ENERGETIC ANALYSIS OF AN ABSORPTION CHILLER USING NH3/LiNO3 AS AN ALTERNATIVE WORKING FLUID

Abstract

This paper presents a thermodynamic model developed for a prototype absorption chiller using NH3/LiNO3 with 10 kW of nominal capacity. The study was undertaken using thermodynamic modeling based on the mass and energy balance, takes the overall heat transfer coefficients into consideration and uses the characteristic equation method. First, the results obtained from the thermodynamic modeling developed were compared with those obtained from the characteristic equations of thermal power activation and the cooling capacity. These showed good agreement with the experimental data, there being maximum relative errors of around 5% for most of the operational conditions of the system. Secondly, a parametric analysis was made by altering the variables, such as temperature, mass flow rate, and configuring the heat dissipation that influences the overall performance of the prototype chiller.

Keywords:
Prototype absorption chiller; Characteristic equation method; Parametric analysis; NH3/LiNO3

INTRODUCTION

LiBr/H2O and NH3/H2O, the conventional fluids used in absorption refrigeration systems cause great inconveniences, such as corrosion problems and high pressures, in addition to which there is a need to rectify the solution, which tends to crystallize (Akrami et al., 2018Akrami, E., Nemati, A., Nami, H., Ranibar, F. Exergy and exergoeconomic assessment of hydrogen and cooling production from concentrated PVT equipped with PEM electrolyzer and LiBr-H2O absorption chiller, International Journal of Hydrogen Energy, 43, 622-633 (2018). https://doi.org/10.1016/j.ijhydene.2017.11.007
https://doi.org/10.1016/j.ijhydene.2017....
; Guido et al., 2018Guido, W.H., Laner, W., Petersen, S., Ziegler, F. Performance of absorption chillers in field tests, Applied Thermal Engineering , 134, 353-359 (2018). https://doi.org/10.1016/j.applthermaleng.2018.02.013
https://doi.org/10.1016/j.applthermaleng...
). The binary pair, lithium nitrate/ammonia binary, has been used as an alternative solution for these systems (Libotean et al., 2007Libotean, S., Salavera, D., Valles, M., Esteve, X., Coronas, A. Vapor-Liquid Equilibrium of Ammonia + Lithium Nitrate + Water and Ammonia + Lithium Nitrate Solutions from (293.15 to 353.15) K, Journal of Chemical and Engineering Data , 52, 1050-1055 (2007). https://doi.org/10.1021/je7000045
https://doi.org/10.1021/je7000045...
and 2008Libotean, S., Martin, A., Salavera, D., Valles, M., Esteve, X., Coronas, A. Densities, Viscosities, and Heat Capacities of Ammonia + Lithium Nitrate and Ammonia + Lithium Nitrate + Water Solutions between (293.15 and 353.15) K, Journal of Chemical and Engineering Data, 53, 2383-2388 (2008). https://doi.org/10.1021/je8003035
https://doi.org/10.1021/je8003035...
; Cuenca et al., 2014Cuenca, Y., Salavera, D., Vernet, A., Teja, A. S., Valles, M. Thermal conductivity of ammonia + lithium nitrate and ammonia + lithium nitrate + water solutions over a wide range of concentrations and temperatures, International Journal of Refrigeration, 38, 333-340 (2014). https://doi.org/10.1016/j.ijrefrig.2013.08.010
https://doi.org/10.1016/j.ijrefrig.2013....
). The mixture (NH3/LiNO3) has shown good results when compared to the mixtures used in commercial systems (LiBr/H2O and also NH3/H2O), especially when solar energy is used as an activation source of the system (Amaris et al., 2014Amaris, C., Bourouis, M., Vallès, M., Salavera, D., Coronas, A. Thermophysical Properties and Heat and Mass Transfer of New Working Fluids in Plate Heat Exchangers for Absorption Refrigeration Systems, Heat Transfer Engineering, 36, 388-395 (2014). https://doi.org/10.1080/01457632.2014.923983
https://doi.org/10.1080/01457632.2014.92...
; Buonomano et al., 2018Buonomano, A., Calise, F., Palombo, A. Solar heating and cooling systems by absorption and adsorption chillers driven by stationary and concentrating photovoltaic/thermal solar collectors: Modelling and simulation, Renewable and Sustainable Energy Reviews, 82, 1874-1908 (2018). https://doi.org/10.1016/j.rser.2017.10.059
https://doi.org/10.1016/j.rser.2017.10.0...
).

Several studies on absorption systems that use NH3/LiNO3 have been conducted, some of which seek to take experimental approaches (Moreno-Quintanar et al., 2011 and 2012Moreno-Quintanar, G., Rivera, W., Best, R. Comparison of the experimental evaluation of a solar intermittent refrigeration system for ice production operating with the mixtures NH3/LiNO3 and NH3/LiNO3/H2O. Renewable Energy, 38, 62-68 (2012). https://doi.org/10.1016/j.renene.2011.07.009
https://doi.org/10.1016/j.renene.2011.07...
; Jimenez and Rivera, 2014Jiménez, C., Rivera, W. Experimental assessment of an absorption cooling system operating with the ammonia/lithium nitrate mixture, Energy, 78, 685-692 (2014). https://doi.org/10.1016/j.energy.2014.10.058
https://doi.org/10.1016/j.energy.2014.10...
; Cai et al., 2016Cai, D., Jiang, J., He, G., Li, K., Niu, L., Xiao, R. Experimental evaluation on thermal performance of an air-cooled absorption refrigeration cycle with NH3-LiNO3 and NH3-NaSCN refrigerant solutions. Energy Conversion and Management , 103, 32-43 (2016). https://doi.org/10.1016/j.enconman.2016.04.089
https://doi.org/10.1016/j.enconman.2016....
; Jiang et al., 2017Jiang, J., Liu, Y., He, G., Liu, Y., Cai, D., Liang, X. Experimental investigations and an updated correlation of flow boiling heat transfer coefficients for ammonia/lithium nitrate mixture in horizontal tubes, International Journal of Heat and Mass Transfer, 112, 224-235 (2017). https://doi.org/10.1016/j.ijheatmasstransfer.2017.04.135
https://doi.org/10.1016/j.ijheatmasstran...
) while others take theoretical approaches (Acuña et al., 2013Acuña, A., Velázquez, N., Cerezo, J. Energy analysis of a diffusion absorption cooling system using lithium nitrate, sodium thiocyanate and water as absorbent substances and ammonia as the refrigerant, Applied Thermal Engineering, 51, 1273-1281 (2013). https://doi.org/10.1016/j.applthermaleng.2012.10.046
https://doi.org/10.1016/j.applthermaleng...
; Farshi et al., 2014Farshi, L. G., Infante-Ferreira, C. A., Mahmoudi, S. M. S. First and second law analysis of ammonia/salt absorption refrigeration systems, International Journal of Refrigeration , 40, 111-121 (2014). https://doi.org/10.1016/j.ijrefrig.2013.11.006
https://doi.org/10.1016/j.ijrefrig.2013....
; Alvarez et al., 2016Álvarez, M.E., Hernández, J.A., Bourois, M. Modelling the performance parameters of a horizontal falling film absorber with aqueous (lithium, potassium, sodium) nitrate solution using artificial neural networks, Energy, 102, 313-323 (2016). https://doi.org/10.1016/j.energy.2016.02.022
https://doi.org/10.1016/j.energy.2016.02...
; Azhar and Siddiqui, 2017Azhar, M., Siddiqui, M.A. Energy and Exergy Analyses for Optimization of the Operating Temperatures in Double Effect Absorption Cycle, Energy Procedia, 109, 211-218 (2017). https://doi.org/10.1016/j.egypro.2017.03.043
https://doi.org/10.1016/j.egypro.2017.03...
; Maryami and Dehghan, 2017Maryami, R., Dehghan, A.A. An exergy based comparative study between LiBr/water absorption refrigeration systems from half effect to triple effect, Applied Thermal Engineering , 124, 103-123 (2017). https://doi.org/10.1016/j.applthermaleng.2017.05.174
https://doi.org/10.1016/j.applthermaleng...
; Sabbagh and Gómez, 2018Sabbagh, A.A., Gómez, J.M., Optimal control of single stage LiBr/water absorption chiller, International Journal of Refrigeration , 92, 299-311 (2018). https://doi.org/10.1016/j.ijrefrig.2018.05.007
https://doi.org/10.1016/j.ijrefrig.2018....
), especially in the direction of creating prototypes. This is seen in the literature (Hernández-Magallanes et al., 2014Hernández-Magallanes, J. A., Domínguez-Inzunza, L. A., Gutiérrez-Urueta, G., Soto, P., Jiménez, C., Rivera, W. Experimental assessment of an absorption cooling system operating with the ammonia/lithium nitrate mixture, Energy 78, 685-692 (2014). https://doi.org/10.1016/j.energy.2014.10.058
https://doi.org/10.1016/j.energy.2014.10...
; Zamora et al., 2014Zamora, M., Bourouis, M., Coronas, A., Vallès, M. Pre-industrial development and experimental characterization of new air-cooled and water-cooled ammonia/lithium nitrate absorption chillers, International Journal of Refrigeration , 45, 189-197 (2014). https://doi.org/10.1016/j.ijrefrig.2014.06.005
https://doi.org/10.1016/j.ijrefrig.2014....
and 2015Zamora, M., Bourouis, M., Coronas, A., Vallès, M. Part-load characteristics of a new ammonia/lithium nitrate absorption chiller, International Journal of Refrigeration , 56, 43-51 (2015). https://doi.org/10.1016/j.ijrefrig.2014.11.005
https://doi.org/10.1016/j.ijrefrig.2014....
). Moreno-Quintanar et al. (2012)Moreno-Quintanar, G., Rivera, W., Best, R. Comparison of the experimental evaluation of a solar intermittent refrigeration system for ice production operating with the mixtures NH3/LiNO3 and NH3/LiNO3/H2O. Renewable Energy, 38, 62-68 (2012). https://doi.org/10.1016/j.renene.2011.07.009
https://doi.org/10.1016/j.renene.2011.07...
made a comparison with a solar-powered intermittent absorption refrigeration system, which takes both a binary mixture (NH3/LiNO3) and also a ternary mixture (NH3/LiNO3+H2O) into account, their goal being to verify the best mixture for the solar absorption chiller. They found that the advantages offered by the ternary mixture were greater than those presented by the binary mixture (NH3/LiNO3). Studies by Zamora et al. (2014Zamora, M., Bourouis, M., Coronas, A., Vallès, M. Pre-industrial development and experimental characterization of new air-cooled and water-cooled ammonia/lithium nitrate absorption chillers, International Journal of Refrigeration , 45, 189-197 (2014). https://doi.org/10.1016/j.ijrefrig.2014.06.005
https://doi.org/10.1016/j.ijrefrig.2014....
, 2015Zamora, M., Bourouis, M., Coronas, A., Vallès, M. Part-load characteristics of a new ammonia/lithium nitrate absorption chiller, International Journal of Refrigeration , 56, 43-51 (2015). https://doi.org/10.1016/j.ijrefrig.2014.11.005
https://doi.org/10.1016/j.ijrefrig.2014....
) developed two pre-industrial absorption chillers, one with a water-cooled system and the other with an air-cooled system, which were built with brazed plate heat exchangers. The goals of these papers were to optimize the chiller, the focus being on the circulation pump, and also to characterize these pre-industrial chillers at part-load.

