The influence of connecting pile cap-column in the mechanisms of break in the two pile caps

Abstract

The paper analyzes the two pile caps with partially embedded socket and subject a center load. Three models were experimentally tested, varying the type of conformation of the column and walls of the socket, with a smooth, the other rough, and a monolithic two pile cap, used for reference. The roughening of the column-socket interface was examined with the aim of verifying the difference of the distribution of compressive and tensile stresses in the strut an tie model used for design. The experimental test to show that the two pile caps with conformation rough of the column and walls of the socket, support more load in comparison with two pile caps with smooth of the column and walls of the socket. Both however underperformed the monolithic two pile cap, with values of 66% and 36% respectively.

Keywords :
two pile caps; reinforced concrete; foundations

Resumo

O trabalho analisa o comportamento de blocos sobre duas estacas com cálice parcialmente embutido, submetidos à ação de força centrada. Foram ensaiados experimentalmente três modelos, variando-se o tipo de conformação das paredes dos pilares e do cálice, sendo uma lisa, outra rugosa e um bloco monolítico, utilizado para referência. A rugosidade na interface pilar-cálice foi analisada, com o intuito de verificar a diferença das distribuições dos fluxos de tensões de compressão e tração no modelo de biela e tirante empregado no dimensionamento e, consequentemente, o comportamento estrutural. As análises experimentais constataram que o modelo com conformação rugosa das paredes do cálice e do pilar apresentou capacidade resistente superior ao modelo com conformação lisa. Ambos, porém tiveram desempenho inferior ao bloco monolítico, com valores de 66% e 36% respectivamente.

Palavras-chave:
blocos sobre duas estacas; concreto armado; fundações

1. Introduction

1.1 Initial considerations

The foundations are element to connections the superstructures and the soil and it is responsible in to transfer the actions in the structures. The foundations are separates in two groups: the superficial foundations and deep foundations. The distinction between types are done about criteria the transmission the forces. In deep foundations the rupture not reaches the superficial layer of the soil. Usually, the rupture mechanism shown in the NBR 6122:2010 [11 [1] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6122:2010 - Projeto e execução de fundações. Rio de Janeiro, 2014.], reaches twice the small dimension of the foundations, so, the deep foundations are that in the your base of the foundation, are built with depth superior the three times the small dimension or superior the three meters.

The choice of the foundation for each building depends on several factors, such as construction technology available in the building area, economic conditions, geotechnical characteristics, intensity of actions, neighboring buildings, among others. With these factors and combinations of them, the engineer determines which type of foundation suitable for every situation.

Through studies on the choice of the type of foundation to be used in a particular construction, when the foundation is with piles, the construction of another structural element it is necessary: the pile caps. These pile caps are volume structures that have the function of solidarity heads of the piles and transfer the actions of the column to the piles.

Despite the importance of the pile cap, it does not allowed visual inspection when in service. Therefore, it is important to know their behavior. The models of design to this type of element are the strut and tie models and three-dimensional models.

The plan dimensions of the pile caps depend on the position of the piles, by adopting, in general, the smallest possible spacing between them to avoid the need to use suspension reinforced. This spacing is assumed equal to 2.5 times its diameter in the case of precast piles and 3.0 times the diameter if the piles are molded in place. When stabs the minimum distances between the piles, it avoids the group effect on the pile caps. It still must be a minimum distance between the faces of the pile and the end of the pile cap, in order to improve the conditions of the anchor of tie reinforced, as MUNHOZ [22 [2] MUNHOZ, F.S. (2004). Análise do comportamento de blocos de concreto armado sobre estacas submetidos à ação de força centrada. Dissertação (mestrado) - Escola de Engenharia de São Carlos, Universidade de São Paulo, São Carlos.].

The structural behavior and design depend on the rigidity of the pile cap, using the same criteria superficial foundation, according to ABNT NBR 6118: 2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.]. In the case of rigid pile caps can be adopted for the design and details of the pile caps, linear three dimensional structural models or nonlinear and strut and tie models, these being preferred latter for defining with better efficiency distribution of forces within the pile cap. The NBR 6118: 2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.] does not bring in your text recommendations for verification and design of this element only suggests that the criteria to be used and recommendations of the stress values in inferior (near the pile) and superior node (near the column). However, there are no recommendations determining the geometric shape of the strut.

