1. Introduction
The supply chain of the construction industry is responsible for many positive impacts on the built environment, given that it enables the implementation of urban infrastructure and provides quality of life for its inhabitants. However, it consumes a significant amount of natural resources and generates tons of waste each year[1-4].
Construction waste consists of various types of materials, such as concrete, mortar, wood, and plastic, accounting for about 60% of the entire residue collected each year in Brazil. In general, these materials are used for embankment, which can cause solubilization or leaching of certain harmful substances present in these materials. Furthermore, Mancini et al.[2,5-7] claims that plastics have low biodegradability and occupy a large amount of space, decreasing the useful life of landfill areas. The effects of degradation can appear after 20-30 years[5,8]. Building companies are improving their construction techniques and optimizing proper waste disposal to meet the current Brazilian legislation (CONAMA Resolution No. 307)[9]. The environmental impact of building materials can be reduced signicantly by increasing the amount of recycled materials.
Polyvinyl chloride is a thermoplastic polymer widely used in construction works as electrical conduit pipes. PVC conduit can be embedded, buried, or apparent, typically used in electrical installations for buildings, with a rated voltage not exceeding 1000 V for alternating current, and frequency below 400 Hz, or 1500 V for direct current. The conduit function is to protect and route electrical wiring in a building structure. It should withstand temperatures from -5 °C to 60 °C for 24 hours without showing any deformity, not allowing the passage of electric current above 100 mA. PVC conduit was chosen as the focus of this research because the main properties of the material encompass thermal insulation, low flammability, and self-extinguishing flame[6,10-12].
Polyurethane is a thermoplastic polymer often used in construction works due to its excellent performance as thermal and acoustic insulation[7,8,13-17]. The physico-chemical properties of polyurethane are important for that purpose[5]. The material has suitable mechanical strength to be used as thermal insulation in applications such as precast insulated sandwich wall panels, in ceiling lining or floors, and inside wood frame walls[18-21]. Singh[8], however, warns that this is not suitable for surface coating and interior finishes in buildings because it is not resistant to fire. The ignition of polyurethane foams includes all gas-phase processes that occur between the fuel production step and the occurrence of a visible hot flame. The ignition of polyurethane foams occurs by the interdiffusion of the flammable gases with air. The basic physical and chemical aspects of gas-phase ignition reactions have been studied by several researchers[7,8,22]. Thus, the introduction of flame retardants is required in those situations[7,8,16,23]. Flame retardants are intended to inhibit or stop the polymer combustion process. Depending on their nature, they can act physically (by cooling, forming a dilution layer or fuel protection) or chemically (gas or condensed phase reaction). They can interfere with different processes involved in the polymer combustion (heating, pyrolysis, ignition, and propagation of thermal degradation)[13,16,23].
There is a large number of flame-retardant additives, which are divided into halogenated and non-halogenated compounds[3,13,16,23-28]. The halogenated flame retardants are more efficient than the non-halogenated composites, although they are more toxic during the burning process[23,26,27].
Halogenated flame retardants are organic compounds containing chlorine or bromine (or fluorine, or iodine). When they decompose, they interfere with the combustion process, both in the gaseous combustion and in the condensed phase. However, fluorine- and iodine-based retardants are not commonly used because none of them interferes with the exact point of ignition of the combustion process[22,23,25,26].
In 2013, a tragedy of epic proportions was reported in the national and international media: the Kiss nightclub fire in the southern Brazilian city of Santa Maria[29]. This was not an isolated case, though. In 2003, there was a deadly Rhode Island nightclub fire in the United States as well. Several security failures were decisive for the former event, but it should be noted that polyurethane foam used for acoustic insulation has high flammability properties.
Flame retardants for polyurethane are generally utilized to retard ignition timing and reduce the burning rate and smoke formation. The type of flame retardant for PU depends on the application and rules that govern that application. Halogenated flame retardants are commonly used for rigid foams, and include tetrabromophthalic anhydride, aliphatic chlorine, tetrabromophthalate, and 2,3-dibromo-2-butene-1,4-diol[16,25,30].
