling degree-days air conditioning, heating and ventilating. Transactions of the ASAE, Atlanta, vol. 55, no. 7, p. 65-72, 1958.), as well as black globe-humidity index (BGHI) were determined from the recorded meteorological variables and tbg (BUFFINGTON et al., 1981BUFFINGTON, D. E. et al. Black globe-humidity index (BGHI) as comfort equation for dairy cows. Transaction of the ASAE, St. Joseph, v.24, n.3, p.711-714, 1981. Available from: <Available from: https://www.tandfonline.com/servlet/linkout?suffix=CIT0005&dbid=16&doi=10.1080%2F09291016.2018.1526499&key=10.13031%2F2013.34325 >. Accessed: Oct. 17, 2019. doi: 10.13031/2013.34325.
https://www.tandfonline.com/servlet/link...
), besides the specific enthalpy (h) (ALBRIGHT, 1990ALBRIGHT, L. D. Environment control for animals and plants. ASAE Textbook, 4. American Society of Agricultural Engineers Michigan, St. Joseph, 1990. and adapted by RODRIGUES et al., 2011RODRIGUES, V. C. et al. A correct enthalpy relationship as thermal comfort index for livestock. International Journal of Biometeorology, v.55, n.3, p.455-459, 2011. Available from: <Available from: https://doi.org/10.1007/s00484-010-0344-y >. Accessed: May, 03, 2019. doi: 10.1007/s00484-010-0344-y.
https://doi.org/10.1007/s00484-010-0344-...
), cooling effectiveness (ε) (RIANGVILAIKUL & KUMAR, 2010RIANGVILAIKUL, B.; KUMAR, S. An experimental study of a novel dew point evaporative cooling system. Energy and Buildings , v.42, n.5, p.637-644, 2010. Available from: <Available from: https://doi.org/10.1016/j.enbuild.2009.10.034 >. Accessed: Oct. 10, 2019. doi: 10.1016/j.enbuild.2009.10.034.
https://doi.org/10.1016/j.enbuild.2009.1...
), performance factor of evaporative cooling (F) (ASHRAE, 1997ASHRAE. Handbook - fundamentals (SI). American Society of Heating, Refrigerating, and Air Conditioning Engineers, Atlanta, GA .1997.) and the vapor pressure deficit (VPD) (ASHRAE, 2005ASHRAE. Handbook of fundamentals. American Society of Heating, Refrigerating, and Air Conditioning Engineers, Atlanta, GA 30329. 2005.). All the equations are cited in table 1.

Table 1
Equations for calculation of the thermal environment evaluation indices, thermodynamic properties of the air and effectiveness of the evaporative cooling of the air.

The THI is a thermal comfort evaluation index dependent upon the tdb and air dew-point temperature (tdp) (THOM, 1958THOM, E. C. Cooling degree-days air conditioning, heating and ventilating. Transactions of the ASAE, Atlanta, vol. 55, no. 7, p. 65-72, 1958.). In a single value, the BGHI surveys the effects of tdb, radiation and air flow via the tbg and air humidity through the tdp (BUFFINGTON et al., 1981BUFFINGTON, D. E. et al. Black globe-humidity index (BGHI) as comfort equation for dairy cows. Transaction of the ASAE, St. Joseph, v.24, n.3, p.711-714, 1981. Available from: <Available from: https://www.tandfonline.com/servlet/linkout?suffix=CIT0005&dbid=16&doi=10.1080%2F09291016.2018.1526499&key=10.13031%2F2013.34325 >. Accessed: Oct. 17, 2019. doi: 10.13031/2013.34325.
https://www.tandfonline.com/servlet/link...
). Enthalpy is a physical quantity, expressed in the realm of thermodynamics, which quantifies the energy of a system (ALBRIGHT, 1990ALBRIGHT, L. D. Environment control for animals and plants. ASAE Textbook, 4. American Society of Agricultural Engineers Michigan, St. Joseph, 1990.). The cooling effectiveness or saturation efficiency indicates the ratio between the lowered tdb recorded and the maximum that can be theoretically achieved (CAMARGO, 2008; RIANGVILAIKUL & KUMAR, 2010RIANGVILAIKUL, B.; KUMAR, S. An experimental study of a novel dew point evaporative cooling system. Energy and Buildings , v.42, n.5, p.637-644, 2010. Available from: <Available from: https://doi.org/10.1016/j.enbuild.2009.10.034 >. Accessed: Oct. 10, 2019. doi: 10.1016/j.enbuild.2009.10.034.
https://doi.org/10.1016/j.enbuild.2009.1...
). The performance factor F, pertinent to non-adiabatic cooling processes is the ratio between the enthalpy reduction observed and the maximum theoretically achievable (ASHRAE, 1997). The VPD refers to the difference between the water vapor pressure during saturation conditions and the current water vapor pressure at a specific temperature (YUAN et al., 2019YUAN, W. et al. Increased atmospheric vapor pressure deficit reduces global vegetation growth. Ecology, v.5, n.8, eaax1396, 2019. Available from: <Available from: https://www.science.org/doi/10.1126/sciadv.aax1396 >. Accessed: May, 7, 2021. doi: 10.1126/sciadv.aax1396.
https://www.science.org/doi/10.1126/scia...
).