Using model strut and tie, it is considered that the formation of discrete regions (known as D regions) that are the regions where the stress distribution is not linear and that are not valid hypotheses Bernoulli (known as regions B, where there linear change in tension acting on the cross section). In this model, the checks of the compression stress of the strut are from the model Blévot & Frémy [44 [4] BLÉVOT, J.; FRÉMY, R. (1967). Semelles sur piex. Analles d'Institut Techique du Bâtiment et des Travaux Publics, Paris, v. 20, n. 230.]. The stresses in the nodes zone, are suggested by NBR 6118: 2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.] and have lower values the stresses limits suggested by Blévot & Frémy [44 [4] BLÉVOT, J.; FRÉMY, R. (1967). Semelles sur piex. Analles d'Institut Techique du Bâtiment et des Travaux Publics, Paris, v. 20, n. 230.], considering the deleterious effect of tensile stresses in the node zone with traction. However, near the nodal zones without traction, that is, node with stress compression only, the NBR 6118:2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.] does not consider the effect of concrete triaxial compressive stress, reducing the value in the node zone equal to 0,58nfcd (or 0,27nαv n fcd ) in function of the Rüsch effect, in the effect of increased concrete strength with the time, in the factor form and in the difference between the test of specimens and the behavior of the structure. The Model Code CEB-FIP [55 [5] COMITE EURO-INTERNACIONAL DU BÉTON (1990). CEB-FIP Model code for concrete structures. Bulletin D'Information, Paris, n. 203-205, July.] suggests geometries for the nodes of nodal regions, being possible to verify the stress in theses nodes.

The strut and tie model can be used considering in the flow of the stress in structure, using the minimal path forces, suggested by Schlaich et al. [66 [6] SCHLAICH, J.; SCHAFER, K.; JENNEWEIN, M. (1987). Toward a consistente design of reinforced structural concrete. Journal of Prestressed Concrete Institute, v. 32, n. 3, May-June;]. These stresses can be obtained through linear or no-linear analysis, using numeric methods, for example, the Finite Element Method.

The used the precast structures, it is necessary, after the construction of the pile and the pile caps, the setting of the column. After that, is necessary to ensure the fix of the column with the foundation. Then used a connecting element (The link between the pillar and the pile cap may occur through the base plate, by amendment of reinforcing steel bars with grout and hem, by amendment of protruding reinforcement bars and socket, which will be studied in this work), whose main objective structural transfer of efforts between the pillar and pile cap, and allow the structural interaction between them. These connections are discontinuous regions where stress concentrations occur and form a fine point with respect to the dimensioning and assembly of precast concrete structures, because they have great influence on the structural behavior of the same.

The union of the superstructure through socket, in the pile cap is accomplished by embedding a part of column (embedded length) in an opening of the foundation element that enables its holder. Usually the socket is built on the block, but is also used pile caps with embedded or partially embedded socket.

1.2 Objetivos

The objective of this study is to analyze and discuss the structural behavior of the connection column-pile cap through of type socket in two pile caps, using experimental tests.

2. Experimental program, materials and methods

2.1 Geometric properties of te models

To this work, were buildings three models of the pile caps, one monolithic (column and pile caps concreted together - figure [1]), with reference models and two pile caps for precast column. One model for precast column has a socket-column interface with a rough surface (Figure [2]) and the other has socket-column interface with a smooth surface (Figure [3]).

Figure 1
Geometric properties of the monolith pile caps

Figure 2
Geometric properties of the rough connection pile caps of wall of the cup and the column

Figure 3
Geometric properties of the smooth connection pile caps of wall of the cup and the column

As suggested by EL DEBS [7], the wall of the cup (hc) should be the greater of 10 cm and a third of the opening of the socket socket . Thus, the adopted value was equal to 10 centimeters (Figure [4]).

Figure 4
Pile caps

The distance between the support of the piles was defined to the angle of the strut in the relation in the horizontal plane was equal α = 60,23°. This value is below the allowed limit by NBR 6118: 2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.], those angle is equal to 63,43°. Thus, the distance between the centers of the support of the pile was adopted equal to 50 cm.

It was necessary this distance depending on the space limitations for the use of testing equipment within the laboratory.