To compare configurations of absorption refrigeration systems and their performance, Domínguez-Inzunza et al. (2014Domínguez-Inzunza, L. A., Hernández-Magallanes, J. A., Sandoval-Reyes, M., Rivera, W. Comparison of the performance of single-effect, half-effect, double-effect in series and inverse and triple-effect absorption cooling systems operating with the NH3-LiNO3 mixture, Applied Thermal Engineering , 66, 612-620 (2014). https://doi.org/10.1016/j.applthermaleng.2014.02.061
https://doi.org/10.1016/j.applthermaleng...
) compared five configurations of operational absorption systems (namely, those of half-effect; single-effect; double-effect in series; double-inverse and triple-effect) using ammonia/lithium nitrate solution as the working pair. The results showed that the single-effect chiller has the simplest configuration in comparison to the other chillers analyzed and also its Coefficient of Performance (COP) is almost twice as high as those obtained with the half-effect cycle. In their paper, Cai et al. (2015Cai, D., He, G., Tian, Q., Bian, Y., Xiao, R., Zhang, A. First law analysis of a novel double effect air-cooled non-adiabatic ammonia/salt absorption refrigeration cycle, Energy Conversion and Management, 98, 1-14 (2015). https://doi.org/10.1016/j.enconman.2015.03.083
https://doi.org/10.1016/j.enconman.2015....
) introduced a new component to improve the thermal performance of a novel air-cooled double effect absorption refrigeration system that could use ammonia/lithium nitrate and ammonia/sodium thiocyanate solutions as working fluids and a high temperature source to activate the cycle. In the same context, although using a two-stage configuration of a thermodynamic double-effect absorption cycle with ammonia/lithium nitrate, Ventas et al. (2016) found that the maximum COP could reach 1.25 when the driven temperature was around 100°C. Cai et al. (2016) conducted an experimental study of an air-cooled type single-effect absorption refrigeration cycle that uses two different solutions (NH3/LiNO3 and ammonia-sodium thiocyanate) as working pairs, with a view to determining how these influenced the evaporation temperature and capacity of the chiller. Ventas et al. (2017)Ventas, R., Lecuona, A., Rodriguez-Hidalgo, M.C. Performance analysis of an absorption double-effect cycle for power and cold generation using ammonia/lithium nitrate, Applied Thermal Engineering , 115, 256-266 (2017). https://doi.org/10.1016/j.applthermaleng.2016.12.102
https://doi.org/10.1016/j.applthermaleng...
conducted a study with a view to proposing a NH3/LiNO3 two-stage double-effect absorption chiller for cogeneration systems that produce electricity and cooling using solar thermal or residual heat as energy sources. It was found that a combined power and cooling system allows the production of power to be adapted either to the demand for cooling or to the demand for power by splitting the vapor generated.

On using this alternative mixture (NH3/LiNO3) in absorption systems, some advantages were demonstrated, mainly with respect to the simplicity of the configuration of the cycle, due to excluding the rectifier in absorption systems that use ammonia/water as the working fluid. From this context, numerous experimental proposals were put forward for different applications of these systems, such as thermal comfort and also refrigeration (Domínguez-Inzunza et al., 2014Domínguez-Inzunza, L. A., Hernández-Magallanes, J. A., Sandoval-Reyes, M., Rivera, W. Comparison of the performance of single-effect, half-effect, double-effect in series and inverse and triple-effect absorption cooling systems operating with the NH3-LiNO3 mixture, Applied Thermal Engineering , 66, 612-620 (2014). https://doi.org/10.1016/j.applthermaleng.2014.02.061
https://doi.org/10.1016/j.applthermaleng...
; Hernández-Magallanes et al., 2014Hernández-Magallanes, J. A., Domínguez-Inzunza, L. A., Gutiérrez-Urueta, G., Soto, P., Jiménez, C., Rivera, W. Experimental assessment of an absorption cooling system operating with the ammonia/lithium nitrate mixture, Energy 78, 685-692 (2014). https://doi.org/10.1016/j.energy.2014.10.058
https://doi.org/10.1016/j.energy.2014.10...
; Jiménez and Rivera, 2014Jiménez, C., Rivera, W. Experimental assessment of an absorption cooling system operating with the ammonia/lithium nitrate mixture, Energy, 78, 685-692 (2014). https://doi.org/10.1016/j.energy.2014.10.058
https://doi.org/10.1016/j.energy.2014.10...
; Zamora et al., 2014Zamora, M., Bourouis, M., Coronas, A., Vallès, M. Pre-industrial development and experimental characterization of new air-cooled and water-cooled ammonia/lithium nitrate absorption chillers, International Journal of Refrigeration , 45, 189-197 (2014). https://doi.org/10.1016/j.ijrefrig.2014.06.005
https://doi.org/10.1016/j.ijrefrig.2014....
and 2015Zamora, M., Bourouis, M., Coronas, A., Vallès, M. Part-load characteristics of a new ammonia/lithium nitrate absorption chiller, International Journal of Refrigeration , 56, 43-51 (2015). https://doi.org/10.1016/j.ijrefrig.2014.11.005
https://doi.org/10.1016/j.ijrefrig.2014....
; Cai et al., 2016Cai, D., Jiang, J., He, G., Li, K., Niu, L., Xiao, R. Experimental evaluation on thermal performance of an air-cooled absorption refrigeration cycle with NH3-LiNO3 and NH3-NaSCN refrigerant solutions. Energy Conversion and Management , 103, 32-43 (2016). https://doi.org/10.1016/j.enconman.2016.04.089
https://doi.org/10.1016/j.enconman.2016....
).

