Combined axial and flexural loads in short reinforced concrete columns in fire: ultimate limit state curves using 500 °C isotherm method

Abstract

Ultimate limit state curves of short reinforced concrete columns in fire situation are going to be presented in this paper. The authors created a code developed in Matlab. It makes a discretization of the cross sections of the columns and calculates the equilibrium integrals of them. The curves were plotted with the code considering the 500 °C isotherm method.

Keywords:
reinforced concrete columns; fire situacion

Resumo

Curvas envoltórias correspondentes ao estado - limite último de pilares curtos de concreto armado em situação de incêndio serão apresentadas neste artigo. Os autores criaram um código desenvolvido no programa Matlab. Esse código realiza uma discretização da seção transversal dos pilares e o cálculo numérico das integrais de equilíbrio. As curvas foram representadas graficamente com o código considerando o método da isoterma de 500 °C.

Palavras-chave:
pilares; concreto armado; incêndio; flexão composta; isoterma de 500 ºC

1. Introduction

Combined axial and flexural loads in short reinforced concrete columns in fire situation is a very new subject studied internationally [1[1] FÉDÉRATION INTERNATIONALE DU BÉTON. Fire design of concrete structures - structural behavior and assessment. State of art report. Lausanne, 2008.] and [2[2] FÉDÉRATION INTERNATIONALE DU BÉTON. Fire design of concrete structures - materials, structures and modelling. State of art report. Lausanne, 2007.]. Several aspects should be considered in order to determine the safety of these structural elements, among others, the temperature field in the cross-section and the non-linearity of the materials. Consideration of these aspects increases the level of difficulty. As an option, a strategy is to define maximum values for strains and the pivot diagrams (Figure 1), and to apply them to create the ultimate limit state curves and surfaces, also called interaction curves and surfaces, that allow to verify the safety of the columns. They are function of, among others, the constitutive laws of concrete and reinforcing steel, the cross-section geometry and the maximum strains. There is an extensive bibliography available, such as abacuses and simplified methods [3[3] MESEGUER, A. G.; CABRÉ, F. M.; PORTERO, J. C. A. Jimenez Montoya - Hormigón Armado. Gustavo Gili, Barcelona, España, 2009.], [4[4] EUROPEAN COMMITTEE FOR STANDARIZATION. EN 1992-1-1. Eurocode 2: Design of concrete structures - part 1.2 General rules and rules for buildings. Brussels: CEN, 2004.], and more advanced numerical methods, for columns at room temperature [5[5] RODRIGUEZ, J.A.; ARISTIZABAL, O.D. Biaxial Interaction Diagrams for Short RC Columns of Any Cross Section. Journal of Structural Engineering. v. 125, p. 672-683, 1999.]. But there is a smaller quantity for fire situation, among others, advanced software DIANA, ABAQUS, ANSYS and SAFIR.

Figure 1
Pivot diagrams at room temperature

In Figure 1:

εcu: Strain conventionally corresponding to the ultimate limit state of the most compressed concrete fiber of a fully compressed cross-section.

εc2: Strain conventionally corresponding to the ultimate limit state of the less compressed concrete fiber of a fully compressed cross-section.

εsu: Strain conventionally corresponding to the ultimate limit state of the tensioned reinforcing steel.

εyd: Strain corresponding to the beginning of the yield of the reinforcing steel.

h: Cross-section high.

In fire situation, these interaction curves are function (besides the mentioned variables) of the time. In order to generate these interaction curves in fire situation, two strategies can be considered [1[1] FÉDÉRATION INTERNATIONALE DU BÉTON. Fire design of concrete structures - structural behavior and assessment. State of art report. Lausanne, 2008.], those that consider the moment-curvature relationship and those that consider the boundary strains according to pivot diagrams. Those pivot diagrams in fire situation are different of those used at room temperature, which should vary according to the temperature. The pivot diagrams have been studied in [6[6] SUAZNABAR, J.S.; SILVA, V.P.; PIERIN, I. Estudo dos Domínios de Deformação em Seções Transversais de Concreto Armado em Situação de Incêndio. 56 Congresso Brasileiro do Concreto. Natal, 2014.], they are presented in the Figure 2 and are part of more advanced researches in the same research group of the authors. However, using these domains implies a greater computational effort and allows the study of straight but not oblique composite bending of the columns [7[7] SUAZNABAR, J.S.; SILVA, V.P. Flexão composta de pilares curtos de concreto armado sob incêndio não simétrico. 3 Congresso Ibero-Latino-Americano Sobre Segurança Contra Incêndios. Porto Alegre, 2015.].

Figure 2
Pivot diagrams in fire situation

In Figure 2:

εcu,Ɵ: Strain conventionally corresponding to the ultimate limit state of the compressed concrete at Ɵ temperature.