The embedded length (lemb ), defined by NBR 9062: 2006 [88 [8] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 9062:2006 - Projeto e execução de estruturas de concreto pré-moldado. Rio de Janeiro, 2007.], for precast columns with rough walls, is 40 centimeters. The roughness must be equal to 1 centimeter to 10 centimeters. However, by design criterion, it adopted the embedded length (lemb ) of 30 cm and the roughness of 5 centimeters to 10 centimeters. These values were adopted by the ease of construction of this surface in the industry or in place, using wood slats found commercially, with dimensions of 5:01 cm. Although the embedded length be less than that specified by NBR 9062: 2006 [88 [8] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 9062:2006 - Projeto e execução de estruturas de concreto pré-moldado. Rio de Janeiro, 2007.], it is according to the EN 1991 [99 [9] EN 1991-1-1. Eurocode 2: Design of concrete structures - Part 1-1: General rules and rules for buildings. European standard, 2004.], given by 1,2 hx or 1,2hy , being hx and hy defined as the dimensions of the abutment.

Another item recommended by NBR 9062: 2006 [88 [8] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 9062:2006 - Projeto e execução de estruturas de concreto pré-moldado. Rio de Janeiro, 2007.] for determining the embedded length of column, refers to the length required for bond of reinforcing steel bars abutment for transferring stress to the pile cap. This length of embedded inlay must be greater than the length of bond. In this case, it was considering the diameter of the longitudinal steel bars equal the sixteen millimeter, type CA-50, conditions of the good bond and average compressive strength equal the 48 MPa, the value this length will be 18,4 centimeters.

The ABNT 6118:2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.] indicated the favorable effect of the strut near the column (describe in the item 9.4.2.5 and 22.7.4.14), in function the concentration of the stress compression in this region, may be applied the redactor coefficient to length bond, that by Fusco [10] is equal the 0,60, what resulted the eleven centimeters.

2.2 Concrete

The construction of the pile caps was made with Self-compacting concrete. This concrete it was produced in the CMEC Structures Laboratory (Master course in Civil Engineering - UFG). The used this concrete justified by researches realized by CMEC about Self-compacting concrete. The materials to construction were donated by Redmix Concrete Brazil Inc. The characterization of materials and the study of concrete mix design they were made by Carlos Campos Laboratory Consulting and Design Ltd.

The mix of concrete used in the construction of the pile caps it was equal a 1:2,05:1.36;1.14;0,76:0,67 (cement, natural sand, artificial sand, rock 0, rock 1 and water-cement ratio - a/c). To achieve the required fluidity and cohesion were also used 0.6% of polyfunctional additive, the superplasticizer 0,4% and 6% active silica, both in relation to the Cement consumption.

The mechanics properties of concrete were obtained by test cylindrical specimens compressive, tensile strength by diametrical compression and elasticity module.

The average compressive strength and tensile concrete used in the molding pile caps, at 28 days, had values equal to 44,5 MPa and 4,04 MPa respectively. The elasticity module to 31,2 GPa.

For the column was used grout industrial type Bautech brand with average compressive strength and superior traction of the pile caps with values equal to 48,0 MPa and 4,2 MPa. The measured elasticity module was equal to 22,0 GPa.

The structural elements were built separately: first the pile caps, after the column, with your respective concretes.

After concrete curing and remove of the modes, the precast columns were placed in your respective pile caps and after to put grout in the socket.

2.3 Reinforcement

The steel bars used for reinforcement of the assembly were the Gerdau brand, donated by Prémoldaço Industry Precast Ltd. and assembled in the laboratory of CMEC structures (Master course in Civil Engineering - UFG).

The pile caps were detailing with four steel bars of 16 millimeters and steel CA-50 to tie reinforcement; the horizontals and verticals stirrups with diameters equal to 6,3 millimeters, with spacing between them equal to 10 centimeters. The Figure [5] to show the reinforcement used in monolithic pile cap and the Figure [6] the reinforcement of the precast models.

Figure 5
Schematic arrangement of the monolith pile caps

Figure 6
Schematic arrangement of the rough connection and smooth connection pile caps of wall of the cup and the column

The average yield stress (fyk) of the steel bars with 16 millimeters were equal a 559 MPa and yield strain (εy) was equal the 3,46 ‰. To steel bars with 6,3 millimeters, the value of the yield strain was equal the 2,77 ‰ and the yield stress equal the 523 MPa.

2.4 Molds

The molds to construction of the pile caps and columns were made with wooden plate plasticized plywood with thick of the 18 mm, in the CMEC Structures Laboratory.