In this paper, a complete energetic analysis of the prototype absorption chiller is presented. The study uses thermodynamic modeling based on the mass and energy balances that take the overall heat transfer coefficients into consideration. Its uses the characteristic equation method by applying the Duhring rule of the internal temperature based on the saturation mean temperatures and the Duhring slope. It also conducts a sensitivity analysis of the parameters such as the temperatures of hot, cold and chilled water and the mass flow rates, the configuration of the heat dissipation systems (series and parallel) and also the effect of the overheating introduced at the outlet of the evaporator. The goal is to increase the thermal COP of the prototype chiller.

METHODOLOGY

The absorption refrigeration equipment modeled in this paper is a 10 kW single-effect hot water-fired absorption chiller of nominal capacity which uses NH3/LiNO3 as the working fluid. It was designed, built and tested by the SOLAFRIO and CONFISOL project (Zamora, 2012Zamora, M. Optimización industrial y estrategia de control de una enfriadora de absorción de amoniaco/nitrato de litio con disipación por aire. Ph.D thesis. Universitat Rovira i Virgili, Spain (2012).). This prototype was modeled in the steady state, based on the mass, species and energy balances. As is known, a single-effect absorption refrigeration system is a device that, basically, consists of a generator, a condenser, an absorber, an evaporator, expansion valves, a solution heat exchanger and pumps, see Figure 1. However, this model includes a refrigerant heat exchanger in order to enhance the efficiency of the absorption system.

Figure 1
Diagram of the Prototype Absorption Chiller.

In addition to the generator, condenser, absorber, evaporator, there are two plate heat exchangers: one for the solution and another for the refrigerant. These components were chosen because of their compactness. The operation takes place using three internal and external fluids. The internal ones are divided into the NH3/LiNO3 solution, which passes through points 1 - 6 (which are responsible for the desorption and absorption processes), and the refrigerant vapor, which passes through points 7-10, and points 19 and 20 (which is responsible for the cooling effect).

The external circuits are divided into three, namely, the hot, cold and chilled water circuits. The hot water circuit (points 11-12) represents the activation source for the absorption chiller, while the cold water circuit (points 13-16) represents the dissipation source of the systems, and the chilled water circuit (points 17-18) represents the cooling capacity of the chiller.

Thermodynamic Modeling of the prototype absorption chiller

In the thermodynamic modeling of the prototype, see Figure 1, the external circuits (cold, hot and chilled water) and their interactions with the internal circuit (solution and/or refrigerant) had to be included. This was achieved by using the characteristic equations of each heat exchanger. The equation that characterizes the heat exchanger is based on the product (UA) and the logarithmic average temperature (ΔT ln ), the latter being the boundary condition between the internal circuit and the external fluid. This modeling of the internal circuit with external circuits allows the output conditions (pressures, temperatures, energy flows) of the chiller to be checked based on the variations made to the system (thermal load, source activation, cooling circuit). To construct the thermodynamic model of the prototype, the following simplifying assumptions were considered:

  • The system is in steady state;

  • The temperature, pressure and concentration are homogeneous in each component;

  • The refrigerant circuit consists exclusively of pure ammonia;

  • There are only two pressure levels, high (generator - condenser) and low (absorber - evaporator);

  • A variation in pressure occurs only in the expansion valves;

  • The rich solution leaving the absorber is in saturation conditions at the pressure and temperature of the absorber;

  • The heat exchange with the neighborhood is negligible;

  • The expansion valves are considered adiabatic.

The properties of the working fluids of the system were determined from the correlations found in the literature. For pure ammonia, the correlations presented by Tillner-Roth et al. (1993Tillner-Roth, R., Harms-Watzenberg, F., Baehr, H.D. A new fundamental equation for ammonia. DKV-Tagungsbericht, 20, 167-181 (1993). (in German).) were used and for the NH3/LiNO3 solution, the vapor pressure specific heat, density, viscosity and enthalpy were determined by using, the correlations found by the CREVER group (Libotean et al., 2007Libotean, S., Salavera, D., Valles, M., Esteve, X., Coronas, A. Vapor-Liquid Equilibrium of Ammonia + Lithium Nitrate + Water and Ammonia + Lithium Nitrate Solutions from (293.15 to 353.15) K, Journal of Chemical and Engineering Data , 52, 1050-1055 (2007). https://doi.org/10.1021/je7000045
https://doi.org/10.1021/je7000045...
and 2008Libotean, S., Martin, A., Salavera, D., Valles, M., Esteve, X., Coronas, A. Densities, Viscosities, and Heat Capacities of Ammonia + Lithium Nitrate and Ammonia + Lithium Nitrate + Water Solutions between (293.15 and 353.15) K, Journal of Chemical and Engineering Data, 53, 2383-2388 (2008). https://doi.org/10.1021/je8003035
https://doi.org/10.1021/je8003035...
; Cuenca et al., 2014Cuenca, Y., Salavera, D., Vernet, A., Teja, A. S., Valles, M. Thermal conductivity of ammonia + lithium nitrate and ammonia + lithium nitrate + water solutions over a wide range of concentrations and temperatures, International Journal of Refrigeration, 38, 333-340 (2014). https://doi.org/10.1016/j.ijrefrig.2013.08.010
https://doi.org/10.1016/j.ijrefrig.2013....
).

Table 1 shows the equations of the mass, species and energy balances for all the components of the absorption chiller and it also shows the set of equations of the external circuitry and the heat transfer equations of the heat exchangers. These equations represent the overall energetic modeling of the prototype as can be seen in Ochoa et al. (2014Ochoa, A.A.V., Dutra, J.C.C., Henríquez, J.R.G., Rohatgi, J. Energetic and exergetic study of a 10RT absorption chiller integrated into a microgeneration system, Energy Conversion and Management , 88, 545-553 (2014). https://doi.org/10.1016/j.enconman.2014.08.064
https://doi.org/10.1016/j.enconman.2014....
a and 2014b; Ochoa et al., 2016; Ochoa et al., 2017Ochoa, A.A.V., Dutra, J.C.C., Henríquez, J.R.G., Santos, C.A.C. dos, Rohatgi, J. The influence of the overall heat transfer coefficients in the dynamic behavior of a single effect absorption chiller using the pair LiBr/H2O, Energy Conversion and Management , 136, 270-282 (2017). https://doi.org/10.1016/j.enconman.2017.01.020
https://doi.org/10.1016/j.enconman.2017....
).

Table 1
Mass, species and energy balances, and heat transfer equations of the heat exchangers modeled.

The subscript X represents the components (absorber, evaporator, condenser and generator) of the chiller. The temperature of the external water circuit is represented by the letter (t) and the temperatures of the internal circuit of the chiller are represented by the letter (T).

