The influence of grouting and reinforcement ratio in the concrete block masonry compressive behavior

Abstracts

This paper presents an experimental investigation on the compressive strength and stress-strain curves of concrete block masonry with varying block and grout strengths and reinforcement ratio. The three-block prisms, built with 8.5 and 15.0 MPa blocks, were tested hollow and filled with 17.0 and 30.0 MPa compressive strength grouts. In addition, prisms and walls with reinforcement rates of 0.15%, 0.40% and 1.0 % were also tested. With the results, it was possible to measure the compressive strength and stress-strain behavior of masonry with inclusion of different grout and reinforcement components, giving parameters for better evaluation of their performance and design. Among the conclusions, it was observed that increasing the compressive strength of masonry is not proportional to the increase of the grouting area and the efficiency of reinforcement to increase compressive strength is low. Stress-strain curves for the several materials combinations are made available.

concrete blocks; reinforcement; masonry; compressive strength; stress-strain curve


Este trabalho apresenta uma investigação experimental do comportamento estrutural, resistência à compressão axial e deformabilidade, da alvenaria de bloco de concreto em função da variação da resistência dos blocos e graute e da taxa de armadura. Os prismas de três fiadas de altura, construídos com blocos de 8,5 e 15,0 MPa, foram ensaiados ocos e preenchidos com grautes de 17,0 e 30,0 MPa. Além destes, também foram ensaiados prismas e paredes armadas com taxas de 0,15%, 0,40% e 1,0%. Com os resultados foi possível mensurar a variação da resistência e os diagramas tensão-deformação da alvenaria com a inserção destes componentes (graute e armadura), fornecendo parâmetros para melhor avaliação de seu desempenho para projeto. Entre as conclusões, pode-se afirmar que o aumento da resistência à compressão das alvenarias não é proporcional ao aumento de área pelo grauteamento e que é baixa a eficiência da presença de armaduras para aumento da resistência a compressão. São disponibilizados os diagramas tensão-deformação para as várias combinações de materiais.

blocos de concreto; armadura; alvenaria estrutural; resistência a compressão; curva tensão-deformação


1. Introduction

Everyday, the construction of high structural masonry buildings, with greater spans and higher load, becomes more frequent. Masonry elements are then subject to high load with high load resistance demand in walls and columns.

However, many important issues in the masonry research remains unanswered. The theoretical analysis of the masonry structural system yields a large number of variables, given that it is a system with plates and shells composed of non-homogeneous materials and nonlinear behavior [1CAMACHO, J. S.; RAMALHO, M. A.; ANDOLFATO, R. P. An experimental study of the interaction among walls submitted to vertical loads. In: Australian Masonry Conference - AMC, 6th, Adelaide, 2001, Proceedings of the 6th Australian Masonry Conference, Adelaide, 2001, v. 1, p. 95-104.].

In reinforced masonry, the interference between different materials are even greater. The insertion of grout and rebar increases the number of variables uncertain. At a certain point, the unknowns on the masonry structural behavior cause some insecurity and inhibit its use.

The compatibility of all components involved in the production of masonry (block, mortar, grout and rebar) is paramount and essential to maximize and optimize their performance, taking advantage of all the system's potential. This compatibility is only possible with knowledge of the material characteristics and the physical and mechanical phenomena developed in the masonry under service and ultimate loadings [2MENDES, R. J. K. Resistência à compressão da alvenaria de blocos cerâmicos estruturais, Florianópolis, 1998, Dissertação (Mestrado) - Universidade Federal de Santa Catarina, 200 p.].

Several reports of experimental tests on concrete and ceramic blocks ([3DRYSDALE, R. G..; HAMID, A. A.. Behaviour of concrete block masonry under axial compression. ACI Journal, v. 76, n. 6, 1979, p. 707-721.], [4CHAHINE, G. N. Behaviour Characteristic of Face Shell Mortared Block Masonry Under Axial Compression, Hamilton (Ontario), 1989, Master of Engineering thesis - McMaster University, 423 p.], [5HAMID, A. A..; CHUKWUNENYE, A.. The Compression Behaviour of Concrete Masonry Prisms. Journal of the Structural Division, Proceedings of ASCE, v. 112, n. 3, 1986, p. 605-614.]) indicate that it is not valid to simply add a grouted area to the hollow ungrouted section to determine the prism strength. According to [6PARSEKIAN, G. A..; HAMID, A. A..; DRYSDALE, R. G.. Comportamento e Dimensionamento de Alvenaria Estrutural, São Carlos: EdUFSCar, 2ed, 2013, 625 p.] incomplete consolidation of the grout, plastic and drying shrinkage, incompatibility between block and grout deformation and geometric factors may explain this effect.