For the construction of the rough surface in the model with roughening of the socket and column, were put pieces of the Styrofoam with a thickness of 1,0 centimeters. Also were placed piece of the Styrofoam in the interface pile/pile cap, for subsequent fitting of plate metal. These plates metals, which were supported on rollers, were thickness of 20,o millimeters.

2.5 Instrumentation

The deformations of the tie, the stirrups were analyzed by strain-gages of 5 millimeters of the base, trade maker Sensors Excel Ltd.

The displacement horizontal and vertical of pile caps were obtained by five dial gages.

The Figure [7] to show the positions were installed the strain-gages and the dial gages.

Figure 7
Position of electrical-resistance strain gages and dial indicators in the pile caps

2.6 Experimental analysis

The experimental tests were realized in Materials and Structures Laboratory of Goias University, using hydraulic machine, with capacitated of 3.000 kN and length piston equal to 1 meter. The loads were obtained by analogic dial of machine.

To simulate the pile of pile caps, were used two sets of metal plates, supported on rollers of metal. These sets served as support equipment for restricting the vertical displacement and allowing horizontal displacement.

The intention of rollers was simulate the rotation of piles in soil, after the loading of pile cap, by vertical and horizontal forces and bending, according with model to design.

The load was applied in the top of column, in steps of loads, divided every each 10 kN.

The Figure [9] shows the set of test.

Figure 8
Detail of the sets of sheet metal supported on metal rollers to simulate the column

Figure 9
Tests of two pile caps

3. Results and discussions

The monolithic specimens, to reference, showed greater load capacity, when comparted with the precast pile caps. The model precast pile cap, with the rough shaping of the walls of the socket and the column showed better performance than the model with the smooth conformation, but still below the monolithic model.

The rupture load of the monolithic pile caps was equal to 2150 kN (Figure[10]), while the pile cap with roughened walls and column, was load equal to 1420 kN (Figure [11]), a corresponding performance at 66 % compared to the monolithic model. But the pile caps with smooth conformation of the walls of the socket and the column, supported a load equal to 780 kN (Figure [12]), obtaining performance of the 36 % when compared to monolithic model.

Figure 10
Deformations in tie reinforcement bars strain - monolith pile caps: force of first crack and last force

Figure 11
Deformations in tie reinforcement bars strain - rough connection pile caps: force of first crack and last force

Figure 12
Deformations in tie reinforcement bars strain - smooth connection pile caps: force of first crack and last force

Similarly the pile cap model with smooth conformation of the walls of the socket and the column, showed performance 55%, when compared with rough pile cap.

The models of monolithic pile cap and precast pile caps with roughened walls, had collapsed by traction of strut, followed by concrete crushing. It was verified that the occurred yield of the steel bars. The precast pile caps with smooth walls, to show rupture fragile, by punching shear in the background pile cap, near the piles (Figure [ 13]). This fact is explained by deficiency of bond between walls socket and column, what result that the load in the column was to the background of pile cap and not making the struts.

Figure 13
Curve load vs. Displacement

In the Table [1], showed the relation between the ultimate load of pile caps and a comparison was performed between the same, with reference to the monolithic pile cap.

Table 1
Load rupture of pile caps tested

The pile caps tested were design using the Blévot & Frémy Model [44 [4] BLÉVOT, J.; FRÉMY, R. (1967). Semelles sur piex. Analles d'Institut Techique du Bâtiment et des Travaux Publics, Paris, v. 20, n. 230.], considering that the struts between column and pile. The stresses in the nodal zone were verified by recommendations of the Brazilian Code - ABNT 6118:2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.].These analyzes are showed in the Table [2]. To design these stress, it not considered the increase coefficient of load and mitigation coefficients of the materials.

Table 2
Strain in the superior and inferior nodal zone

In the Table [3], it was made the relations between the values of effective stress in the limited stress. It was observed that the rupture of monolithic model occurred by diagonal traction of strut, followed of the crushing of strut and after the yield of the tie. (see Figure [10]). It was observed that the limited stress recommendations by Brazilian Code - ABNT 6118:2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.] are conservatives, because not was considered the behavior of the biaxial concrete in the superior nodal zone.