εsu,Ɵ: Strain conventionally corresponding to the ultimate limit state of the tensioned reinforcing steel at Ɵ temperature.

εtot,i: Total strain in a point i of the fully compressed concrete cross-section.

The objective of this paper is to present a computational code developed in MATLAB [8[8] SUAZNABAR, J.S.; SILVA, V.P. Code for combined axial and flexural load on short RC columns: failure surfaces. XXXVI Jornadas Sudamericanas de Ingeniería Estructural. Montevideo, 2014.] which, through numerical methods, accurately calculates forces and moments, strains and interaction curves for short columns of reinforced concrete in fire situation. It is considered the hypotheses of the 500 °C isotherm method to generate the interaction curves.

2. Method of the 500 °C isotherm

The method of the 500 °C isotherm is a simplified method created by the swedish researcher Dr. Yngve Anderberg. In 1978, Anderberg proposed the isotherm method of 550 °C, later the method was modified considering as limit the isotherm of 500 °C.

Considering a cross section in fire situation, with the known temperature field, the method of the 500 °C isotherm consists of assuming that concrete with temperatures higher than 500 °C is disregarded. In this way, only concrete with temperatures lower than 500 °C, i.e. the region of the inner cross-section at the 500 °C isotherm, is considered. In a simplified way, the concrete of this inner region is considered with the original properties at room temperature, even the the strains, however, with the exceptional coefficients. The reinforcement is considered with the properties of the reinforcing steel at the current temperature (in fire situation).

In Figure 3, an example cross-section with the 500 °C isotherm marked in the temperature field is presented and the concrete with a temperature greater than 500 °C is disregarded.

Figure 3
Discretized cross-section with the temperature field and the isotherm of 500 °C

In spite of being considered a simplified method by EN 1992-1-2: 2004 [9[9] EUROPEAN COMMITTEE FOR STANDARIZATION. EN 1992-1-2. Eurocode 2: Design of concrete structures - part 1.2 General rules - structural fire design. Brussels: CEN, 2004.], to apply this method it is necessary to use a thermal analysis program, to calculate the temperature field in the cross-section, which is not common in civil engineering.

3. Equilibrium of the cross-section

For the development of the software the following hypothesis were considered:

  • a) In the cross-section, only the normal stresses are considered, the tangential stresses and the strains resulting from them are disregarded.

  • b) The cross-section remains plane after deformation and the total strain is the result of summing the thermal and mechanical strains.

  • c) There is bond between reinforcement and concrete.

  • d) It is not considered geometric non-linearity related to the slenderness of the column.

  • e) Thermal restrains are not considered.

Under the above hypothesis and for the region of the inner concrete section to the 500 ºC isotherm, the cross section presented in Figure 4 is considered to be in equilibrium if the system of equations 1 is satisfied.

Figure 4
Reinforced concrete cross-section

In Figure 4:

CG: Geometric center of the cross-section.

S = σ ( ε ) Z d x d y (1)

In the system of Equations 1:

S = [ N M x M y ] Z = [ 1 y x ]

Where:

N: Axial force.

Mx : Moment around the x-axis.

My : Moment around the y-axis.

In the system of Equations 1, the left-hand side represents the efforts in fire situation and the right-hand side represents the stresses and resistant forces (Figure 5).

Figure 5
Equilibrium of the cross-section, at room temperature

All the efforts and stresses cited in this paper refer to fire situation. For simplicity, the subscript “θ” was not included. The values of those efforts must be calculated following the Brazilian code ABNT NBR 15200:2012 [10[10] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 15200: Projeto de estruturas de concreto em situação de incêndio. Rio de Janeiro, 2012.].

It should be noted that in this article, the ultimate limit state curves are calculated for short columns of reinforced concrete in fire situation, using the method of 500 °C isotherm. According to that, as explained previously, the stress and strength of concrete are those corresponding to the ambient temperature, and those of the reinforcing steel are those corresponding to the current temperature (in a fire situation).

In Figure 5:

εc: Strain of concrete.

εs: Strain of reinforcing steel.

fc: Stress of concrete.

fs: Stress of reinforcing steel.

N: Axial force.

M: Moment.

To solve the system of Equations 1, a cross section discretization is performed. In this way it is possible to solve the integrals quite precisely even when there are cross sections with unusual geometry.

3.1 Equilíbrium of the discretized cross-section

The code developed by the authors allows to perform a discretization of the cross section, in square or rectangular elements. For the concrete, the strain and the stress are considered constant in each element and equal to the respective geometric center. For the reinforcement, which always have circular sections and small diameter in relation to the dimensions of the concrete cross-section, the strain and the stress are considered constant and equal to the respective geometric center of each reinforcement bar. In areas where there is overlap between the concrete and the reinforcement, the stress of the concrete corresponding to that area of the reinforcement is subtracted.