Regarding the reinforcement ratio, the 1989 version of the Brazilian standard for structural concrete blocks masonry design [7ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Cálculo de alvenaria estrutural de blocos vazados de concreto. - NBR 10837, Rio de Janeiro, 1889.], allowed a small increase in the masonry compressive strength with the rebar presence. However, the allowable compression stress in the rebar was limited to 62 MPa. In practice this specification resulted in very small efficiency of including rebar to increased compressive strength. The 2011 version of the same standard [8ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Alvenaria estrutural - Blocos de concreto - Parte 1: Projeto. - NBR 15961-1, Rio de Janeiro, 2011.] eliminates the possibility of using rebar to increased compression resistance. The main cause of this low efficiency in walls under compression load is the lack of providing stirrups to tie laterally the longitudinal rebar [6PARSEKIAN, G. A..; HAMID, A. A..; DRYSDALE, R. G.. Comportamento e Dimensionamento de Alvenaria Estrutural, São Carlos: EdUFSCar, 2ed, 2013, 625 p.]. The use of stirrups in walls is not the common practice.

On the masonry stress-strain curves, Eurocode [9EN 1996-1-1: EUROCODE 6: Design of Masonry Structures - Part 1-1: General rules for buildings - Rules for reinforced and unreinforced masonry, Brussels, 2013.] indicates the curve on Figure 1, with an masonry failure strain equal to 0.0035 blocks for Group 1 and 0.002 for Group 2 and 3, wherein the Group blocks 1 are the maximum void volume of 25% (perforated masonry) and Group 2 blocks between 25% and 50% (includes hollow blocks). Other standards admit the following values:

Figure 1.
Design masonry stress-strain curve as Eurocode [9EN 1996-1-1: EUROCODE 6: Design of Masonry Structures - Part 1-1: General rules for buildings - Rules for reinforced and unreinforced masonry, Brussels, 2013.]

  • BS 5628-part 2 - 1995 [10] = 0.0035 (all masonry types).

  • MSJC (2011) [11] = 0.0035 (clay masonry) ou 0.0025 (concrete masonry).

  • S304. 1-04 [12] = 0.0030 (all masonry types).

  • AS 3700-1998 [13] = 0.0035 (all masonry types).

Tests reported in [1414 PRIESTLEY, M. J. N. Seismic Design of Concrete Masonry Shear Walls. Journal of the American Concrete Institute, v. 83, 1986, p. 58-68.] indicates the stress-strain diagram of Figure 2, with failure strain equal to 0.002 for concrete blocks.

Figure 2.
Masonry stress-strain curve as [1414 PRIESTLEY, M. J. N. Seismic Design of Concrete Masonry Shear Walls. Journal of the American Concrete Institute, v. 83, 1986, p. 58-68.]

According to [6PARSEKIAN, G. A..; HAMID, A. A..; DRYSDALE, R. G.. Comportamento e Dimensionamento de Alvenaria Estrutural, São Carlos: EdUFSCar, 2ed, 2013, 625 p.] "from the observation that the maximum failure strain varies between 0.0020 and 0.0035 for prisms with concrete and ceramic blocks, the adoption of an average value of 0.0030 for the national standards would be appropriate, as specified in the Canadian code".

The main objective of this paper is to present a study on the behavior of concrete hollow block masonry with variable grout and rebar use. Parameters are measured to assess the increase of structural masonry resistance in the presence of grout and rebar, as well as the behavior of materials at rupture, providing information to aid in the understanding of this composite material behavior and to better calibrate design models in the ultimate limit state .