Characteristic Equation Method

Based on the information found in the open literature, specifically in Albers and Ziegler (2015Albers, J., Ziegler, F. Improved control strategies for solar assisted cooling systems with absorption chillers using a thermosyphon generator, In: Proceedings of the Int. Solar Air. Cond., October, Kloster Banz, Germany (2015).) and Zinet et al. (2012Zinet, M., Rulliere, R., Haberschill, P. A numerical model for the dynamic simulation of a recirculation single-effect absorption chiller, Energy Conversion and Management , 62, 51-63 (2012). https://doi.org/10.1016/j.enconman.2012.04.007
https://doi.org/10.1016/j.enconman.2012....
), the characteristic equation method is based on the thermodynamic fundamentals and nominal characteristics of the chiller. The aim is to determine the behavior of the absorption chiller considering the average temperatures of the cold, hot and chilled water (external circuits) and specific characteristics of the chiller, such as the overall heat transfer coefficients and flow rates. Implementation takes the Duhring rule into account, thus allowing both the internal average temperatures of each heat exchanger of the chiller to be identified and the weak and strong concentrations (X sol ) of the system and the temperatures of the saturated solution (Tsat,sol) from a linear equation with slope B and intersection Z, expressed as:

T s a t , s o l = B X s o l T s a t , r e f + Z X s o l (1)

This considers the four main heat exchangers (Absorber, Evaporator, Condenser and Generator), and lets calculations be made of the heat flow (Qi), based on the overall heat transfer coefficient and the area of the heat exchanger, the product (UA X ), and the average logarithmic difference (∆Tlm X ) as shown in Table 1. To simplify the equations and according to the literature for heat exchangers, the analysis of absorption refrigeration systems (Kohlenbach and Ziegler, 2008Kohlenbach, P., Ziegler, F. A dynamic simulation model for transient absorption chiller performance. Part II: Numerical results and experimental verification, International Journal of Refrigeration , 31, 226-233 (2008). https://doi.org/10.1016/j.ijrefrig.2007.06.010
https://doi.org/10.1016/j.ijrefrig.2007....
and 2008b; Myat et al., 2011Myat, A., Thu, K., Kim, Y. D., Chakraborty, A., Chun, W. G., Choon, K. N. A second law analysis and entropy generation minimization of an absorption chiller, Applied Thermal Engineering , 31, 2405-2413 (2011). https://doi.org/10.1016/j.applthermaleng.2011.04.004
https://doi.org/10.1016/j.applthermaleng...
; Ochoa et al., 2016Ochoa, A.A.V., Dutra, J.C.C., Henríquez, J.R.G., Santos, C.A.C. dos. Dynamic study of a single effect absorption chiller using the pair LiBr/H2O, Energy Conversion and Management , 108, 30-42 (2016). https://doi.org/10.1016/j.enconman.2015.11.009
https://doi.org/10.1016/j.enconman.2015....
and 2017Ochoa, A.A.V., Dutra, J.C.C., Henríquez, J.R.G., Santos, C.A.C. dos, Rohatgi, J. The influence of the overall heat transfer coefficients in the dynamic behavior of a single effect absorption chiller using the pair LiBr/H2O, Energy Conversion and Management , 136, 270-282 (2017). https://doi.org/10.1016/j.enconman.2017.01.020
https://doi.org/10.1016/j.enconman.2017....
) and the term (∆Tlm) of the characteristic equation can be replaced by the mean difference in temperature between the hot and cold fluids (∆Tlm X|t X - T X |). Where t X is the average temperature of the external fluid and T X is the average temperature of the internal fluid of the flows of the heat exchanger.

The characteristic equation method was described by applying the First Law of Thermodynamics to the absorption refrigeration system, taking into account a steady-state regime with the energy and mass balances of the system. Table 2 shows the equations of the first part of implementing the characteristic equation method of the prototype chiller.

Table 2
First Part of the Equation characteristic Method of the absorption chiller.

By applying the Duhring rule for two temperature levels, Eq. 1, (high and low), the relationships found were:

T G T A = B X s o l T C T E (2)

The B term of equation 2 represents the slope of the Duhring diagram. By combining the equations from Table 2 and equation (2), the average external temperatures of the cold, hot and chilled water circuits are determined, expressed as:

t G t A B t C t E = Q ˙ E G U A G + A U A A + Q ˙ l o s s 1 U A G + 1 U A A + B Q ˙ E C U A C + 1 U A E (3)

The term on the left can be represented by the total temperature difference (∆∆t), as:

Δ Δ t = t G t A B t C t E = Δ t t h r u s t B Δ t l i f t (4)

Eq. 4 could be interpreted as the difference between the temperature thrust ∆t thrust = (t G - t A ) and the temperature lift ∆t lift = (t C - t E ). The total temperature difference can also be defined in terms of the design parameters, such as:

Δ Δ t = Q ˙ E + Q ˙ l o s s 1 U A G + 1 U A A G U A G + A U A A + B C U A C + 1 U A E 1 G U A G + A U A A + B C U A C + 1 U A E (5)

This fraction of the total temperature difference can be simplified based on two parameters: (S E ) representing the proportion of the global coefficient of each component of the chiller Eq. (6); and (αE ), which represents the distribution of the overall heat transfer coefficients inside the equipment Eq. (7), such as:

S E = 1 G U A G + A U A A + B C U A C + 1 U A E (6)

α E = 1 U A G + 1 U A A G U A G + A U A A + B C U A C + 1 U A E (7)

The total temperature difference could be defined as Equation 8:

Δ Δ t = Q ˙ E S E + Δ Δ t min E (8)

The minimum total temperature difference (∆∆t minE ) represents a relationship between the parameters (S E , αE and Q loss ), expressed as:

Δ Δ t min E = α E Q ˙ l o s s S E (9)

The thermal power activation (generator) and cooling capacity (evaporator) of the absorption chiller can be expressed as:

Q ˙ E = S E Δ Δ t Δ Δ t min E (10)

Q ˙ G = G S E Δ Δ t Δ Δ t min E + S E α E Δ Δ t min E (11)

The full modeling and implementation of the characteristic equation method of the prototype chiller are detailed in Ochoa et al. (2017Ochoa, A.A.V., Costa, J.A.P. da, Franco, S.S. Implementation of the Characteristic Equation Method applied to an Absorption Chiller LiBr/H2O of Commercial type, CIENTEC, 9, 24-38 (2017).).

Coefficient of Performance of the Chiller (COP)

The COP of the chiller can be expressed as:

C O P = Q ˙ E Q ˙ G = S E Δ Δ t Δ Δ t min E G S E Δ Δ t Δ Δ t min E + Q ˙ l o s s = Δ Δ t Δ Δ t min E G Δ Δ t S E 1 α E G + Δ Δ t min E (12)

DISCUSSION AND RESULTS

The energetic analysis using the theoretical thermodynamic modeling based on the mass, species and energy balances and the characteristic equation method was compared with experimental data collected from the paper by Zamora (2012Zamora, M. Optimización industrial y estrategia de control de una enfriadora de absorción de amoniaco/nitrato de litio con disipación por aire. Ph.D thesis. Universitat Rovira i Virgili, Spain (2012).) and also by adapting the thermal power activation and cooling capacity based on two correlations in accordance with the method found in the literature (Puig et al., 2010Puig, A. M., López, V. J., Bruno, J. C. Coronas, A. Analysis and parameter identification for characteristic equations of single - and Double effect absorption chillers by means of multivariable regression, International Journal of Refrigeration , 33, 70-78 (2010). https://doi.org/10.1016/j.ijrefrig.2009.08.005
https://doi.org/10.1016/j.ijrefrig.2009....
). In the second part, a parametric analysis was conducted to verify the influence of the operational parameters on the performance of the prototype chiller.

Nominal Conditions of the Prototype NH3/LiNO3 Absorption Chiller

The nominal temperature conditions of the cold, chilled and hot water of the prototype are shown in Table 3 (Zamora, 2012Zamora, M. Optimización industrial y estrategia de control de una enfriadora de absorción de amoniaco/nitrato de litio con disipación por aire. Ph.D thesis. Universitat Rovira i Virgili, Spain (2012).). The Products (UA) were estimated from the nominal conditions used in the equation:

U A = Q ˙ Δ T l m (13)

Table 3
Nominal Conditions of the Prototype Absorption Chiller.

Comparison of the experimental data and numerical results of the thermodynamic modeling

To validate the thermodynamic modeling applied for the prototype absorption chiller, 10 operational scenarios were selected that take the flows of hot, cold and chilled water into account. The experimental data and the numerical results obtained were compared, considering the (hot, cold and chilled) outlet water streams. Figures 2 and 3 show the temperature profiles of the hot and chilled water, respectively, that were simulated by the model and those determined experimentally by Zamora (2012Zamora, M. Optimización industrial y estrategia de control de una enfriadora de absorción de amoniaco/nitrato de litio con disipación por aire. Ph.D thesis. Universitat Rovira i Virgili, Spain (2012).).