Next, the equilibrium formulation is presented for the discretized section, which is analogous to the formulation already presented. In this formulation the subscript “e” indicates that it is referring to a generic element “e”.

After the discretization, an element of the discretized section can be considered in equilibrium if the system of Equations 2 is satisfied.

S e = σ e ( ε e ) Z e d x d y (2)

In the system of Equations 2, we have:

S e = [ N e M x e M y e ] Z e = [ 1 y e x e ]

In an analogous way to the system of Equations 1, in the system of Equations 2 the left-hand side represents the efforts in fire situation related to the element and the right-hand side represents the stresses and resistant forces related to the element.

For the complete cross-section, already discretized, the system of equations 1 can be expressed according to the system of Equations 3.

N = i = 1 n e c σ c i ( ε c i ) A c i + i = 1 n e s σ s i ( ε s i ) A s i M x = i = 1 n e c σ c i ( ε c i ) y c i A c i + i = 1 n e s σ s i ( ε s i ) y s i A s i M y = i = 1 n e c σ c i ( ε c i ) x c i A c i + i = 1 n e s σ s i ( ε s i ) x s i A s i (3)

In system of Equations 3:

N: Axial force.

Mx : Moment around the x-axis.

My : Moment around the y-axis.

σci : Stress of the concrete element i.

σsi: Stress of the reinforcing steel element i.

εci : Strain of the concrete element i.

εsi : Strain of the reinforcing steel element i.

Aci : Area of the concrete element i.

Asi : Area of the reinforcing steel element i.

xci : Coordinate x of the geometric center of the concrete element i.

yci : Coordinate y of the geometric center of the concrete element i.

xsi : Coordinate x of the geometric center of the reinforcing steel element i.

It should be noted that the stress distribution is considered constant in the cross section of each element, therefore adequate discretization is required to obtain a good stress distribution in the cross section of the column.

4. Ultimate limit state curves

Under the assumptions given above, for a set of efforts in fire situation, the code applies strain fields to the cross-section and evaluates the system of Equations 3. This process is performed in an iterative way until the equilibrium is satisfied. However, it is simpler to apply the conventional strains of the ultimate limit state and to calculate the stresses related to these strains.

To generate the ultimate limit state curves, it is sufficient to define the conventional rupture strains at room temperature (remembering that the method of the 500 °C isotherm is being applied) and calculate the stresses associated with these strains.

It is worth noting that if it is necessary to obtain only the ultimate limit state curve N - Mx, all the strain fields have in common, rotations about the x axis, since the is no My moment.

For the Mx - My moments ultimate limit state curve the code applies rotations to the cross section around the longitudinal axis of the column (Figure 7) and then applies the strain fields to the rotations about the x axis. It is worth remembering that for these moment ultimate limit state curves, the axial force is constant.

Figure 6
Discretized cross-section

Figure 7
Discretized cross-section, under rotation of the longitudinal axis of the column

5. Materials

In the developed code, the recommendations of EN 1992-1-1: 2004 [4[4] EUROPEAN COMMITTEE FOR STANDARIZATION. EN 1992-1-1. Eurocode 2: Design of concrete structures - part 1.2 General rules and rules for buildings. Brussels: CEN, 2004.] and ABNT NBR 6118: 2014 [11[11] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6118: Projeto de estruturas de concreto: Procedimento. Rio de Janeiro, 2014.] were used for the stress-strain curves of concrete and reinforcing steel at room temperature. The recommendations of EN 1992-1 and ABNT NBR 15200: 2012 [10[10] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 15200: Projeto de estruturas de concreto em situação de incêndio. Rio de Janeiro, 2012.] were used for the stress-strain curves of concrete and reinforcing steel in fire situation.

Next, the stress-strain diagrams for concrete and reinforcing steel will be presented at both conventional and fire situation.

5.1 Materials at room temperature

For materials at room temperature, EN 1992-1-1: 2004 [4] and ABNT NBR 6118: 2014 [11[11] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6118: Projeto de estruturas de concreto: Procedimento. Rio de Janeiro, 2014.] recommend the use of the strain-strain curves of Figure 8 and Figure 9 given by Equations 4 and Equations 5 for compressed concrete and reinforcing steel respectively.

Figure 8
Stress-strain curve of compressed concrete at room temperature

Figure 9
Stress-strain curve of reinforcing steel at room temperature

σ c = α c c f c d [ 1 ( 1 ε c ε c 2 ) n ] 0 ε c ε c 2 σ c = α c c f c d ε c 2 ε c ε c u (4)

In Equations 4:

fcd: Design compressive strength of concrete.

αcc: Coefficient of the strength of concrete under long duration loading.

