Determination of reinforcing bars for tests of hollow core slabs with continuity

Abstracts

The structural designs of floors formed by hollow core slabs usually consider these as simply-supported slabs. In recent years there have been project changes and hollow core slabs with continuity are widely used. The objective of this study is to suggest a way to calculate the reinforcement bars to be used in tests with continuity provided by a structural topping. Thus, this paper presents a method based on the maximum positive resistance moment and maximum shear strength of a hollow core slab. The method is applied to a test in hollow core slab specimens which have the following dimensions: 2 m width, 6 m long, and 21 cm high. The results indicated that the method was satisfactory to the performed test, and can therefore be applied to the other test configurations or even designs.

hollow core slab; continuity; reinforcing bars; topping; tests


Os projetos estruturais de pavimentos formados por lajes alveolares usualmente as consideram como simplesmente apoiadas. Nos últimos anos têm ocorrido modificações nos projetos, de tal forma que lajes alveolares com continuidade têm sido muito utilizadas. O objetivo deste trabalho é sugerir uma forma de se calcular a armadura negativa para ser utilizada em ensaios com continuidade obtida por meio de uma capa estrutural. Para isso, apresenta-se um método baseado no máximo momento resistente positivo e na máxima força cortante resistente de uma laje alveolar. O método é aplicado a um ensaio em lajes alveolares com as seguintes dimensões: 2 m de largura, 6 m de comprimento e 21 cm de altura. Os resultados indicaram que o método foi satisfatório para o ensaio realizado e, portanto, pode ser aplicado para outras configurações de ensaio, ou até mesmo em projetos.

laje alveolar; continuidade; armadura negativa; capa estrutural; ensaios


Determination of reinforcing bars for tests of hollow core slabs with continuity

A. P. SantosI; M. A. FerreiraII; R. C. CarvalhoII; L. M. PinheiroI

IUniversity of Sao Paulo, Sao Carlos School of Engineering, Department of Structural Engineering, Sao Carlos, SP, Brazil, andreiltonsantos@yahoo.com.br, libanio@sc.usp.br

IIFederal University Federal of Sao Carlos, Department of Civil Engineering, Sao Carlos, SP, Brazil, marcelo@power.ufscar.br, chust@power.ufscar.br

ABSTRACT

The structural designs of floors formed by hollow core slabs usually consider these as simply-supported slabs. In recent years there have been project changes and hollow core slabs with continuity are widely used. The objective of this study is to suggest a way to calculate the reinforcement bars to be used in tests with continuity provided by a structural topping. Thus, this paper presents a method based on the maximum positive resistance moment and maximum shear strength of a hollow core slab. The method is applied to a test in hollow core slab specimens which have the following dimensions: 2 m width, 6 m long, and 21 cm high. The results indicated that the method was satisfactory to the performed test, and can therefore be applied to the other test configurations or even designs.

Keywords: hollow core slab, continuity, reinforcing bars, topping, tests.

1. Introduction

The hollow core slabs were developed in the 1950s in the United States of America and in Europe on account of the production progress in concrete technology and also the increased use of long-line prestressed system. This type of structure is known for providing economic flooring and covering systems, high speed assembly, small number of elements and low self-weight. It is estimated that the self-weight of a hollow core unit is about half the size of a solid section of the same height. Figure 1 shows an example of hollow core slab floors, Figure 2 presents examples of hollow core units, and Figure 3 displays a typical cross section.




Structurally, the hollow core slabs provide the efficiency of a prestressed element, reaching considerable spans with high load bearing capacity and small displacements. Moreover, if properly designed and detailed, they help to distribute the horizontal loads through the floor diaphragm effect.

Another important benefit of the hollow core slabs is fire resistance. According to PCI [3] a hollow core panel can resist up to four hours when subjected to high temperatures. This resistance depends on the height of the element and also on the cover of the reinforcement.

Usually these slabs are designed assuming simple supports. This happens because they are prestressed elements in which pretensioning is used, with the prestressed tendon placed near the bottom face. This provides the slabs high load bearing capacity, large spans, and small displacements.

However, a connection between two hollow core slabs can be implemented to ensure the negative moment resistance. This is called continuity.

This continuity can be made by placing reinforcement bars over the supports, inside the cover (Figure 4), or in openings made in the cores (Figure 5), in the regions of negative bending moment.



1.1 Tests of hollow core slabs

Experimental analysis of hollow core slabs have been carried out in several research centers worldwide in order to study their behavior alone or together. The main subjects studied are: shear and bending.