For that purpose, a polyurethane composite was developed with the incorporation of polyvinyl chloride (PVC) of flexible conduit residues[31] from the construction industry. PVC was incorporated into the foam components by simple mechanical mixing at the compounding stage. This is still a relatively unexplored method, and this study is intended to contribute to analyze PVC compatibility with PU[32-40]. This paper presents an analysis of the conduit residue (PVC) incorporation into polyurethane to obtain plates, in order to investigate whether this material presents flammability reduction and improvement of thermal and mechanical properties.
2. Materials and Methods
2.1 Preparation of the composites PU/PVC
Formulated polyether polyol, and toluene diisocyanate reagents were purchased from Arinos company (Arinos Química, São Paulo, Brazil) to manufacture the composite. All reagents were used as received, and safety guidelines were followed.
Figure 1 exhibits a package of PVC conduit in yellow as marketed (Figure 1A). PVC conduit installation during construction generates residual cuts that are usually discarded. After collection, the residues were washed, dried in an oven at 40 °C for 48 hours, and ground in a blender (Figure 1B) and classified by particle size (Figure 1C). A number 16 ASTM stainless steel sieve was used for the classification of grain sizes. The material used for the production of composites presented particle sizes passing a 1.18 mm sieve (Figure 1D) and Mw 108.511 (Mw/Mn 2.233).

Figure 1 (A) Flexible PVC conduit; (B) pieces of conduit cuts; (C) pieces for grinding; (D) triturated conduit and sieves for particle size classification; (E) conduit powder with particle size less than 1.18 mm.
Molecular mass distribution of the PU and PVC was estimated by size exclusion chromatography (SEC), using a GPC Viscotek VE2001 with an ultraviolet detector at the wavelength of 280 nm and bimodal exclusion columns PVDF. Samples weight was 0.01-0.02 g and tetrahydrofuran was used as an eluent. The calibration of columns was carried out with a polystyrene standard of the Mw 30,000 and polydispersity Mw/Mn 1.0. The model polyurethane used as a standard was synthesized from the same polyether polyol and the same toluene diisocyanate (component molar ratio was 1:1.1, Table 1).
Table 1 Amounts of raw materials for the production of PU specimens and PU/PVC composites with 5%, 10%, 15%, and 20% of PVC from conduit residues.
Poliol (g) | Toluene diisocyanate (g) | PVC residues (g) | |
---|---|---|---|
PU | 6.12 | 6.73 | - |
PU/5PVC | 5.85 | 6.39 | 0.64 |
PU/10PVC | 5.50 | 6.06 | 1.29 |
PU/15PVC | 5.20 | 5.72 | 1.93 |
PU/20PVC | 4.90 | 5.39 | 2.56 |
Specimens with a mass percentage of 5%, 10%, 15%, and 20% of PVC waste were prepared to substitute for polyurethane (polyol and isocyanate) with a total mass of 12.85 g. PVC was incorporated into the foam components by simple mechanical mixing at the compounding stage. Table 1 shows the mass of the reagents used in each test.
The composites were obtained by mixing conduit residues (PVC) to formulated polyether polyol, and adding toluene diisocyanate. The mixture was stirred for 0.5 min and poured into a mold 0.05 m in diameter and 0.1 m height, cut in half vertically to facilitate demolding. A lid 0.05 m in diameter was used to close the molds. The specimens were demolded after 24 hours[38,41,42].
The curing time consisted in the reaction between hydroxyl (formulated polyether polyol) and isocyanate groups (isocyanate polymer), leading to the formation of a polymeric matrix (Mw 278 and Mw/Mn 1.133). The chemical reaction that occurs between isocyanate and polyol forms a chemical bond by urethane links (-O-CO-NH-), which forms polyurethane because of polycondensation[14,43,44]. Isocyanate worked as a crosslinking agent, promoting solidification of the mixture, thus the proportions of the reactants were maintained for all composites[21,22]. Immediately after adding the curing agent, the mixture viscosity was suitable for being poured into the molds. The incorporation of the conduit residue occurred in different proportions with mass reduction of the reagents at baseline, being incorporated into PU.