Figure 2
Comparison of the temperature profiles obtained by the thermodynamic modeling and the experimental data for the Hot water.

Figure 3
Comparison of the temperature profiles obtained by the thermodynamic modeling and the experimental data for the Chilled water.

For the hot water circuit, the values obtained by the thermodynamic modeling and from experimental data showed the same trend, there being a minimal divergence between them. In the case of the chilled water circuit, the comparison showed a similar result to that of the hot water circuit; namely the same trend was followed and there was also a slight divergence between the simulated and experimental values. The minimum and maximum errors are 0.02% and 6% for the chilled water and the hot water, respectively. Therefore, the adjustment between the numerical and the experimental data can be considered good and, hence, the comparison is very good. As to the cold water circuit, the behavior is the same as that shown in the case of the hot water, but there is a little more divergence between the numerical and experimental data in all 10 of the scenarios. This fact can be attributed to the uncertainties of the experimental data (around 5%, as found by Zamora, 2012Zamora, M. Optimización industrial y estrategia de control de una enfriadora de absorción de amoniaco/nitrato de litio con disipación por aire. Ph.D thesis. Universitat Rovira i Virgili, Spain (2012).).

Comparison of the experimental data with the results from the characteristic equation

To validate the results obtained by implementing the characteristic equation method, a comparison with the experimental data was made in two ways: First, the results between the real experimental data were compared and secondly, so were the results from the experimental correlation coming from the adjustment of the experimental data, based on the data used in Puig et al. (2010Puig, A. M., López, V. J., Bruno, J. C. Coronas, A. Analysis and parameter identification for characteristic equations of single - and Double effect absorption chillers by means of multivariable regression, International Journal of Refrigeration , 33, 70-78 (2010). https://doi.org/10.1016/j.ijrefrig.2009.08.005
https://doi.org/10.1016/j.ijrefrig.2009....
).

The adjusted experimental correlations obtained from the data presented in Zamora (2012Zamora, M. Optimización industrial y estrategia de control de una enfriadora de absorción de amoniaco/nitrato de litio con disipación por aire. Ph.D thesis. Universitat Rovira i Virgili, Spain (2012).) and adapted by the methodology presented in Puig et al. (2010Puig, A. M., López, V. J., Bruno, J. C. Coronas, A. Analysis and parameter identification for characteristic equations of single - and Double effect absorption chillers by means of multivariable regression, International Journal of Refrigeration , 33, 70-78 (2010). https://doi.org/10.1016/j.ijrefrig.2009.08.005
https://doi.org/10.1016/j.ijrefrig.2009....
) can be expressed as:

Q ˙ e _ exp _ c o r r = a e T c h b e T a c + c e T g + d e (14)

Q ˙ g _ exp _ c o r r = a g T c h b g T a c + c g T g + d g (15)

The experimental data of the Prototype Absorption chiller were extracted from the study by Zamora (2012Zamora, M. Optimización industrial y estrategia de control de una enfriadora de absorción de amoniaco/nitrato de litio con disipación por aire. Ph.D thesis. Universitat Rovira i Virgili, Spain (2012).) considering the following operational temperature ranges: 7-15°C chilled water, 80-100°C hot water, and 32-45°C cold water. Seventeen (17) operating conditions of the absorption chiller were selected. Table 4 shows the values of the parameters of equations 16 and 17.

Table 4
Coefficients Values of equations 16 and 17.

Figures 4 and 5 compare the results of using the thermal activation power and the cooling capacity of the prototype, respectively. These were obtained by the characteristic equation method (Q g_ce ; Q e_ce ), experimental data (Q g_exp ; Q e_exp ) and the adjusted experimental correlations (Q g_corr ; Q e_corr ), arising from the total difference in temperature that considered the whole operational range of the equipment.

Figure 4
Comparison of the results obtained by the characteristic equation method, real experimental data and the correlations adjusted for the Thermal activation power (Q g ).

Figure 5
Comparison of the results obtained by the characteristic equation method, real experimental data and the correlations adjusted for the Cooling capacity (Q e ).

Figures 6 and 7 show that results obtained by implementing the characteristic equation method for the thermal activation power and the cooling capacity fit well over the operating range of the absorption chiller. This was considered a good adjustment since the minimum and maximum errors were around 1 to 10%, which is good when the complexity of the absorption and desorption processes in the cycle are considered, and also, because of the assumptions that were made to simulate the prototype chiller.

Figure 6
Comparison of the results obtained by the characteristic equation method, real experimental data and the adjusted correlations for the COP.

Figure 7
Comparison of the results obtained by the characteristic equation method, real experimental data and the adjusted correlations taking into the account the Minimum and Maximum errors.

Figure 6 shows the comparison of the COP of the absorption chiller results obtained by the characteristic equation method (COP ce ), the experimental data (COP exp ) and the adjusted experimental correlation (COP exp_corr ), arising from the total difference in temperature that considered the whole operational range of the equipment. Figure 7 shows their minimum and maximum errors.

Note that there are differences between results of the COP, see Figure 6, that could be due to propagation of error in the thermal activation power and cooling capacity. Once more, these were attributed to uncertainties in the experimental data (around 5%) and also to simplifying assumptions of the modeling.

Despite these errors, the adjustment can be considered good because, for most operating conditions, these deviations were not greater than 5%, especially at the nominal operational conditions of the prototype, namely when the hot, chilled and cold water were at temperatures of 90°C, 15°C and 37.5°C, respectively, represented by a ΔΔt of 23K where the deviation was lower than 1%.

As already mentioned, Figure 7 shows good agreement between the results obtained from the characteristic equation and the experimental data, and also when the experimental data and the results from the adjusted correlation are compared. For most of the operational range of the chiller, including the nominal condition, the deviations were 5% lower. The maximum errors of the results were found in the thermal power activation, around 9%, as was the minimum error of around 0.2%. These errors lead to maximum and minimum errors in the COP of 10% and 0.6%, respectively. Therefore, in order to tackle the overall uncertainties involved in operating the prototype, this could be considered a good adjustment for predicting the behavior of the systems.

Parametric analysis of the prototype NH3/LiNO3 absorption refrigeration chiller

The idea of this parametric analysis was to verify the thermodynamics of the different technical parameters such as: the type of configuration of series and parallel heat dissipation circuit and the temperatures of the (hot, cold and chilled water) external circuits, the mass flow rate of the ammonia-rich solution in the internal circuit of the prototype chiller, the influence of the flow mass rate according to the dissipation system and finally, the influence of the overheating at the outlet of the evaporator. In the parametric analysis, the effects were compared including and excluding the heat exchanger of the refrigerant of the prototype chiller.

COP Profile based on the configuration of the heat dissipation circuit (series and parallel) and the temperatures of the hot, cold and chilled water

Single-effect absorption systems can basically use two dissipation circuit configurations; series or parallel. The series configuration predicts that a single water line will flow through the absorber - condenser assembly, i.e., the circulation water passes first through the absorber and later either through the condenser or the dissipation system (cooling tower, air heater, air dissipation). On the other hand, the parallel configuration predicts that the line coming from the dissipation system will be divided into two sub lines, which keep the same inlet temperature, i.e., the cold dissipation water will enter the absorber and the condenser at the same temperature. These settings have different behaviors with regard to the performance of the chiller. In this section, it was decided to vary the COP based on the configuration with the system, whether or not the refrigerant heat exchanger was used, but nevertheless taking the hot and cold water inlet temperatures and the chilled water outlet into account.

In the parallel configuration the flow is divided into two streams that keep the same value for the water flow rate. This is done with the intention of having the same cold water inlet temperature in the two heat exchangers that integrate the heat dissipation system.

Figures 8 to 10 show the COP profile based on the inlet temperatures of the hot and cold water and the output of the chilled water, respectively.

Figure 8
COP Profile (with and without a refrigerant heat exchanger) varying the inlet hot water temperature considering the series and parallel configuration of the heat dissipation system.