Bending tests can be made according to the FIP guidelines [4]. A rigid beam should be used to transfer the force to the slab, for example a steel beam. The rigid beam has the purpose to ensure a uniform load distribution over the entire width of the slab. This steel beam must have a minimum height of 15 cm, and 25 cm of height is indicated for tests using a hydraulic jack. The force is applied in the middle of the span, as shown in Figure 6. The standard test can be used to evaluate the shear strength of the slab, also suggested in the FIP guidelines [4]. The scheme of this test is similar to that presented for bending tests (Figure 6). However, the rigid beam must be positioned near one of the supports, at a distance of two and a half times the slab height.


Rigid beams are also used in tests of hollow core slabs with continuity in order to simulate a transversal linear load in the center of the each slab, characterizing a bending test. Figure 7 presents a schema for continuous slabs test, with the instrumentation used in this work.


1.2 Justification

In Brazil, many buildings made with precast concrete have their floors constructed with hollow core slabs, commonly using topping to solidify the slabs. In these cases the use of top reinforcement over the supports is common. However, this reinforcement is not always considered in order to take the continuity in account. Therefore, it is important to analyze continuity in floors with hollow core slabs in which the materials and structural elements are used according to the Brazilian reality.

1.3 Objective

The objective of this work is to determine a methodology to calculate the negative reinforcement to be used in the experimental analyses, on full-scale test, of hollow core slabs with continuity by adding the reinforcement bars inside the topping (Figure 4). This methodology can be employed in customary design situations, provided it is appropriately adapted.

1.4 Methodology

This method includes discussing the theories, present the deductions and use the equations necessary to obtain the negative reinforcement. Furthermore, to analyze its performance in a test considering the self-weight and two concentrated loads, one for each span.

2. Advantages to promote continuity

Some technical papers on continuity demonstrate approaches to obtain benefits when performing continuity. Table 1 describes these advantages.

In the structural design of these elements, each benefit should be taken into consideration according to the aspects of the project.

However, with regards to the experimental analysis, of the three advantages cited in Table 1, the most plausible situation that can be analyzed and controlled in the laboratory is the first one. Therefore, comparative tests between the simple support situation and with continuity can be made for a single element, in other words, with the same geometry and materials, the same amount of prestressing bars (Ap) and the same span (ℓ).

3. Changes in the structural system

The design of a hollow core slab considering continuity must be obey the two phases described below:

  • The first one corresponds to the simply supported slab condition. At this phase the self-weight of the precast slab has an effect (g1) and also the weight of the concrete cast in situ (g2), corresponding to the topping. The slab must resist the positive moment in the middle of the span. This first phase occurs during the continuity test;

  • The second phase corresponds to connection with continuity and the emergence of rigid support. In this case, the positive moment is the sum between the positive moment obtained in the first phase and related to the second phase, in which the other dead loads (g3) and the live loads (q) act. Consequently, the maximum negative moment is that calculated for the second phase, with the dead and live loads in the most unfavorable conditions. In the continuity test the second phase is represented by the hydraulic jack and the self-weight of the steel beams used to promote the load.

4. Determination of the continuity reinforcement bars

The design of a hollow core slab, taking into account continuity, can be made according to the model proposed by PETRUCELLI [10], adding one step that consist in calculating the continuity reinforcement bars (As). It must also consider the change in the structural system discussed in section 3.

As mentioned earlier, these reinforcement bars can be obtained considering the full action of the theoretical negative moment, commonly denominated as elastic moment. Furthermore, As can be calculated taking into account a fraction of this moment.

However the negative bending moment depends on the value of the applied load. As this is a variable in the experimental analysis, the question is how to determine the amount of reinforcement bars (As), for the experimental analyses, corresponding to 100% of continuity.

To solve that question it is necessary to set a criterion and through this obtain the reinforcement As corresponding to 100% of continuity. One possible criterion is to consider the maximum resistance positive moment of the prestressing bars (Ap) and then analyze the maximum shear resistance of hollow core slabs to be tested.

4.1 Maximum resistance positive moment

To understand the criterion of the slab's maximum positive resisting moment is required to use a hypothetical bending test with a simply supported slab. Figure 8 shows the structural scheme of this test highlighting the bending moment diagrams due to self-weight of the slab (g1) and the weight of the topping (g2) and later due to the action of the hydraulic jack (F1).