Figure 2 shows the PU/PVC composites with 5%, 10%, 15%, and 20% conduit. They had a uniform surface, good visual appearance, and showed no deformation after demolding.
2.2 Scanning Electron Microscopy (SEM)
The micrographs of PU and PU/PVC plates were obtained by scanning electron microscopy using a JEOL JSM-6390LV device, at a voltage of 15 kV, and the samples were fractured in liquid nitrogen.
2.3 Water resistance test
The procedure followed the gravimetric method recommended by the Standard Test Method for Water Absorption of Plastics D 570-98[45].
Initially, the samples were oven-dried at 50 °C for 24 hours. The dry material was weighed on a digital scale (Shimadzu BL-3200H) with a precision of 0.01 g. Then, the samples were immersed in a distilled-water bath at 25 °C for 24 hours. After that, they were removed and dried with paper towels and weighed again. The water absorption rate was obtained by the following formula:
where: A: Water absorption (%); Msat: Mass of saturated sample (g); Ms: Mass of dry sample (g).
2.4 Thermal insulation
The insulation test consisted of a qualitative evaluation for comparison of heating curves between the PU and the developed materials. A specimen made from the composite containing an internal cavity was developed to perform the assay. This apparatus allowed placing a beaker inside with 10 ml of previously cooled water, as shown in Figure 3. A heating curve for water was then provided by using a digital thermometer (Hanna HL2221) at 10-minute time intervals, up to a maximum time of 60 minutes.
2.5 Mechanical compression strength
Mechanical compressive strength tests followed the requirements of ASTM D695-15[47]. The mechanical tests were carried out by compressing 5 kN load cell in a universal testing equipment (EMIC DL-30000), according to the requirements of ASTM D-63890. In these tests, the specimens were subjected to pressure increments until the plastic deformation occurred, at room temperature.
2.6 Differential Scanning Calorimetry (DSC)
The analysis of differential scanning calorimetry was performed by using the Q2000 Thermal Analyst Instruments, Universal (TA Instruments). The temperature of the samples ranged from -50 °C to 150 °C, with heating-cooling rate of 5 °C min-1 under nitrogen atmosphere.
2.7 Thermogravimetry
Thermogravimetric analysis (TGA) of samples was performed under nitrogen atmosphere at a heating rate of 10 °C/min within a temperature range of 20 °C to 900 °C, using a TGA Q5000 (TA Instruments) device.
2.8 Burning rate
Tests to measuring the burning characteristics followed the requirements of NBR 9178:2015[48] and ASTM D3801. Five samples of the composite measuring 102 mm in width × 356 mm in length × 13 mm in thickness were used for the tests. Each sample was placed in contact with the flame, and measurements were made of the time it took for the material to combust, and the distance traveled by the flame along the board. Figure 4 shows a schemating drawing of the test.
3. Results and Discussions
3.1 Scanning Electron Microscopy
Scanning Electron Microscopy (SEM) analysis made it possible to evaluate the effect of incorporating conduit residues into the morphology of polyurethane foam. Figure 5 shows images of PU (5A and 5B) and images of PU containing 20% conduit residue (5C and 5D). There is no certified or standard micrograph for PU foams, given that they vary with the type and percentage of their components[3,4,27,28,31,49]. Therefore, the PU sample used as reference was prepared under the same conditions of the composite.

Figure 5 SEM micrographs of freeze-fractured surfaces of PU (A and B) and PU with 20% conduit residue (C and D), at 15-fold (A and C) and 30-fold magnification (B and D), respectively.