The air wet-bulb temperature (twb) was calculated analytically by the equations that define the psychrometric properties of the air (WILHELM, 1976WILHELM, L. Numerical calculation of psychrometric in SI units. Transactions of the ASAE, v.19, n.2, p.318-321, 325, 1976. Available from: <Available from: https://elibrary.asabe.org/abstract.asp?aid=36019 >. Accessed: Jan. 14, 2020. doi: 10.13031/2013.36019.
https://elibrary.asabe.org/abstract.asp?...
).

Experimental phases, experimental design and statistical analysis

To confirm the presence of equivalence between the two ECS fitted in the physical models, experiments were conducted prior, for three non-consecutive days, where similar conditions required for the system to function were maintained. This step was termed the ‘pre-test phase’.

Subsequently, nine non-consecutive days, the systems (ECSnw and ECScw) were evaluated, during the hottest part of the day (from 12:00 to 15:45), termed the ‘test phase’. The twater values during the course of the tests were in the 18.3 to 21.5 C range for the ECSnw and from 8.8 to 16.1 °C for the ECScw. Analysis was done each day, for three operating cycles of the ECS, with and without cooling the water used to wet the plates. Each cycle took 1 hour to complete, which included 15 min of ECS operation and 45 min of waiting, to cool the water down to as close to the desired temperature as possible.

From among all the 15 min of data collected, only the data drawn during the intermediate 5 min were statistically analyzed. This procedure enabled higher stabilization of the ECS because in the initial stage the evaporative cooling plate was kept wet and, during the final 5 minutes, there was a trend of the surface temperature of the plate to rise due to the inability of the water cooling system to maintain the water at constant. All the data recording was done in 10 second intervals.

The completely randomized design was adopted (CRD) with the water temperature represented as a single factor, subdivided into two levels (ECSnw and ECScw), used in the physical models. The response variables, pertaining to the thermal comfort in these two situations, were evaluated, giving 27 repetitions in all, for each one.

Using the Student’s t test for the independent data with 5% significance level these variables were analyzed between the two levels of the factor. The fit of the models was assessed based on the regression analysis of variance and the coefficient of determination (R²). Adjustment was done for the multiple linear regression models to evaluate the cooling performance factor for the ECScw as a function of the twater, thermal environment variables, thermal environment evaluation indices and enthalpy, and the correlation coefficients were determined.

Employing the R statistical computational system (R DEVELOPMENT CORE TEAM, 2019R DEVELOPMENT CORE TEAM. R: A Language and Environment for Statistical Computing. Vienna: R Foundation for Statistical Computing, 2019. Available from: <Available from: http://www.R-project.org/ >. Accessed: Apr. 19, 2021.
http://www.R-project.org/...
), all the statistical analyses were done.

RESULTS AND DISCUSSION:

The equivalence present between the cellulose board cooling system using natural water (ECSnw) and the cellulose board cooling system utilizing chilled water (ECScw) was obvious during the pre-test phase (Table 2) because, on analysis, all the variables were statistically equal (P > 0.05, t test). The reduction of tdb, THI, BGHI and h showed values of -7.1 and -6.7 ºC, -6.2 and -6.0, -10.0 and -10.4, -3.5 and -3.1 for the ECSnw and ECScw, respectively. The ε values for the ECSnw and ECScw were 79.7 and 75.5, respectively, clearly indicating that the responses of the cooling systems were similar and that it is the exclusively the water temperature variations that induce the changes.

Table 2
Student's t test applied to compare thermal and cooling effectiveness of scaled-down models equipped with evaporative cooling of the wetted porous plate type, in the pre-test and test phases.