Therefore, considering a hollow core slab element with the geometry and materials characteristics, also prestressing bars (Ap) and span (ℓ) determined, the maximum positive moment (Mpos,tot,1) that the prestressing bars resists in simple support condition is given by the sum of the positive moments corresponding to the loads g1, g2, and F1.

Table 2 presents the equations for the hypothetical flexural test for simply supported slabs.

Figure 9 shows the bending moment diagram for the same slabs, assuming continuity in the intermediate support. In this Figure, F2 corresponds to the hydraulic jack in the continuity test. Thus, the total positive bending moment for this test (Mpos,tot,2) is given by equation 2.


Mpos,tot,1 can be obtained using the value of Ap. The value of M3, which corresponds to the positive moment due to the force F2 applied to the middle of the slab for the test with continuity, can be obtained equating Mpos,tot,1 with Mpos,tot,2.

Once M3 is known the F2 force value can be calculated, and through this obtain the moment M4. Finally, using M4 the reinforcement bar, As, is calculated, in terms of 100% of continuity.

After this the ratio between F1 and F2 can be determined. If F2 is greater than F1 it proves the increasing support capacity. Table 3 shows the equations to determine As for the continuity tests.

In addition to the variables already determined, Table 3 also show:

  • z = lever arm balance in this section with simple bending. This value can be different, considering the balance with positive and negative moment;

  • fyk = characteristic yielding stress of reinforcement bars.

4.2 Bending moment M4 and the support condition

As the intermediate support consists of a connection in precast concrete, the value of As is calculated with the negative bending moment (M4) in the section in which rotation occurs. Thus the geometry of Figure 10 was used, according to the nomenclature shown below:

  • F2 = concentrated load applied at the middle span for the test with continuity;

  • θ = rotation in the section where the slab begins supporting on the beam (rotation section);

  • M4,1 = negative bending moment at the center of the support;

  • M4,2 = negative bending moment at the center of rotation;

  • M3 = positive bending moment due to the F2;

  • a = distance between the edges of the hollow core slabs;

  • b = support length of the hollow core slab;

  • c = distance between the bending moment equal to zero and the rotation section;

  • hc = height of the cover (topping);

  • h = height of the hollow core slab;

  • 1 = distance between the fixed support and bending moment equal to zero;

  • 2 = distance between the concentrated load (F2) and the moment equal to zero;

  • ℓ/2 = half of the span.

Figure 10

4.3 Verification of the shear force

The criteria suggested for establishing 100% of continuity reinforcement bars through the maximum moment of resistance by the prestressing bars must be complemented by verifying the shear force.

Performing a continuity test (Figure 7) it can show that the hollow core slab reaches failure by shear force before the yielding or failure of the continuity reinforcement bar. In other words, the concentrated load corresponding to the failure can be less than that expected by the flexure analysis.

The verification of shear force in hollow core slabs is widely researched. A recent study by CATOIA [11] addresses this verification in regions of flexural cracks. In Catoia's work, several shear force equations were studied and compared with test results. The equation of the Brazilian code ABNT NBR 6118:2007 [12] was satisfactory evaluated in terms of verifying shear force, especially for hollow core slabs with or without topping and concentrated load applied at 2.5 h, where h is the height of the element being tested (section with or without topping).

The shear force was verified using the formulation of the Brazilian code ABNT NBR 6118:2007 [12] which is based on the European formulation, and which serves as a basis for its use in another Brazilian code, ABNT NBR 14861:2011 [13] that especially addresses the hollow core slabs. However, they are similar especially when there is no filled cores, as in this work.

According to Brazilian code ABNT NBR 6118:2007 [12], a slab can be made without transverse tension reinforcement when the equation 6 is satisfied.

  • VSd = acting shear force of design;

  • VRd1 = resisting shear force of design;

  • τRd = resisting shear stress of design – τRd = 0,25 fctd;

  • fctd = concrete tensile strength – fctd = fctk,inf / γc;

  • k = |1.6 - d|> 1 (d in meters);

  • ρ1 = As1 / (bw d) < 0.02;

  • As1 = steel area considered in the pin effect;

  • bw = slab width discounting voids corresponding to the cores;

  • d = depth of the slab, measured from the extreme compression fiber to the centroid of the tensioning reinforcement;

  • σcp = concrete compression stress due to the prestressing force – σcp = Nsd / Ac;

  • NSd = longitudinal force due to prestressing;

  • Ac = area of the concrete cross section.

Equation 7 shows the VSd value considering the concentrated load applied to the continuity test responsible for the failure by shear (F2,Q). This equation considers that the concentrated load (F2) is applied in the middle of the span, as shown in Figure 9. If there is any change in the position of the concentrated load, equation 7 should be adapted.