Figure 5 images show that cryogenically fractured surfaces exhibited a closed-cell structure, probably due to the type of cross-link during the polymerization reaction, which helps reduce cell disruption during the expansion process. Both the PU (Figure 5A and 5B) and the PU/PVC composite (Figure 5C and 5D) had an approximately spherical shape. There was a PVC dispersion in PU, and the interaction between the polymers occured at the interfacial level. There were hard PVC particles in the PU foam, which led to foam contraction[31,49]. Cell growth was hampered by the incorporation of the conduit as it can be seen by comparing 5A (PU) with 5C (PU/PVC), at a 15-fold magnification, and 5B (PU) with 5D (PU/PVC), at a 30-fold magnification. PU cells have a diameter of about 0.800 mm (Figure 5A), whereas PU/20PVC composite cells (Figure 5C) have a diameter of about 0.300 mm, corresponding to an approximately 2.5-fold reduction. PU has cell size around 0.800 mm (5A), whereas in the image 5C there are up to three cells in 0.800 mm. The embedded PVC presented a maximum size of 1.18 mm, and the size reduction of PU foam cells was higher in the composite containing 20% PVC.
There was good adhesion between PU and PVC resulting from intermolecular interactions between Cl groups (PVC) and N-H groups (PU)[50], given that PU foam was observed in PVC particle on the fracture surface, as circled in Figures 5C and 5D. Another indication of this interaction is that the images were obtained from the fracture surface, and there were no signs that the conduit was pulled out of the matrix at the time of the fracture. In fact, this homogeneity between conduit and matrix is essential for mechanical reinforcement[51].
The presence of predominantly closed-cell structures prevented moisture absorption, blocked the passage of gases and vapors, and did not communicate with the external environment. These are important characteristics for materials to be used as thermal insulation[52,53]. This behavior was maintained for all prepared PU/PVC composites, regardless of the percentage of conduit residues (PVC) incorporated into PU.
3.2 Water Resistance Test
This test was intended to determine the percentage of water absorbed by the material when subjected to immersion. After weighing each specimen, water absorption percentage was obtained for each composite in the different conduit percentages, as shown in Table 2.
Table 2 Average immersion test results for PU and PU-conduit composites (PU/PVC).
Sample | Water absorption percentage (%) |
---|---|
PU | 13.12 (0.18) |
PU/5PVC | 11.86 (0.22) |
PU/10PVC | 13.31 (0.17) |
PU/15PVC | 13.27 (0.18) |
PU/20PVC | 13.71 (0.19) |
() standard deviation
Considering that PU and composites presented predominantly closed-cell structures, as shown in the microstructure analysis, there was no significant variation in water absorption between the samples. Most study samples showed about 13% water absorption in the immersion test. Then, when hold in environmental condition, they lost the absorbed water and returned to the original mass within 6 days, thereby not accumulating moisture. These results indicate that the material keeps its integrity even in contact with water[5,6].
3.3 Thermal insulation
Figure 6 shows the results of the mass heating curve of water thermally isolated in PU and PU/PVC composites.

Figure 6 Profile of temperature variations of PU/PVC composites with 5%, 10%, 15%, and 20% conduit and pure PU.
Figure 6 shows that all samples had the same thermal behavior, i.e., the incorporation of PVC residues did not alter the profile of the heating curve already shown by the PU apparatus. The temperature change rate for the mass of water was approximately 0.18 °C/min for all samples in Figure 6. Therefore, the incorporation of conduit residues in the percentage indicated in this study did not hamper the product’s performance related to thermal insulation as already shown by PU.
These results confirm those from the microstructural analysis that identified the existence of closed-cell structures in the composites[3,4,27,28,31,49]. The existence of closed cells in the composite is particularly important for materials to be used as thermal insulation, given that conductivity occurs by radiation, which is hampered regardless of the cellular size[20]. These facts may explain the similar scores found for the heating curves of thermal-insulated water mass.
3.4 Mechanical compressive strength
The effect of PVC on the compressive strength of the PU/PVC composites was studied. Figure 7 shows the compressive strength-deformation profile for the specimens of PU and PU/PVC composites.