1.1 Justificative

Masonry buildings in are built in Brazil in heights and boldness conceptions not usually seen in other parts of the world. The increase in masonry elements strength capacity demand, in particular compression strength, is noticeable. Recently, an effort was made to update the Brazilian codes regarding concrete blocks masonry design, with elements now designed within the ultimate limit state criteria. Thus, experimental studies that contribute to the better understanding of elements composed by different combinations of blocks, mortar, grout and rebar are fully justified.

2. Materials and experimental program

2.1 Concrete blocks

The concrete blocks have dimensions of 14 cm x 19 cm x 29 cm, regular block, and 14 cm x 19 cm x 14 cm, half block (width x height x length) with two block strength tested, designated B1 and B2. The test results indicated compression strengths of 8.64 (B1) and 15.76 (B2) MPa with their net areas shown in Table 1.

Table 1.
Results of blocks characterization testing

Tests were performed according to NBR 12118 [1515 ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Blocos vazados de concreto simples para alvenaria - Métodos de ensaio. - NBR 12118. Rio de Janeiro, 2013.]. The blocks were capped with gypsum plaster in the proportions 1: 0.6 (plaster : water). Dial gauges, electrical strain gauge and load cells were used to measure the stress-strain diagram. Figure 3illustrates the test scheme and Table 1 shows the results.

Figure 3.
Scheme of the blocks testing

2.2 Prisms

The prisms were built with three blocks and pre-mixed mortar with mix proportions in volume of 1: 0.5: 4.5 (cement: lime: sand), with a/c ratio equal to 1.27, and following the procedures described by NBR 15961- 2 [1616 ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Alvenaria estrutural - Blocos de concreto - Parte 2: Execução e controle de obras. - NBR 15961-2. Rio de Janeiro, 2011.] for the two classes of blocks.

Two grout strengths of 17 and 30 MPa were tested, with slumps of 200 ± 30 mm, named G1 and G2, respectively, which were combined with each block strength. Thus, the grout and block combination in prism testing are B1-G1 and B1-G2, B2-G1 and B2-G2, and also hollow prisms for each class of blocks B1 and B2.

Three reinforcement ratios were tested, r1, r2 e r3, combined with grouted prisms cited above. The rebar sizes and grouts mix proportions are shown in Table 2. Prism capping are the same as the blocks.

Table 2.
Mortar, grout and rebar characteristics

The axial compression resistance tests were also performed using dial gauges, electrical strain gauges and load cells. Table 3 summarize results and Figure 4presents the prisms test scheme.

Table 3.
Results for mortar, grout and hollow, unreinforced and reinforced grouted prism testing

Figure 4.
Scheme of the prisms testing

2.3 Walls

Small walls with dimensions of 100 cm x 90 cm (height x length, three blocks long and five courses high), were assembled and tested using the two classes of blocks. Walls were built with the two block strengths.

The mortar, grout and rebar used were the same adopted in the prisms, with the difference that in the walls only one type of grout was used, G1, as this grout showed higher efficiency in the prism testing. The walls building procedures followed NBR 8949 [1717 ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Paredes de alvenaria estrutural - Ensaio à compressão simples - Método de ensaio. - NBR 8949, Rio de Janeiro, 1985.]. Instrumentation and gypsum capping were similar to the prism testing.

Table 4 summarize the results and Figure 5 show the test assembling.

Table 4.
Results hollow, unreinforced and reinforced grouted wall testing

Figure 5.
Walls testing scheme

3. Results and discussion

3.1 Prisms

Table 4 presents the prism strength results of all combinations, which shows a significant increase in the grouted prisms strength when compared to the hollow prisms results (compared to gross area). However, increasing the grout strength accounted for minor variations in prism strength, a fact confirmed by other authors such as [1818 ROMAGNA, R. H. Resistência à compressão de prismas de blocos de concreto grauteados e não grauteados, Florianópolis, 2000, Dissertação (Mestrado) - Universidade Federal de Santa Catarina, 218 p.], [1919 CUNHA, E. H. Analise experimental do comportamento de prismas grauteados em alvenaria estrutural, Goiânia, 2001, Dissertação (Mestrado) - Universidade Federal de Goiás, 149 p.], [2020 CAMACHO, J. S..; RODRIGUES, R.. O. Utilização do graute na alvenaria estrutural. In: do 41º Congresso Brasileiro de Concreto, 41º, Salvador, 1999, Anais, Salvador, 1999, p. 142.], [2121 CALÇADA, L. M. L. Avaliação do comportamento de prismas grauteados e não grauteados de bloco de concreto, Florianópolis, 1998, Dissertação (Mestrado) - Universidade Federal de Santa Catarina, 188 p.].