Therefore, the force value one wants to know (F2,Q) depends on the reinforcement ratio (ρ1), in other words, F2,Q depends on the negative reinforcement (As).

Therefore the As value is used to verify shear, with As obtained according to the flexural test with continuity, and then the F2,Q is calculated.

If F2 is less than F2,Q, the slab will not achieve failure by shear force. Otherwise, the continuity reinforcement will have to be calculated again, limited by the force F2,Q. This can be done by replacing, in Table 3, F2 by F2,Q, again calculating M4,1 and M4,2, and finally As.

Table 4 shows the summary of the equations when shear force is considered. Figure 11 presents the flow chart of the calculation of As by the criteria suggested to establish 100% of continuity reinforcement bars for the maximum resistance moment of the hollow core slab.


5. Experimental program

The experimental test in this paper is part of an ongoing doctoral program at the Department of Structural Engineering, Sao Carlos School of Engineering, University of Sao Paulo (SET/EESC/USP), in Brazil. The tests are being conducted at the Study and Technology Center in Precast Concrete, Department of Civil Engineering, Federal University of Sao Carlos (NETPRE/DECiv/UFSCar). The hollow core slabs were donated to this research as part of the agreement between the Brazilian Association of Industrialized Concrete Construction (ABCIC) and the aforementioned universities. The slabs were manufactured by LATTICE SLAB (LAJE TRELIÇADA) IND. and COM. LTDA., headquartered in Cuiaba (MT), and comprise a part of the hollow core slabs (Figure 12) for the soccer stadium Arena Pantanal, in Cuiaba, Mato Grosso state, Brazil.


The experimental test in question was performed on March 7, 2012 in full-scale hollow core slabs. These slabs had the following dimensions: width 2.00 m, length 6.00 m and height 0.21 m. Figure 13 shows a panoramic view of the test.


Figure 14 shows the cross section of the hollow core slab. For the concrete compressive characteristic strength (fck) and the concrete compressive strength at 24 hours (fcj,24h) 40 MPa and 21 MPa were used, respectively. For the prestressing bars, 9-wire strands of 12.7 mm diameter, steel CP 190 – RB were used. The initial prestressing force (in each strand) was 142 kN. The geometric properties are shown in Table 5, while the material properties are shown in Table 6.


Differently from Figures 8 and 9, the concentrated load was applied at a distance of 2.10 m from the center of the model, as shown in Figure 15. The span (ℓ) of the test was 4.82 m.


6. Results

Using the methodology set out in item 4 of this paper, it is possible to draw curves simulating other tests for the slab in question. Table 7 shows the design of the continuity reinforcement bars for the followings spans (in meters): 3.75; 5.00; 6.25; 7.50; 8.75; 10.00.

Table 8 shows the summary of the concentrated loads for the failure, also indicating the real capacity increase of the slab to withstand the loads, through the F2/F1 ratio and the shear force resistance (F1,Q) for the simple support test.

Based on Table 8 it was possible to plot the curves shown in Figure 16. This figure shows five curves relating the concentrated load to the failure of the slab, by flexure (F1 or F2) or shear (F1,Q or F2,Q) with the spans for the hypothetical tests in Table 7.


These curves are explained below. In all cases, it is considered that the forces are positioned at the middle span of each slab.

  • F1 – Simple supports – Flexural – Concentrated loads of the hypothetical simple supports slabs in flexural tests;

  • F1,Q – Simple supports – Shear – Concentrated loads of the hypothetical simple supports slabs in shear tests;

  • F2 – Continuity – Flexural – Concentrated loads corresponding to the hypothetical slabs with continuity in flexural tests;

  • F2,Q – Continuity – Shear – Concentrated loads corresponding to the hypothetical slabs with continuity in shear tests;

  • F2,E – Continuity – Envelopment – Considers the most unfavorable situation between F2 and F2,Q characterizing an envelope. This envelope can also be seen in Tables 7 and 8, emphasizing the most unfavorable situation.

6.1 Calculation of the continuity reinforcement bars to use in the tests

The calculations to obtain the continuity reinforcement bars (As) for the tests are presented.

Figure 15 shows the configuration of the span (ℓ) and the position of the applied load (F2). This test used a span of 4.82 m, and the distance from the center of the model to the load application point of 2.10 m. Therefore, it should be mentioned that the internal stress was calculated in accordance with the test configuration. This was performed by using the conversions shown in Table 9.