During the test phase, statistical differences were confirmed, revealing improved ECScw performance when the means of the tdb, tdp and twater variables, and the THI and BGHI indexes and the thermodynamic property h (P < 0.01, test t) were analyzed. The tbg also displayed identical profile (P < 0.05, t-test). In turn, the variables UR and tps were statistically equal (P > 0.05, t test).

During the days that the experiments were performed, when the tdb and RH mean values of the external environment were 31.2 ºC and 40.9%, respectively, the ECSnw induced a 6.8 ºC decrease in the tdb, with a corresponding 29.1 % increase in the RH, while the ECScw caused the tdb to decline at 8.1ºC and the RH to show a rise of 28.3 % in (Table 2). For a closely similar thermal condition (32 ºC and 40 %), a system made up of a cellulose evaporative plate can lower by 7.7 ºC the internal temperature of aviaries, while causing a 34.6% increase in the RH (VANTRESS, 2018VANTRESS, Cobb. Cobb broiler management guide. Cobb-Vantress, Siloam Springs, AR, USA, 2018.).

In their investigations of a variety of configurations for the evaporative cooling system using computer simulations, CARVALHO et al. (2009CARVALHO, V. F. et al. Mapping of potential use of evaporative cooling systems in Southeastern Brazil. Revista Brasileira de Engenharia Agrícola e Ambiental, Campina Grande, PB, v.13, n.3, p.358-366, 2009. Available from: <Available from: https://www.scielo.br/scielo.php?script=sci_arttext&pid=S1415-43662009000300020 >. Accessed: Oct. 17, 2019. doi: 10.1590/S1415-43662009000300020.
https://www.scielo.br/scielo.php?script=...
) concluded that in September, for the study duration, a tunnel mode ventilation system related to a porous material type evaporative cooling system, moistened at 70% efficiency, lowered the THI by 1.8±1.4 when compared to a negative pressure wind tunnel ventilation system lacking the evaporative cooling. In the current study, the ECScw induced a 2.0±0.8 reduction when compared to the ECSnw, for the same index being investigated.

In their research, in Brazil, TINÔCO et al. (2002TINÔCO, I. F. F. et al. Evaluation of alternative materials used in the manufacture of porous plates for adiabatic evaporative cooling systems. Brazilian Journal of Agricultural and Environmental Engineering, v.6, no.1, p.147-150, 2002. Available from: <Available from: http://dx.doi.org/10.1590/S1415-43662002000100026 >. Accessed: Oct. 15, 2019. doi: 10.1590/S1415-43662002000100026.
http://dx.doi.org/10.1590/S1415-43662002...
) compared a few of the available alternative porous materials, and reported BGHI values roughly 2.5 lower in the expanded clay-filled slabs than for those filled with sawdust, vegetable fiber and charcoal. A difference of 2.2, on average, was achieved favoring the ECScw, suggesting this as another possibility to boost the cooling performance.

In their endeavor to determine the distribution of illuminance and enthalpy in two aviaries used for rearing broilers, FAUSTINO et al. (2021FAUSTINO, A. C. et al. Spatial variability of enthalpy and illuminance in free-range broiler sheds. Revista Brasileira de Engenharia Agrícola e Ambiental , Campina Grande, PB, v.25, n.5, p.340-344, 2021. Available from: <Available from: https://www.scielo.br/j/rbeaa/a/CBdbpVJpKg7F8W87Ry4Mmvk/?lang=en&format=html >. Accessed: Oct. 10, 2019. doi: 10.1590/1807-1929/agriambi.v25n5p340-344.
https://www.scielo.br/j/rbeaa/a/CBdbpVJp...
) recorded a 0.5 kJ kg-1 reduction, induced by a clay tile-covered brick shed when compared to a straw-covered wooden shed. In this study, the ECScw registered a 3.9±0.8 kJ kg-1 reduction compared to the ECSnw for the same index investigated.

For ECSnw, the mean value of ε was found to be 72.5 % (Table 2), the range being 52.4 to 83%. ROSA et al. (2011ROSA, J. F. et al. Analysis of the cooling efficiency of porous panels filled with expanded clay compared to cellulose, using a wind tunnel. Engineering in Agriculture, Viçosa, MG, v.19, no.6, p.516-523, 2011. Available from: <Available from: https://periodicos.ufv.br/reveng/article/view/96/80 >. Accessed: Dec. 28, 2019. doi: 10.13083/reveng.v19i6.107.
https://periodicos.ufv.br/reveng/article...
), recorded 78.1 % as the average value of ε for cellulose. Of note, that the value of ε shows variations as a function of the air that flows through the porous plates, the water mass that flows over the porous material surface and its uniformity, besides other variables.