The composites studied had an increase in the elasticity modulus and maximum strength as compared to the PU matrix. These behaviors are due to the optimal level of compatibility reached between the components, which indicates that PVC has contributed to the mechanical reinforcement of PU/PVC composites, because PVC presented a uniform distribution in the PU matrix, as well as good interfacial interaction between the polymers[31,49]. The addition of PVC to the PU matrix causes two opposite intermolecular effects. Firstly, it reduces hydrogen interactions in the PU matrix, leading to a reduction in the mechanical properties of the material. Secondly, the intermolecular interactions between the Cl groups (PVC) and NH groups (PU) led to an increase in the mechanical properties. The second effect prevailed, leading to a slight increase in the mechanical properties of the material. These results confirm what was observed in microscopy studies, since it shows good adhesion between the PVC and the PU matrix.
It is worth mentioning that the strength-deformation curves for the composites showed elastic and plastic characteristics regardless of the conduit percentage added to the PU matrix. The elastic and plastic deformations are attributed to the presence of polyurethane, wherein PU/PVC composites were less elastic and had higher maximum strength scores as compared to those of PU.
As it can be seen in Figure 7, the material is elastic in the initial stage of load application. This feature is important because the composite with elastic characteristics makes it difficult for the membrane of closed cells to break, which is vital for thermal insulation. Otherwise, air expansion within cell structures, for example, could facilitate thermal radiation[20].
3.5 Differential Scanning Calorimetry (DSC)
Figure 8 shows the thermograms obtained for PU plate and PU/PVC composite with 15% conduit residue. The curves for all blends show similar profile.
Tg and Tm scores were similar for both PU plate and PU/PVC composite. For the PU, Tg was observed at -9.89 °C and Tm at 104.43 °C. Tg and Tm scores of the PU/PVC blend were similar to the PU component alone, since the interaction occurs at the interfacial level.
3.6 Thermogravimetry
Figure 9 shows the TGA results for PU, PVC and PU/20PVC composite developed in this study. Degradation curves occurred in all samples at a temperature range between 20 °C and 900 °C. The heating rate was 10 °C/min with nitrogen atmosphere.
For the PU sample, mass loss began at 293.40 °C. At 325.00 °C, the mass loss was 45.43%, and complete degradation occurred at 770 °C. The first and second PU decomposition steps correspond to urethane bond-breaking and polyol decomposition, respectively[8,39,50,51].
Dehydrochlorination of PVC starts at the temperature the 32.87 °C, HCl is released from the polymer backbone in sequential stages, to yield long, conjugated polyenes. At the temperature of 52.31 °C, there was a PVC mass loss of 57.68%, and at a temperature of 208.13 °C, mass loss was 87.49%[33,35,39], completing the decomposition around 300 °C.
For the PU/PVC composite with 20% conduit residue, degradation also occurred in two stages. The degradation started at 22.5 °C and then a decrease in the values of degradation temperatures occurred, which can be attributed to the PU/PVC interface. Dehydrochlorination occurred mainly in the first stage of degradation and began at a lower temperature than that observed for PVC. HCl formation may have been catalyzed by PU amino groups[33,35,39,50]. At a temperature of 48.39 °C, there was a 51.39% loss of the total mass of the sample, which means that urethane bond-breaking also occurred at a lower temperature than that observed for the PU. There were two effects on the temperature scores for the composite degradation. The first effect consisted of the partial destruction of PU hydrogen bonds caused by the addition of PVC in the PU matrix. Thus, the temperature score for the PU degradation decreases by increasing the PVC content. The second effect is that the increase in the PVC content causes greater interaction between the Cl groups and NH groups, leading to catalyze C-Cl and C-NH bond breaking at lower temperatures. The results indicate that these effects led to decrease the degradation scores for the PU/PVC composite. Degradation of the composite samples was completed at 300 °C, whereas for the PU it occurred at 770 °C.
The interaction between polymers can influence the ignition and burning rate of the materials, given that HCl formation at a temperature lower than that of the PU decomposition act as a retardant in the gaseous phase of the composite burning. For that purpose, a vertical burning rate test was performed, which is designed for a diagnosis of real burning conditions.