Moreover, the following should be taken into account:

  • σpt, = 107.67 kN/cm² (prestressing stress considering the losses, calculated from manufacturing until the date of the test, equals to 24.18%);

  • Np = 107.67 (kN/cm²) x 8.91 (cm²) = 959.29 kN (prestressing force acting on the section).

The results are shown in Tables 10, 11, 12 and 13. Note that as it is an experimental analysis fck was used instead of fcd. The same applies to the value of fctd, which was replaced by fctk,inf.

Since the value of F2,Q is less than that of F2, it is necessary repeat the calculations in Table 11 using F2,Q instead of F2, and this is done in Table 13.

It is worth noting that the increasing load capacity of the slab was of 1.09 (Table 12) and not 1.82 (Table 10).

Thus, the continuity reinforcement bars corresponding to 100% is As = 19.56 cm², limited by the verification of the shear force. Therefore, 17 bars of diameter 12.5 mm were used, spaced of 12 cm, totaling 20.86 cm².

The cracking moment of the topping (Mr) and the force F2 corresponding to this cracking are shown and calculated in Table 14.

6.2 Test results

Figure 17 shows the force-displacement curves (F2 versus δ) obtained from the values measured by the load cells and displacement transducers. The blue curve (right in Figure 17) and the red curve (left) correspond to the slabs highlighted in blue (left of Figure 17) and red (right). In addition, the F2 value includes the self-weight of the rigid steel beams (equal to 10.7 kN) and the force applied by the hydraulic jack.


The maximum load obtained, also considering the self-weight value of the rigid steel beams, was F2 = 272.0 kN (each slab).

The cracking moment of the topping can be seen in the curves of Figure 17 for values of around F2 = 107.9 kN.

Moreover, based on Figure 17, the maximum displacements resulted in δ = 4.7 mm and δ = 9.5 mm, respectively, at the right (in red, Figure 13) and left (in blue, in the same figure).

7. Conclusions

According to the results it is concluded that the method presented was able to accurately predict the behavior of the system and especially the failure mode, showing to be adequate for planning continuity tests in hollow core slabs subjected to concentrated loads. The following facts were observed:

  • The model tested reached failure by shear force, as provided in the calculations;

  • The F2 force estimated for the cracking of the topping (F2 = 117.59 kN, Table 14) was close to the real condition (F2 = 107.9 kN, Figure 17);

  • Similarly, the F2 force estimated for the shear failure (F2 = 274.13 kN, Table 12) was very close to the value achieved in the test (F2 = 272.0 kN, Figure 17).

With regard to the curves shown in Figure 16 it is observed that the relationship between the forces corresponding to the flexural failure with continuity and the simple support slabs, F2/F1, is always equal to 1.6 (see Table 7). This relationship can be visually verified in Figure 16. If only the flexural failure results were considered, it could be conclude for all cases that continuity increases by 1.6 times the resistance of hollow core slabs. However this conclusion is only possible for the slabs with span equal to 6.25 m or above.

There is also a relationship between the forces corresponding to the failure by shear forces (F1,Q and F2,Q). This relationship is affected by the rate of continuity reinforcement (ρ1) adopted for each situation. However, taking into account only the results of shear forces, it is concluded that the shear strength decreases when continuity is promotes. This fact was expected given that in the simple support condition the shear force is equivalent to the half of the force F1,Q, while in the continuity condition, the support considered absorbs more load, with this ratio equal to (11/16) F2,Q. For the cases with continuity at the two supports, the curve of F1,Q is equal to that of F2,Q. This is because even with continuity the shear force is equivalent to half of the applied force.

The curve "F2,E – Continuity – Envelope" represents the envelope of the slab with continuity considering the failure by flexure or shear force.

Analyzing the two effects simultaneously (flexural or shear) it is concluded that the failure mode would be by shear force for the followings spans ℓ = 3.75 m; ℓ = 5.00 m and ℓ = 6.25 m. For the first case (ℓ = 3.75 m) there is no load resistance increase in the slabs, that is, the failure force value for the flexure tests with continuity (F2) is lower than the failure force value of the simple support tests (F1). For the last cases (ℓ = 7.50 m; ℓ = 8.75 m and ℓ = 10.00 m), the failure occurs by flexure.

When analyzing the efficiency of continuity (F2/F1, last column of Table 8), the slabs that performed better were those limited by flexural failure. Furthermore, Figure 16 shows the efficiency of the continuity condition by the distance between the curve F2,E and those below this: the curve F2,Q for the span of 3.75 m (inefficient) and the curve F1 for the other slabs.