For the ECScw, the mean performance factor (F) was found to be 0.237±0.054. During the tests, the outdoor and indoor air dry-bulb temperatures were in the 28.2 to 35.6 °C range (average of 31.2° C) and from 21.5 to 27.1° C (average of 23.1° C), respectively. The relative humidity of the outdoor air was in the range of 25.8 to 51.4 % (average 40. %) while, for the indoor air, the variation hovered between 53.2 and 76.8%, with 69.1% as the average value. The water temperature was in the 8.8 to 16.1 °C range, with the average at 12.9 °C. In fact, AL-BADRI & AL-WAALY (2017AL-BADRI, A. R; AL-WAALY, A. A. Y. The influence of chilled water on the performance of direct evaporative cooling. Energy and Buildings, v.155, p.143-150, 2017. Available from: <Available from: https://www.sciencedirect.com/science/article/abs/pii/S0378778817319977 >. Accessed: Jun. 10, 2020. doi: 10.1016/j.enbuild.2017.09.021.
https://www.sciencedirect.com/science/ar...
), in their assessment of a direct evaporative cooler for inlet air temperatures from 24.5 to 33.6 °C (average 31.0° C) and water temperatures from 15.8 to 21.0 °C (average 18.7° C), observed that F values occurred between 0.10 and 0.41, showing a mean of 0.214. Thus, among other factors, the greatest value achieved by the average performance factor acquired in this research can be credited to the lowest values attained by the wetting water temperature on the porous plates. Further, these results imply an escalation in the performance factor with lowering of the water temperature, findings which concur with those reported by these authors.

On investigating the multiple regression models among the variables, the best fit model identified to determine the F values was seen as a function of the twater, tdb and twb (equation 8), achieving R² of 0.9753 and with all the variables showing a minimum of 97.52% significance. The standard errors corresponding to the coefficients of the equation for twater, tdb and twb were 0.004267, 0.004019 and 0.005922, respectively.

F = - 0.010218 ∙ twater - 0.017841 ∙ tdb + 0.042595 ∙ twb

CONCLUSION:

In the present study, under the specific conditions, pre-cooling the water used to wet the porous plates present in the evaporative cooling systems induced an additional drop in the thermal variables (of 1.4 °C and 1.4 °C for tdb and tbg, respectively). With respect to the evaluation of the indices of the thermal environment and the thermodynamic property of the air values of 2.1, 2.2 and 4.0 kJ kg dry air-1 (for THI, BGHI and h, respectively) were observed, related to the wetting of the porous plates, using water at room temperature.

In order to estimate the evaporative cooling performance factor as a function of the temperature of wetting water of the porous plates, as well as the air dry- and wet-bulb temperatures, an empirical equation was fitted.

The electrical energy consumed for cooling the water in the chilled water cellulose board cooling system (ECScw) was not determined in the current study because the investigations were performed only on a small-scale model; however, in future it has been suggested to conduct the research in commercial aviaries.

ACKNOWLEDGEMENTS

We are grateful to Conselho Nacional de Desenvolvimento Científico e Tecnológico (CNPq) for the finantial incentive for the second (CNPq, Grant no. 310729/2018-1) and financial support for the third (CNPq, Project no. 462095/2014-2) authors. This study was financed in part by the Coordenação de Aperfeiçoamento de Pessoal de Nível Superior - Brasil (CAPES) - Finance Code 001.

REFERENCES

  • CR-2020-1015.R1

Edited by

Editors: Leandro Souza da Silva(0000-0002-1636-6643)
Marcia Xavier Peiter(0000-0001-8945-5412)

Publication Dates

  • Publication in this collection
    10 June 2022
  • Date of issue
    2022

History

  • Received
    19 Nov 2020
  • Accepted
    09 Nov 2021
  • Reviewed
    05 June 2022
Universidade Federal de Santa Maria Universidade Federal de Santa Maria, Centro de Ciências Rurais , 97105-900 Santa Maria RS Brazil , Tel.: +55 55 3220-8698 , Fax: +55 55 3220-8695 - Santa Maria - RS - Brazil
E-mail: cienciarural@mail.ufsm.br