Table 3
Ratio betweem in the nodal zone

In the experimental tests of precast pile caps in this research, the Blévot & Frémy Model [44 [4] BLÉVOT, J.; FRÉMY, R. (1967). Semelles sur piex. Analles d'Institut Techique du Bâtiment et des Travaux Publics, Paris, v. 20, n. 230.] not showed adequate results. With reference to the monolithic model and stress limited established by Blévot & Frémy [44 [4] BLÉVOT, J.; FRÉMY, R. (1967). Semelles sur piex. Analles d'Institut Techique du Bâtiment et des Travaux Publics, Paris, v. 20, n. 230.], the NBR 6118: 2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.], and the rupture load for each model, it was determined the theoretical inclinations of the strut and their respective heights useful and compared with experimental results. The results are show by Table [4] and Figure [14].

Table 4
Inclination of the strut, in function of the forces

The results showed in the Table [3], indicate that the experimental values, when compared with the theoretical values are fairly representative for the monolithic and rough models, when using the recommendations of Blévot & Frémy [4]. When analyzing the values obtained when used the criteria to NBR 6118: 2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.], it was found that the pile caps should have greater rigidity to be the conditions of nodal security.

With respect to the forces on the ties, there was a significant reduction when the steel bars of the tie through the inferior nodal zone near the pile. This reduction is caused by the favorable effect of the strut, which increases the frictional force at the interface of steel bars and concretes that region. Table [5] shows these results.

Table 5
Forces on tie reinforcement bars strain

The results presented in Table [5], corroborate the results obtained by Adebar et al. [1111 [11] ADEBAR, P.; KUCHMA, D.; COLLINS, M. P. (1990). Strut-and-tie models for design of pile caps: an experimental study. ACI Journal, v. 87, p. 81-91, Jan/Feb;] Miguel [1212 [12] MIGUEL, G. M. (2000). Análise experimental e numérica de blocos sobre três estacas. Tese (doutorado) - Escola de Engenharia de São Carlos, Universidade de São Paulo, São Carlos;] & Giongo Delalibera [1313 [13] DELALIBERA, R. G.; GIONGO, J. S.. Deformation in the strut of two pile caps. IBRACON Structural an Material Journal, v.1, n.2, p. 121-157, june, 2008.] Barros & Giongo [1414 [14] BARROS, R.; GIONGO, J. S.. Estudo experimental de blocos de fundação com cálice externo, embutido e parcialmente embutido considerando interface lisa. IBRACON Structural an Material Journal , v.6, n.5, p. 737-764, October, 2013.] and Delalibera & Giongo [1515 [15] DELALIBERA, R. G.; GIONGO, J. S.. Numerical analysis of two pile caps with sockets embedded, suject the eccentric compression load. IBRACON Structural an Material Journal , v.6, n.3, p. 436-474, june, 2013.].

4. Conclusion

The model monolith, taken as a reference, was as expected, due to the model to design used, based on Model Blévot & Frémy [44 [4] BLÉVOT, J.; FRÉMY, R. (1967). Semelles sur piex. Analles d'Institut Techique du Bâtiment et des Travaux Publics, Paris, v. 20, n. 230.], with rupture load of 2,150.00 kN. The rupture was due to the traction diagonal, followed by crushing of the strut concrete.

The model precast pile cap with rough of wall of the socket and column had underperformed the monolith model, with rupture load equal to 1420.00 kN. The ruptures occurred by diagonal traction of the strut, following by crushing of strut concrete and yield of the steel bars of the tie.

The model precast pile cap with smooth conformation of wall of the socket and column, had performance below the monolithic model. The rupture load was equal to 780 kN. The rupture occurred by punching of the background of the pile cap, near of piles. The steel bar of the tie has not shown yield, but occurred slip.

The transfer of the load of column to pile was efficient in the rough model. This indicates that the roughness of the socket and of column it worked as shear key, which allowed the formation of struts, a fact confirmed also by cracking mad of the tested model.

For the pile caps with smooth conformation, the transfer of load of column to pile was inefficient, indicating the behavior of bending and shear. Due to the small length of inlay, the conformation smooth showed shear key, transferring the load directly to background of the pile cap. This fact caused punching, what can be observed by cracking map in Figure [14]. Another fact which confirms this conclusion is the theoretical value calculated to inclination of strut, depending on the rupture load, generating a lower value than recommended by Blévot & Frémy [44 [4] BLÉVOT, J.; FRÉMY, R. (1967). Semelles sur piex. Analles d'Institut Techique du Bâtiment et des Travaux Publics, Paris, v. 20, n. 230.], as shown in Table [4].