As the focus of this study is not to analyze the cases with filling cores, this is not depicted in Figure 16. However, when this fact is taken into consideration, the tendency is that the shear force values increase. In other words, in Figure 16, the curve F2,Q would move upward, further improving the continuity efficiency (F2/F1) in the first envelope section.

The case in which the simple support condition exhibited a failure force greater than that for the continuity condition (span = 3.75 m) indicates that continuity is not favorable for this span. However, it is possible that the continuity condition is the solution implemented in the project, even with a decrease in efficiency (F2/F1), in terms of controlling displacements or vibration, for verifying serviceability limit states.

8. Acknowledgements

To CAPES – Coordination for the Improvement of Higher Education Personnel (Coordenação de Aperfeiçoamento de Pessoal de Nível Superior) – for the doctoral scholarship granted to the first author.

To Brazilian Association of Industrialized Concrete Construction (ABCIC – Associação Brasileira da Construção Industrializada de Concreto) – and the company LATTICE SLAB (LAJE TRELIÇADA) IND. and COM. LTDA. for providing the hollow core slabs units used in this work.

To the friends who collaborated with the experimental test: Thomaz Mendes Lopes Vaz, Bruna Catoia and Fernando Menezes de Almeida Filho.

9. References

Received: 14 Jul 2013

Accepted: 18 Sep 2013

Available Online: 12 Dec 2013

  • [01] PET CIVIL UFJF. Electronic publishing. Available in: <http://blogdopetcivil.com/2011/08/18/lajes-alveolares/>. Accessed on May 2011.
  • [02] SCHOKBETON INC. Quebec, Canada. Electronic publishing. Available in: <http://www.schokbeton.com/ eng/dalles.html>. Accessed on May 2011.
  • [03] PRECAST/PRESTRESSED CONCRETE INSTITUTE.PCI. Manual for the design of hollow core slabs. 2.ed. Chicago, IL, USA, 1998.
  • [04] FÉDÉRATION INTERNATIONALE DE LA PRÉCONTRAINTE (FIP). Planning and design handbook on precast building structures. London, England, 1994.
  • [05] COSTA, O. O. Avaliação de desempenho de elementos de lajes alveolares protendidas pré-fabricadas. 2009. 132p. Dissertation (Master in Civil Construction) Department of Civil Engineering, Federal University of Sao Carlos, Sao Carlos, SP, Brazil, 2009.
  • [06] RESENDE, R. S.; GASTAL, F. P. S. L. Análise numérico-experimental de lajes pré-moldadas protendidas com continuidade posterior por adição de sobrecamada de concreto armado. In: Congresso Brasileiro do Concreto, 41 IBRACON. Salvador. Sept-Oct. 1999.
  • [07] BARBIERI, R. A.; GASTAL, F. P. S. L. Análise numérico-experimental de elementos pré-moldados protendidos com continuidade posterior por adição de armadura. In: Congresso Brasileiro do Concreto, 41 IBRACON. Salvador. Set-Oct. 1999.
  • [08] TAN, K.; ZHENG, L.; PARAMASIVAM, P. Designing hollow core slabs for continuity. PCI Journal. Precast/ Prestressed Concrete Institute, Chicago, IL, USA. v.41, n.1, p.82-91, Jan-Feb. 1996.
  • [09] PETRUCELLI, N. S.; CARVALHO, R. C. O uso de continuidade em pavimentos com lajes alveolares protendidas. In: Congresso Brasileiro do Concreto, 52 IBRACON. Fortaleza. Oct. 2010.
  • [10] PETRUCELLI, N. S. Considerações sobre projeto e fabricação de lajes alveolares protendidas. 2009. 103p. Dissertation (Master in Civil Construction) Department of Civil Engineering, Federal University of Sao Carlos, Sao Carlos, SP, Brazil, 2009.
  • [11] CATOIA, B. Lajes alveolares protendidas: cisalhamento em região fissurada por flexão. 2011. Thesis (Doctoral in Structural Engineering) Scholl of Engineering of Sao Carlos, University of Sao Paulo, Sao Carlos, 2011.
  • [12] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6118: Projeto de estruturas de concreto.Rio de Janeiro, 2003.
  • [13] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 14861: Laje pré-fabricada – painel alveolar de concreto protendido – Requisitos e procedimentos. Rio de Janeiro, 2011.