Figure 9
COP Profile (with and without refrigerant heat exchanger) varying the inlet cold water temperature considering the series and parallel configuration of the heat dissipation system.

Figure 10
COP Profile (with and without refrigerant heat exchanger) varying the inlet temperature of the inlet chilled water, considering the series and parallel configuration of the heat dissipation system.

Initially, it should be noted that the behavior in terms of magnitudes is the same as in other simulations, i.e., the inclusion of the refrigerant heat exchanger increases the COP by approximately 3%.

Note that the parallel configuration results in the chiller performing better when the cold water dissipation flow is the same in both cases, since this configuration guarantees the same capacity to dissipate heat in both components (absorber and condenser). This is because the performance of the absorption cycle is better when there is a parallel configuration of the heat dissipation circuit because the temperature of the inlet water that goes to the condenser and the absorber is the same, and also the mass flow rate has the same value. Thus, this gives the system more capacity to dissipate heat, i.e., the useful dissipation temperature is low and the total flow rate of the cooling water is high. As to the series configuration, the values of the inlet water temperature are different. This is because the water first flows into the absorber and after the heat in this component is dissipated, the water passes through the condenser but at a higher temperature than at its inlet. Therefore, the capacity of the condenser is lower than in the absorption cycle with the parallel heat dissipation configuration (absorber - condenser). This has been discussed in the literature (Domínguez-Inzunza et al., 2014Domínguez-Inzunza, L. A., Hernández-Magallanes, J. A., Sandoval-Reyes, M., Rivera, W. Comparison of the performance of single-effect, half-effect, double-effect in series and inverse and triple-effect absorption cooling systems operating with the NH3-LiNO3 mixture, Applied Thermal Engineering , 66, 612-620 (2014). https://doi.org/10.1016/j.applthermaleng.2014.02.061
https://doi.org/10.1016/j.applthermaleng...
; Herold et al., 2016Herold, K. E., Radermacher, R., Klein, S. A. Absorption Chillers and Heat Pumps. 2nd Edition, CRC, Press LLC, USA (2016). https://doi.org/10.1201/b19625
https://doi.org/10.1201/b19625...
; Chahartaghi et al., 2019Chahartaghi, M., Golmohammadi, H., Shojaei, A.F. Performance analysis and optimization of new double effect lithium bromide-water absorption chiller with series and parallel flows, International Journal of Refrigeration , 97, 73-87 (2019). https://doi.org/10.1016/j.ijrefrig.2018.08.011
https://doi.org/10.1016/j.ijrefrig.2018....
).

Comparisons of the series and parallel configurations when analyzing the chiller with and without the refrigerant heat exchanger showed there was a maximum percentage increase of 5% when the temperature of the chilled water was varied and a minimum increase of 4% of the COP when the temperature of the cold water is varied.

COP Profile based on the mass flow rate of the ammonia-rich solution considering the dissipation temperature (cold water) and the chilled water temperature

This section shows the influence of the increase in the mass flow rate of the solution on the COP, but considering the dissipation temperatures (in the range of 28-38°C) and chilled water temperatures (in the range of range 2-10°C) of the prototype chiller, see Figures 11-12.

Figure 11
COP Profile (without rhe) varying the ammonia rich mass flow rate for dissipation water and chilled water temperatures at nominal conditions.

Figure 12
COP Profile (without rhe) varying the ammonia rich mass flow rate for dissipation water and chilled water temperatures at different conditions.

Figures 11 and 12 show the influence of the temperatures of the dissipated water and the chilled water, considering the prototype absorption refrigeration system without the refrigerant heat exchanger.

Figures 13 and 14 show the influence of the temperatures of the dissipated water and the chilled water temperatures considering the prototype absorption refrigeration system with the refrigerant heat exchanger.

Figure 13
COP Profile (with rhe) varying the ammonia rich mass flow rate for dissipation water and chilled water temperatures at nominal conditions.

Figure 14
COP Profile (with rhe) varying the ammonia rich mass flow rate for dissipation water and chilled water temperatures at different conditions.

In general, Figures 13 and 14 show that the behavior is maintained due to including the refrigerant heat exchanger, which always provides higher COPs than the prototype without this heat exchanger, at the same operating conditions. This is because the prototype needs to generate more refrigerant vapor, i.e., a higher activation power is required (generator heat flow), but the heat removal rate decreases (Evaporator heat flow) due to the low temperatures of the chilled water and, therefore, there is a higher heat rate of dissipation in the prototype.

It is important to note that, on varying the temperature of the chilled water (cooling effect), its return is smaller, which directly affects the cooling capacity of the prototype, whenever the system design conditions are used.

COP profile based on the overheating at the outlet of the evaporator

This section shows the influence of overheating at the evaporator outlet on generating vapor and hence on the COP of the prototype considering a fixed flow of the ammonia-rich solution required by the solution pump and varying the inlet hot water temperature. In addition to analyzing the effect of overheating under the nominal conditions.

Figure 15 shows the difference between the COP and the mass flow of the vapor produced in the generator (desorption process) of the chiller with and without overheating at the evaporator outlet based on the temperature of the hot water inlet, while Figure 16 shows this difference under nominal conditions.

Figure 15
Comparison of the COP and vapor mass flow rate considering (with/without) overheating at the evaporator output varying the inlet hot water temperature, including the refrigerant heat exchanger.

Figure 16
Comparison of the COP and vapor mass flow rate considering (with/without) overheating at the evaporator output varying the overheating, considering nominal conditions.

The effect of overheating at the outlet of the evaporator can be favorable in operational terms, since in energy terms this reduces the COP of the system compared to the COP of the chiller without this overheating. This effect can be understood by producing the refrigerant vapor of the generator (ammonia desorption process), since when the system overheats, it tends to produce less refrigerant vapor and, therefore, the refrigerating capacity in the evaporator is also reduced, leading to smaller COPs. This decrease is more relevant at low temperatures of the hot water (70-80°C) where the difference may be 18%, but at temperatures higher than 80°C, this is reduced by up to 3%. This fact can be attributed to vapor being generated, since the lower temperatures of the hot water will lead to refrigerant vapor being generated in both cases; however, whenever there is overheating, the rate at which refrigerant vapor is generated is even smaller.

Figure 16 shows the progressive degrading effect of COP on the chiller when overheating is introduced at the evaporator outlet, so that the generation of refrigerant vapor has a negative rate of production, leading to a lower capacity to remove the thermal heat from the evaporator and therefore reducing the COP of the system. This is proportional to the increase in this overheating at the evaporator outlet. In quantitative terms, the COP was reduced by approximately 6% since the overheating began to be added (0 to 5°C).

CONCLUSIONS

Implementing the thermodynamic modeling and the characteristic equation method enabled the behavior of the prototype absorption chiller to be determined with good accuracy. This was proven because the results obtained after comparing them were good for most of the operational range. In this paper, the parametric analysis of the prototype was presented. In summary, the most significant results of this study are as follows:

  • Comparison of the results of thermal power activation and the cooling capacity of the prototype absorption chiller, obtained by theoretical modeling and the characteristic equation values was very good, since the errors found were lower by 5% for most of the range of operational conditions;

  • The thermodynamic modeling and the characteristic equation method led to being able to determine the behavior of the prototype with good accuracy for all operational conditions;

  • The effect of considering the configuration of the heat dissipation system (cold water) was slightly higher when the system operates in parallel rather than in series;

  • The increase in the amount of the mass flow of the solution (solution rich in NH3) led to a decrease in the COP of the chiller, in a nearly linear way. This phenomenon occurs due to the dimensions of the heat exchangers (previously defined), i.e., the capacity of the heat exchanger was exceeded, which resulted in the COP of the chiller decreasing;

  • The addition of the refrigerant heat exchanger to the prototype absorption refrigeration enabled the COP of the chiller to increase by approximately 3%.

ACKNOWLEDGEMENT

The first author is grateful to the program Science without borders - CNPq -Brazil, for the scholarship for the Post-doctoral study (PDE:203489/2014-4) and also to Professor Alberto Coronas for his support during the Post-doctoral study at the Rovira and Virgili University and also to the Staff of that university, especially the CREVER group. The authors thank FACEPE/CNPq for financial support for the research project APQ-0151-3.05/14 and also the CNPq for financial support for the research project - Universal 402323/2016-5.