Looking at reinforced prisms results, significant variations in the masonry resistance with increasing steel area are not observed.

Table 3 shows the results of the prisms in the net area of unreinforced but grouted prisms of the two block strengths. It is observed that, considering the resistance in the net area, hollow prism B1 resistance substantially matched with the grouted prism, while the hollow prism B2 resistance was increased about 50% after grouting. This can be explained by the thicker block-wall thickness of B2 resulting in a lower area of grout. The B2 thicker block walls are more resistant to inner transverse expansion of the grout, which will also deform less because of its smaller area.

Comparing the results of the prisms with the same blocks and grout type and varying only the reinforcement ratios (Table 3), there is an average increase observed for prism with block B1 when compared to B2. However, comparing different reinforcement ratios for the same block and grout type did not show an increased proportional to the reinforcement ratio and only a very small resistance increase to the unreinforced prism is noted.

Strain-strain curves of the hollow and grouted unreinforced and reinforced prisms are plotted in Figures 6 to 11, with stressed calculated in the gross and net area. Figure 6shows the B1-prisms curves, in which one verifies that grouted prisms G1 and G2 show a close behavior with each other and with hollow prisms with respect to its net areas.

Figure 6.
Stress-strain curve - hollow and grouted prisms B1

Figure 7 shows the B2-prisms curves. Grouted prisms G1 and G2 show initial deformation similar to the ungrouted prism. The failure strain is also similar although at higher stresses.

Figure 7.
Stress-strain curve - hollow and grouted prisms B2

Figures 8 to 11 show the reinforced prisms curves including the four combinations of block and grout. The curves are similar regardless the reinforcement ratios.

Figure 8.
Stress-strain curve - reinforced prisms B1-G1

Figure 9.
Stress-strain curve - reinforced prisms B1-G2

Figure 10.
Stress-strain curve - reinforced prisms B2-G1

Figure 11.
Stress-strain curve - reinforced prisms B2-G2

3.2 Walls

Table 4 shows the mean strength of the hollow ungrouted and the unreinforced and reinforced grouted walls. armed and grouted. The hollow and the unreinforced grouted wall with B1 blocks resulted in similar net area strength. For the B2 walls, there is an increase of 30% in the unreinforced grouted wall strength at net area.

Several authors, e.g. [2222 ALY, V. L. C..; SABBATINI, F. H.. Determinação de correlações de resistências mecânicas de paredes de alvenaria estrutural de blocos de concreto. In: International Seminar on Structural Masonry of Developing Countries, 5th, Florianopolis, 1994, p 115-126.], concluded that the percentage increase in compressive strength of grouted walls in relation to hollow ungrouted walls is inversely proportional to the increased block resistance. It should be noted here that the geometry of blocks (thickness of the block wall) are different on blocks B1 and B2, so direct comparison is not suitable. What can be comment is that thicker block-walls provided greater increase in resistance when fully grouted, possibly because failure occurs by lateral expansion of the blocks due to the lateral deformation of the stiffer inner grout and thicker walls have better resistance to the lateral expansion.

The variation of reinforcement ratios (r1, r2 e r3) on B1-walls did not lead to variation in the resistance of the walls, with an increase of about 18% observed for all reinforcement ratios when compared to the unreinforced walls. In examining the wall failure strain, one can see that there is not enough deformation to yield the steel. For example, with the rebar area of 1.89 cm² area (area relative to r1), steel elastic modulus equal to 21 GPa and the wall of the breaking strain of 1.0 ‰, one obtains a rebar force equal to 39.7 kN very small value (about 2.6%) compared with the wall failure load in the order of 1500 kN. Thus, the observed increase in reinforced B1 walls is related to the change in the failure mode (which occurs by lateral expansion of the block due to the expansion of the inner grout) than the rebar contribution on carrying part of the failure load.