Figure 14
Pile caps tested - identification of angle of inclination of the struts

It was found that the strength of the strut decreases the tensile force in the tie, due to the increased friction in the inferior nodal region.

The models of the monolithic pile cap and precast pile caps with the roughened conformation of the walls of the socket and the column showed characteristic behaviors of rigid pile cap, as determined by NBR 6118: 2014 [33 [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.]: the existence of the concrete compression struts, diagonal cracks of column going to the pile and flexion-compression on the piles.

But the model of the precast pile cap with the smooth conformation of the walls of the socket and the column showed similar behavior to flexible pile caps. Thus, it is evident that when using this type of conformation should work with larger inlays lengths, thus avoiding the fragile collapse, by puncturing the model.

5. Acknowledgements

To: Higher Education Personnel Improvement Coordination - CAPES for the financial support to perform the research that made it possible to write this paper.

To: Redimix Concrete Brazil S.A. for the supply of materials for molding the concrete used.

To Laboratory Carlos Campos Consultancy and Projects Ltd for the characterization of materials and the concrete dosage study.

At Prémoldaço Industry Precast Ltd for the supply of steel bars used.

Bibliographical references

  • 1
    [1] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6122:2010 - Projeto e execução de fundações. Rio de Janeiro, 2014.
  • 2
    [2] MUNHOZ, F.S. (2004). Análise do comportamento de blocos de concreto armado sobre estacas submetidos à ação de força centrada. Dissertação (mestrado) - Escola de Engenharia de São Carlos, Universidade de São Paulo, São Carlos.
  • 3
    [3] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 6118:2014 - Projeto de estruturas de concreto. Rio de Janeiro, 2014.
  • 4
    [4] BLÉVOT, J.; FRÉMY, R. (1967). Semelles sur piex. Analles d'Institut Techique du Bâtiment et des Travaux Publics, Paris, v. 20, n. 230.
  • 5
    [5] COMITE EURO-INTERNACIONAL DU BÉTON (1990). CEB-FIP Model code for concrete structures. Bulletin D'Information, Paris, n. 203-205, July.
  • 6
    [6] SCHLAICH, J.; SCHAFER, K.; JENNEWEIN, M. (1987). Toward a consistente design of reinforced structural concrete. Journal of Prestressed Concrete Institute, v. 32, n. 3, May-June;
  • 7
    [7] EL DEBS, M. K.; Concreto pré-moldado: fundamentos e aplicações. 1ª ed. São Carlos, SP, Publicações EESC-USP, 2000.
  • 8
    [8] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. ABNT NBR 9062:2006 - Projeto e execução de estruturas de concreto pré-moldado. Rio de Janeiro, 2007.
  • 9
    [9] EN 1991-1-1. Eurocode 2: Design of concrete structures - Part 1-1: General rules and rules for buildings. European standard, 2004.
  • 10
    [10] FUSCO, P. B. (1994). Técnicas de armar estruturas de concreto. Editora Pini Ltda., São Paulo.
  • 11
    [11] ADEBAR, P.; KUCHMA, D.; COLLINS, M. P. (1990). Strut-and-tie models for design of pile caps: an experimental study. ACI Journal, v. 87, p. 81-91, Jan/Feb;
  • 12
    [12] MIGUEL, G. M. (2000). Análise experimental e numérica de blocos sobre três estacas. Tese (doutorado) - Escola de Engenharia de São Carlos, Universidade de São Paulo, São Carlos;
  • 13
    [13] DELALIBERA, R. G.; GIONGO, J. S.. Deformation in the strut of two pile caps. IBRACON Structural an Material Journal, v.1, n.2, p. 121-157, june, 2008.
  • 14
    [14] BARROS, R.; GIONGO, J. S.. Estudo experimental de blocos de fundação com cálice externo, embutido e parcialmente embutido considerando interface lisa. IBRACON Structural an Material Journal , v.6, n.5, p. 737-764, October, 2013.
  • 15
    [15] DELALIBERA, R. G.; GIONGO, J. S.. Numerical analysis of two pile caps with sockets embedded, suject the eccentric compression load. IBRACON Structural an Material Journal , v.6, n.3, p. 436-474, june, 2013.