REFERENCES

  • Acuña, A., Velázquez, N., Cerezo, J. Energy analysis of a diffusion absorption cooling system using lithium nitrate, sodium thiocyanate and water as absorbent substances and ammonia as the refrigerant, Applied Thermal Engineering, 51, 1273-1281 (2013). https://doi.org/10.1016/j.applthermaleng.2012.10.046
    » https://doi.org/10.1016/j.applthermaleng.2012.10.046
  • Akrami, E., Nemati, A., Nami, H., Ranibar, F. Exergy and exergoeconomic assessment of hydrogen and cooling production from concentrated PVT equipped with PEM electrolyzer and LiBr-H2O absorption chiller, International Journal of Hydrogen Energy, 43, 622-633 (2018). https://doi.org/10.1016/j.ijhydene.2017.11.007
    » https://doi.org/10.1016/j.ijhydene.2017.11.007
  • Albers, J., Ziegler, F. Improved control strategies for solar assisted cooling systems with absorption chillers using a thermosyphon generator, In: Proceedings of the Int. Solar Air. Cond., October, Kloster Banz, Germany (2015).
  • Álvarez, M.E., Hernández, J.A., Bourois, M. Modelling the performance parameters of a horizontal falling film absorber with aqueous (lithium, potassium, sodium) nitrate solution using artificial neural networks, Energy, 102, 313-323 (2016). https://doi.org/10.1016/j.energy.2016.02.022
    » https://doi.org/10.1016/j.energy.2016.02.022
  • Amaris, C., Bourouis, M., Vallès, M., Salavera, D., Coronas, A. Thermophysical Properties and Heat and Mass Transfer of New Working Fluids in Plate Heat Exchangers for Absorption Refrigeration Systems, Heat Transfer Engineering, 36, 388-395 (2014). https://doi.org/10.1080/01457632.2014.923983
    » https://doi.org/10.1080/01457632.2014.923983
  • Azhar, M., Siddiqui, M.A. Energy and Exergy Analyses for Optimization of the Operating Temperatures in Double Effect Absorption Cycle, Energy Procedia, 109, 211-218 (2017). https://doi.org/10.1016/j.egypro.2017.03.043
    » https://doi.org/10.1016/j.egypro.2017.03.043
  • Buonomano, A., Calise, F., Palombo, A. Solar heating and cooling systems by absorption and adsorption chillers driven by stationary and concentrating photovoltaic/thermal solar collectors: Modelling and simulation, Renewable and Sustainable Energy Reviews, 82, 1874-1908 (2018). https://doi.org/10.1016/j.rser.2017.10.059
    » https://doi.org/10.1016/j.rser.2017.10.059
  • Cai, D., He, G., Tian, Q., Bian, Y., Xiao, R., Zhang, A. First law analysis of a novel double effect air-cooled non-adiabatic ammonia/salt absorption refrigeration cycle, Energy Conversion and Management, 98, 1-14 (2015). https://doi.org/10.1016/j.enconman.2015.03.083
    » https://doi.org/10.1016/j.enconman.2015.03.083
  • Cai, D., Jiang, J., He, G., Li, K., Niu, L., Xiao, R. Experimental evaluation on thermal performance of an air-cooled absorption refrigeration cycle with NH3-LiNO3 and NH3-NaSCN refrigerant solutions. Energy Conversion and Management , 103, 32-43 (2016). https://doi.org/10.1016/j.enconman.2016.04.089
    » https://doi.org/10.1016/j.enconman.2016.04.089
  • Cuenca, Y., Salavera, D., Vernet, A., Teja, A. S., Valles, M. Thermal conductivity of ammonia + lithium nitrate and ammonia + lithium nitrate + water solutions over a wide range of concentrations and temperatures, International Journal of Refrigeration, 38, 333-340 (2014). https://doi.org/10.1016/j.ijrefrig.2013.08.010
    » https://doi.org/10.1016/j.ijrefrig.2013.08.010
  • Chahartaghi, M., Golmohammadi, H., Shojaei, A.F. Performance analysis and optimization of new double effect lithium bromide-water absorption chiller with series and parallel flows, International Journal of Refrigeration , 97, 73-87 (2019). https://doi.org/10.1016/j.ijrefrig.2018.08.011
    » https://doi.org/10.1016/j.ijrefrig.2018.08.011
  • Domínguez-Inzunza, L. A., Hernández-Magallanes, J. A., Sandoval-Reyes, M., Rivera, W. Comparison of the performance of single-effect, half-effect, double-effect in series and inverse and triple-effect absorption cooling systems operating with the NH3-LiNO3 mixture, Applied Thermal Engineering , 66, 612-620 (2014). https://doi.org/10.1016/j.applthermaleng.2014.02.061
    » https://doi.org/10.1016/j.applthermaleng.2014.02.061
  • Farshi, L. G., Infante-Ferreira, C. A., Mahmoudi, S. M. S. First and second law analysis of ammonia/salt absorption refrigeration systems, International Journal of Refrigeration , 40, 111-121 (2014). https://doi.org/10.1016/j.ijrefrig.2013.11.006
    » https://doi.org/10.1016/j.ijrefrig.2013.11.006
  • Guido, W.H., Laner, W., Petersen, S., Ziegler, F. Performance of absorption chillers in field tests, Applied Thermal Engineering , 134, 353-359 (2018). https://doi.org/10.1016/j.applthermaleng.2018.02.013
    » https://doi.org/10.1016/j.applthermaleng.2018.02.013
  • Hernández-Magallanes, J. A., Domínguez-Inzunza, L. A., Gutiérrez-Urueta, G., Soto, P., Jiménez, C., Rivera, W. Experimental assessment of an absorption cooling system operating with the ammonia/lithium nitrate mixture, Energy 78, 685-692 (2014). https://doi.org/10.1016/j.energy.2014.10.058
    » https://doi.org/10.1016/j.energy.2014.10.058
  • Herold, K. E., Radermacher, R., Klein, S. A. Absorption Chillers and Heat Pumps. 2nd Edition, CRC, Press LLC, USA (2016). https://doi.org/10.1201/b19625
    » https://doi.org/10.1201/b19625
  • Jiang, J., Liu, Y., He, G., Liu, Y., Cai, D., Liang, X. Experimental investigations and an updated correlation of flow boiling heat transfer coefficients for ammonia/lithium nitrate mixture in horizontal tubes, International Journal of Heat and Mass Transfer, 112, 224-235 (2017). https://doi.org/10.1016/j.ijheatmasstransfer.2017.04.135
    » https://doi.org/10.1016/j.ijheatmasstransfer.2017.04.135
  • Jiménez, C., Rivera, W. Experimental assessment of an absorption cooling system operating with the ammonia/lithium nitrate mixture, Energy, 78, 685-692 (2014). https://doi.org/10.1016/j.energy.2014.10.058
    » https://doi.org/10.1016/j.energy.2014.10.058
  • Kohlenbach, P., Ziegler, F. A dynamic simulation model for transient absorption chiller performance. Part II: Numerical results and experimental verification, International Journal of Refrigeration , 31, 226-233 (2008). https://doi.org/10.1016/j.ijrefrig.2007.06.010
    » https://doi.org/10.1016/j.ijrefrig.2007.06.010
  • Libotean, S., Martin, A., Salavera, D., Valles, M., Esteve, X., Coronas, A. Densities, Viscosities, and Heat Capacities of Ammonia + Lithium Nitrate and Ammonia + Lithium Nitrate + Water Solutions between (293.15 and 353.15) K, Journal of Chemical and Engineering Data, 53, 2383-2388 (2008). https://doi.org/10.1021/je8003035
    » https://doi.org/10.1021/je8003035
  • Libotean, S., Salavera, D., Valles, M., Esteve, X., Coronas, A. Vapor-Liquid Equilibrium of Ammonia + Lithium Nitrate + Water and Ammonia + Lithium Nitrate Solutions from (293.15 to 353.15) K, Journal of Chemical and Engineering Data , 52, 1050-1055 (2007). https://doi.org/10.1021/je7000045
    » https://doi.org/10.1021/je7000045
  • Maryami, R., Dehghan, A.A. An exergy based comparative study between LiBr/water absorption refrigeration systems from half effect to triple effect, Applied Thermal Engineering , 124, 103-123 (2017). https://doi.org/10.1016/j.applthermaleng.2017.05.174
    » https://doi.org/10.1016/j.applthermaleng.2017.05.174
  • Moreno-Quintanar, G., Rivera, W., Best, R. Comparison of the experimental evaluation of a solar intermittent refrigeration system for ice production operating with the mixtures NH3/LiNO3 and NH3/LiNO3/H2O. Renewable Energy, 38, 62-68 (2012). https://doi.org/10.1016/j.renene.2011.07.009
    » https://doi.org/10.1016/j.renene.2011.07.009
  • Myat, A., Thu, K., Kim, Y. D., Chakraborty, A., Chun, W. G., Choon, K. N. A second law analysis and entropy generation minimization of an absorption chiller, Applied Thermal Engineering , 31, 2405-2413 (2011). https://doi.org/10.1016/j.applthermaleng.2011.04.004
    » https://doi.org/10.1016/j.applthermaleng.2011.04.004
  • Ochoa, A.A.V., Dutra, J.C.C., Henríquez, J.R.G., Rohatgi, J. Energetic and exergetic study of a 10RT absorption chiller integrated into a microgeneration system, Energy Conversion and Management , 88, 545-553 (2014). https://doi.org/10.1016/j.enconman.2014.08.064
    » https://doi.org/10.1016/j.enconman.2014.08.064
  • Ochoa, A.A.V., Dutra, J.C.C., Henríquez, J.R.G., Santos, C.A.C. dos. Dynamic study of a single effect absorption chiller using the pair LiBr/H2O, Energy Conversion and Management , 108, 30-42 (2016). https://doi.org/10.1016/j.enconman.2015.11.009
    » https://doi.org/10.1016/j.enconman.2015.11.009
  • Ochoa, A.A.V., Dutra, J.C.C., Henríquez, J.R.G., Santos, C.A.C. dos, Rohatgi, J. The influence of the overall heat transfer coefficients in the dynamic behavior of a single effect absorption chiller using the pair LiBr/H2O, Energy Conversion and Management , 136, 270-282 (2017). https://doi.org/10.1016/j.enconman.2017.01.020
    » https://doi.org/10.1016/j.enconman.2017.01.020
  • Ochoa, A.A.V., Costa, J.A.P. da, Franco, S.S. Implementation of the Characteristic Equation Method applied to an Absorption Chiller LiBr/H2O of Commercial type, CIENTEC, 9, 24-38 (2017).
  • Puig, A. M., López, V. J., Bruno, J. C. Coronas, A. Analysis and parameter identification for characteristic equations of single - and Double effect absorption chillers by means of multivariable regression, International Journal of Refrigeration , 33, 70-78 (2010). https://doi.org/10.1016/j.ijrefrig.2009.08.005
    » https://doi.org/10.1016/j.ijrefrig.2009.08.005
  • Sabbagh, A.A., Gómez, J.M., Optimal control of single stage LiBr/water absorption chiller, International Journal of Refrigeration , 92, 299-311 (2018). https://doi.org/10.1016/j.ijrefrig.2018.05.007
    » https://doi.org/10.1016/j.ijrefrig.2018.05.007
  • Tillner-Roth, R., Harms-Watzenberg, F., Baehr, H.D. A new fundamental equation for ammonia. DKV-Tagungsbericht, 20, 167-181 (1993). (in German).
  • Ventas, R., Lecuona, A., Rodriguez-Hidalgo, M.C. Performance analysis of an absorption double-effect cycle for power and cold generation using ammonia/lithium nitrate, Applied Thermal Engineering , 115, 256-266 (2017). https://doi.org/10.1016/j.applthermaleng.2016.12.102
    » https://doi.org/10.1016/j.applthermaleng.2016.12.102
  • Ventas, R., Lecuona, A., Vereda, C., Legrand, M. Two-stage double-effect ammonia/lithium nitrate absorption cycle, Applied Thermal Engineering , 94, 228-237 (2017). https://doi.org/10.1016/j.applthermaleng.2015.10.144
    » https://doi.org/10.1016/j.applthermaleng.2015.10.144
  • Wang, J., Li, X., Wang, B., Wu, W., Song, P., Shi, W. Performance Comparison between an Absorption-compression Hybrid Refrigeration System and a Double-effect Absorption Refrigeration System, Energy Procedia , 205, 241-247 (2017). https://doi.org/10.1016/j.proeng.2017.09.959
    » https://doi.org/10.1016/j.proeng.2017.09.959
  • Zamora, M. Optimización industrial y estrategia de control de una enfriadora de absorción de amoniaco/nitrato de litio con disipación por aire. Ph.D thesis. Universitat Rovira i Virgili, Spain (2012).
  • Zamora, M., Bourouis, M., Coronas, A., Vallès, M. Part-load characteristics of a new ammonia/lithium nitrate absorption chiller, International Journal of Refrigeration , 56, 43-51 (2015). https://doi.org/10.1016/j.ijrefrig.2014.11.005
    » https://doi.org/10.1016/j.ijrefrig.2014.11.005
  • Zamora, M., Bourouis, M., Coronas, A., Vallès, M. Pre-industrial development and experimental characterization of new air-cooled and water-cooled ammonia/lithium nitrate absorption chillers, International Journal of Refrigeration , 45, 189-197 (2014). https://doi.org/10.1016/j.ijrefrig.2014.06.005
    » https://doi.org/10.1016/j.ijrefrig.2014.06.005
  • Zinet, M., Rulliere, R., Haberschill, P. A numerical model for the dynamic simulation of a recirculation single-effect absorption chiller, Energy Conversion and Management , 62, 51-63 (2012). https://doi.org/10.1016/j.enconman.2012.04.007
    » https://doi.org/10.1016/j.enconman.2012.04.007