In the reinforced B2-walls, results do show a strength variation with the reinforcement ratio variation. However, for small diameter bars (6.3 mm, r1), wall strength was smaller than in the unreinforced grouted walls, with similar values for 10 mm rebar (r2). An increase of 14% was observed only with 16 mm rebar (r3). Since these reabar are not laterally restrained by stirrups, it is suggested the small diameter bars, subjected to greater stresses than in the case of B1, contributing negatively possibly because of their buckling.

Results indicate that reinforcing grouted walls with longitudinal rebars, without providing stirrups, will not contribute to increasing its compression load capacity proportionally to the reinforcement rate. Eventually, depending on the rebar diameter, the wall strength can be reduced. Results reported in [2222 ALY, V. L. C..; SABBATINI, F. H.. Determinação de correlações de resistências mecânicas de paredes de alvenaria estrutural de blocos de concreto. In: International Seminar on Structural Masonry of Developing Countries, 5th, Florianopolis, 1994, p 115-126.] also indicate small changes in resistance of reinforced concrete block walls compared to their respective grouted walls.

To analyze the behavior of the stress-strain curves of combinations of hollow ungrouted and unreinforced and reinforced, graphs are presented in Figures 12 to 15. Referring to Figure 12, one can see the same deformation behavior of B1 hollow and grouted walls in respect to the net area. This behavior was also observed in the prism testing in which both rebar, and block gages showed similar reading.

Figure 12.
Stress-strain curve - hollow and unreinforced walls B1-G1

Figure 13.
Stress-strain curve - hollow and unreinforced walls B2-G1

Figure 14.
Stress-strain curve -reinforced walls B1-G1

Figure 15.
Stress-strain curve -reinforced walls B2-G1

Figure 13 shows hollow and unreinforced grouted B2 walls. Grouting these walls increased its stiffness and ultimate strength in net area compared with the hollow walls. This behavior was also observed with at prisms testing.

Figures 14 and 15 show the curves of the reinforced B1 and B2 walls. A very similar masonry deformation behavior is observed at the three reinforcement rates, considering both the gage readings at the block and at the rebar. This behavior is also similar to the prism testing.

4. Conclusion

Based on the observations reported here, we can conclude:

  • The grouted and hollow B1 prism testing results show the same strength in the net area, but a 50% increased in the grouted to hollow prism strength was observed with B2 blocks. Similar behavior was observed on the walls, with lower increase (30%) for the B2 case. This behavior suggest that the greater wall thickness of the B2 blocks showed greater resistance to lateral expansion of the inner grout, leading to the greater prism strength.

  • The prism filled with the stiffer grout resulted in smaller failure strain than the one with weaker grout, although the failure strength was similar for the two grout-strengths tested.

  • The insertion of grout on the walls increased by 80% the wall average load-capacity when compared with the hollow walls. Increased masonry resistance with the grouting is not necessarily proportional to ungrouted/grouted net area ratio.

  • The presence of reinforcement did not alter significantly the structural behavior of the prisms and walls (compressive strength and deformability), being eventually observed a small resistance reduction (6.3 mm rebars and B2 blocks), little or no increase in compression resistance (other cases). It is not possible to calculate the reinforced wall resistance by accounting the compatibility of strain and stresses at the block, grout and rebar areas. The lateral expansion of the grout and rebar (without stirrups in this study) affect the wall behavior and resistance.

  • The elongation at break of masonry concrete block is close to 2.0 ‰, a smaller value than the currently adopted in Brazilian standards, specified as 3.5 ‰, but similar to that reported in other references.