3.7 Burning rate
The composites under study were assessed according to the NBR 9178:2015[48] that regulates flexible polyurethane foam testing to determine burning characteristics and investigate the effect of conduit residue incorporation into the PU matrix. According to the NBR 9178:2015[48] and ASTM D3801[54], by comparing the burning times of the two composites it is possible to estimate burning speed and burning length, i.e., the distance traveled by the flame along the board.
Figure 10 exhibits a sequence of images (A-F) for the PU/20PVC composite burning, where (A) 2 s, (B) 4 s, (C) 5 s, (D) 6 s and (F) 7 s from the start of the burn.

Figure 10 Burning test for the PU/20PVC composite, where (A) 2 s, (B) 4 s, (C) 5 s, (D) 6 s and (F) 7 s from the start of the burn.
In the burning test for PU plate, ignition was followed by self-sustained combustion, with complete burning of the specimen in 7 s, that is, the burning rate was 50.9 mm/s[13,54,55]. Figure 10 (A-F) exhibits the PU/20PVC composite burning test; the other samples showed similar behavior to the PU/20PVC. There was immediate ignition and complete burning of the specimens in the time range between 3 s and 8 s; thus, the burning rate ranged from 44.5 to 118.7 mm/s[56]. The presence of PVC in the composite did not slow the burning rate.
According Vilar[57], when polyurethane foam is burned in the open air, a complete combustion occurs, forming carbon dioxide (CO2), nitrogen oxides (NOx), and water (H2O). However, in a closed environment, such as in buildings, the effect of burning becomes even more dangerous because of the drop in atmospheric oxygen, which leads to an incomplete combustion and creates poisonous carbon monoxide (CO), in addition to producing hydrogen cyanide (HCN), also known as hydrocyanic acid or cyanide gas[26,58].
It is widely accepted that PVC dehydrochlorination involves a gradual reaction between chlorine and hydrogen atom neighbors in the polymer chain, comprising a double bond between the carbon atoms in positions in which the two atoms were originally connected, forming a structure of allylic chlorine with another chlorine atom of the polymer chain[11,33,35,39]. Complete combustion leads to the formation of hydrochloric acid, carbon dioxide and water.
The addition of PVC residues to polyurethane does not act as a flame retardant on the composite. Therefore, to meet the requirements of the NBR 9178:2015[48], a flame-retardant additive should be included in the formulation[11,51].
According to the NBR 9178:2015[48], flame-retardant additives must be added to coatings, such as polyurethane, for greater security of the environment and emergency evacuation. The use of polyurethane in the construction industry is regulated by national norms, such as ABNT NBR 9178:2015[48], ABNT NBR ISO 15366-2:2006[59], ABNT NBR ISO 31000:2009[60], ABNT NBR ISO 14001:2004[61], and by international regulations, among which the Polyurethane Products in Fires: Acute Toxicity of Smoke and Fire Gases[62], Fire Safety Guidance: Working with Polyurethane Foam Products During New Construction Retrofit and Repair (AX-426)[63] and Model Building Code Fire Performance Requirements (AX-265)[64].
4. Conclusions
This work presented an alternative to the use of conduit residue from the construction industry to produce a new material for thermal insulation. The composites were prepared by simple mixture in polyol and then polymerized, leading to materials that had thermal insulation behavior similar to that of PU. SEM images of the material exhibited a closed-cell structure, which revealed the thermal insulation property exhibited by the composites and explained water absorption with little variation between the samples. The composites presented elastic and plastic characteristics regardless of the percentage of conduit residues added to the PU matrix, but with enough mechanical strength to be used as thermal insulation. In the DSC thermograms, PU characteristics were predominant, whereas the Tg and Tm scores were similar for the PU/PVC composites. Findings from this study revealed that the addition of PVC (conduit) residues to polyurethane did not provide flame retardant properties to the composites as assessed by NBR 9178: 2015. Therefore, a flame-retardant additive must be included in the formulation to meet the requirements of the NBR 9178: 2015[48].