NOMENCLATURE

  • A  Ratio enthalpy differences of the absorber, dimensionless
  • B  isotherm slope in Duhring Chart - “Coefficient of Duhring”, dimensionless
  • C  Ratio enthalpy differences of the condenser, dimensionless
  • G  Ratio enthalpy differences of generator, dimensionless
  • Z  Intersept of the Duhring Equation, dimensionless
  • COP  Coefficient of Performance, dimensionless
  • m  Mass flow rate [kg.s-1]
  • h  Enthalpy [kJ.kg-1.K-1]
  • Q  Heat Flow [kW]
  • S  Characteristic parameter - Proportion of the overall heat transfer coefficient of each component [kW.K-1]
  • T  arithmetic mean internal temperature [°C]
  • t  arithmetic mean external temperature [°C]
  • UA  Heat transmission [kW.K-1]
  • ∆t  Temperature difference [K]
  • ∆∆t  Total temperature difference or characteristic temperature function [K]
  • ∆Tlm  Logarithmic mean temperature difference [°C]
  • NH3  ammonia
  • LiNO3  Lithium nitrate
  • X  Concentration of the solution [%]
    Greek Symbols
  • α  Characteristic parameter - Distribution of the overall heat transfer coefficient inside the chiller [kW.K-1]
    Subscripts
  • A, a, C, c, G, g, E, e  Generator, absorber, evaporator, condenser
  • ec  Characteristic equation
  • gec  Generator characteristic equation
  • eec  Characteristic equation of the evaporator
  • diss, chi  Dissipated, chilled
  • max, loss  Maximum and loss heat
  • ref  Refrigerant
  • sol  Solution
  • thrust, lift  Thrust and lift temperature
  • strong, weak  Strong and weak solution
  • minE  Minimum evaporator
  • she, rhe  Solution heat exchanger and refrigerant heat exchanger
  • in, out  Inlet and outlet stream
  • X  Components
  • hot, cold  Hot and cold fluids
  • sat  Saturation state
  • exp  Data from the experimental test
  • Sim  Data obtained from the simulation
  • ch, ac  Chilled and cold water stream
  • e_exp_corr, g_exp_corr  Adjusted experimental correlation - Evaporator and generator