5. References

  • 1
    CAMACHO, J. S.; RAMALHO, M. A.; ANDOLFATO, R. P. An experimental study of the interaction among walls submitted to vertical loads. In: Australian Masonry Conference - AMC, 6th, Adelaide, 2001, Proceedings of the 6th Australian Masonry Conference, Adelaide, 2001, v. 1, p. 95-104.
  • 2
    MENDES, R. J. K. Resistência à compressão da alvenaria de blocos cerâmicos estruturais, Florianópolis, 1998, Dissertação (Mestrado) - Universidade Federal de Santa Catarina, 200 p.
  • 3
    DRYSDALE, R. G..; HAMID, A. A.. Behaviour of concrete block masonry under axial compression. ACI Journal, v. 76, n. 6, 1979, p. 707-721.
  • 4
    CHAHINE, G. N. Behaviour Characteristic of Face Shell Mortared Block Masonry Under Axial Compression, Hamilton (Ontario), 1989, Master of Engineering thesis - McMaster University, 423 p.
  • 5
    HAMID, A. A..; CHUKWUNENYE, A.. The Compression Behaviour of Concrete Masonry Prisms. Journal of the Structural Division, Proceedings of ASCE, v. 112, n. 3, 1986, p. 605-614.
  • 6
    PARSEKIAN, G. A..; HAMID, A. A..; DRYSDALE, R. G.. Comportamento e Dimensionamento de Alvenaria Estrutural, São Carlos: EdUFSCar, 2ed, 2013, 625 p.
  • 7
    ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Cálculo de alvenaria estrutural de blocos vazados de concreto. - NBR 10837, Rio de Janeiro, 1889.
  • 8
    ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Alvenaria estrutural - Blocos de concreto - Parte 1: Projeto. - NBR 15961-1, Rio de Janeiro, 2011.
  • 9
    EN 1996-1-1: EUROCODE 6: Design of Masonry Structures - Part 1-1: General rules for buildings - Rules for reinforced and unreinforced masonry, Brussels, 2013.
  • 10
    BRITISH STANDARD INSTITUTION. Code of practice for structural use of masonry. Part 2 - Structural use of reinforced and prestressed masonry. - BS 5628-2, London, 1995.
  • 11
    MASONRY STANDARDS JOINT COMMITTEE. Building code requirements for masonry structures (ACI 530/TMS 402/ASCE 5), 2011.
  • 12
    CANADIAN STANDARDS ASSOCIATION. Design of masonry structures. - CSA S304. 1-04, Toronto, 2004.
  • 13
    STANDARDS ASSOCIATION OF AUSTRALIA. Masonry Structures. - AS 3700, 2ed, Sydney, 1998.
  • 14
    PRIESTLEY, M. J. N. Seismic Design of Concrete Masonry Shear Walls. Journal of the American Concrete Institute, v. 83, 1986, p. 58-68.
  • 15
    ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Blocos vazados de concreto simples para alvenaria - Métodos de ensaio. - NBR 12118. Rio de Janeiro, 2013.
  • 16
    ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Alvenaria estrutural - Blocos de concreto - Parte 2: Execução e controle de obras. - NBR 15961-2. Rio de Janeiro, 2011.
  • 17
    ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. Paredes de alvenaria estrutural - Ensaio à compressão simples - Método de ensaio. - NBR 8949, Rio de Janeiro, 1985.
  • 18
    ROMAGNA, R. H. Resistência à compressão de prismas de blocos de concreto grauteados e não grauteados, Florianópolis, 2000, Dissertação (Mestrado) - Universidade Federal de Santa Catarina, 218 p.
  • 19
    CUNHA, E. H. Analise experimental do comportamento de prismas grauteados em alvenaria estrutural, Goiânia, 2001, Dissertação (Mestrado) - Universidade Federal de Goiás, 149 p.
  • 20
    CAMACHO, J. S..; RODRIGUES, R.. O. Utilização do graute na alvenaria estrutural. In: do 41º Congresso Brasileiro de Concreto, 41º, Salvador, 1999, Anais, Salvador, 1999, p. 142.
  • 21
    CALÇADA, L. M. L. Avaliação do comportamento de prismas grauteados e não grauteados de bloco de concreto, Florianópolis, 1998, Dissertação (Mestrado) - Universidade Federal de Santa Catarina, 188 p.
  • 22
    ALY, V. L. C..; SABBATINI, F. H.. Determinação de correlações de resistências mecânicas de paredes de alvenaria estrutural de blocos de concreto. In: International Seminar on Structural Masonry of Developing Countries, 5th, Florianopolis, 1994, p 115-126.
  • 23
    LOGULLO, B., G. Influência do graute e da taxa de armadura no comportamento da alvenaria de blocos de concreto, Ilha Solteira, 2006, Dissertação (Mestrado) - Faculdade de Engenharia de Ilha Solteira, Universidade Estadual Paulista, 192 p.