F o r | ε s | ε y d f s = E s ε s F o r ε s > ε y d f s = f y d F o r ε s < ε y d f s = f y d (5)

In Equations 5:

Es : Modulus of elasticity of reinforcing steel.

fyd : Design strength of reinforcing steel.

5.2 Materials in fire situation

For the materials in fire situation, EN 1992-1-2:2004 [9[9] EUROPEAN COMMITTEE FOR STANDARIZATION. EN 1992-1-2. Eurocode 2: Design of concrete structures - part 1.2 General rules - structural fire design. Brussels: CEN, 2004.] and ABNT NBR 15200:2012 [10[10] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 15200: Projeto de estruturas de concreto em situação de incêndio. Rio de Janeiro, 2012.] recommend the stress-strain curves of Figure 10 and Figure 11 given by Equation 6 and Equations 7 for compressed concrete and reinforcing steel respectively.

Figure 10
Stress-strain curve of compressed concrete in fire situation

Figure 11
Stress-strain curve of reinforcing steel in fire situation

σ c , θ f c , θ = 3 ( ε c , θ ε c 1, θ ) 2 + ( ε c , θ ε c 1, θ ) 3 (6)

σ s , θ = ε s , θ · E s , θ 0 ε s , θ ε p , θ σ s , θ = f p , θ c + b a · a 2 ( ε y , θ ε p , θ + c E s , θ ) ε p , θ ε s , θ ε y , θ σ s , θ = f y k , θ ε y , θ ε s , θ ε t , θ σ s , θ = f y k , θ · [ 1 ( ε s , θ ε t , θ ) ( ε u , θ ε t , θ ) ] ε t , θ ε s , θ < ε u , θ σ s , θ = 0 ε s , θ ε u , θ (7)

In Equations 6 and 7:

σ(c, θ ): Stress of concrete at θ temperature.

ε(c, θ ): Strain of concrete at θ temperature.

σ(s,θ): Stress of reinforcing steel at θ temperature.

ε(s, θ ): Strain of reinforcing steel at θ temperature.

As an example, the stress-strain curves of a concrete fc = 30 MPa for various temperature values (Figure 12) and strain-strain diagrams of the CA50 reinforcing steel, fy = 500 MPa, for various temperature values are shown below (Figure 13).

Figure 12
Stress-strain curves of concrete varying with temperature

Figure 13
Stress-strain curves of reinforcing steel varying with temperature

6. Results and comments

The mechanical analysis of reinforced concrete structures in fire situation considering the method of the 500 °C isotherm, were performed using the code developed in MATLAB [8[8] SUAZNABAR, J.S.; SILVA, V.P. Code for combined axial and flexural load on short RC columns: failure surfaces. XXXVI Jornadas Sudamericanas de Ingeniería Estructural. Montevideo, 2014.]. For this, the thermal analyzes were performed with the DIANA program, whose results were used in the mechanical analysis mentioned.

The concrete and reinforcing steel properties are fck = 30 Mpa and fy = 500 Mpa, E = 210 GPa, respectively.

Two cross-sections of 30 cm x 30 cm with 4 ϕ 16 mm (Figure 14.a) and 8 ϕ 16 mm (Figure 14.b) were studied with discretization in 1 cm x 1 cm square elements.

Figure 14a
Cross-section with 4 ϕ 16 mm

Figure 14b
Cross-section with 8 ϕ 16 mm

Figure 15a
Temperature field for 30 min

Figure 15b
Temperature field for 60 min

Figure 15c
Temperature field for 90 min

Figure 15d
Temperature field for 120 min

Afterwards, the thermal analyzes were performed for 30 min, 60 min, 90 min and 120 min of exposure to the standard curve ISO 834 (1999) [12[12] INTERNATIONAL ORGANIZATION FOR STANDARIZATION ISSO 834-1:1999(E). Fire-resistance tests - Elements of building construction - Part 1: General requirements. Ginebra, 1999.]. The corresponding temperature fields are shown in Figures 15.a, 15.b, 15.c and 15.d respectively.

Once the temperature fields are known, the code disregards concrete with temperatures higher than 500 °C, considering only the inner concrete at the 500 °C isotherm with the properties at room temperature. The reinforcement, regardless of position, were considered at their current temperature (in fire situation).

Finally, the mechanical analysis was performed verifying the equilibrium with the calculation of the system of Equations 3. It is recalled that the limit deformations of the concrete were considered at room temperature.

The ultimate limit state curves N-M and N-Mx-My were obtained as a result. N, Mx and My are the calculation efforts corresponding to the fire situation.

Then, in Figures 16.a and 16.b, the N-M curves of the two cross sections under study (Figures 14.a and 14.b) are presented for the mentioned temperature fields (Figures 15.a, 15.b, 15.c and 15.d) considering the method of 500 °C isotherm.

Figure 16a
N-Mx curves of the cross-section 30 cm x 30 cm with 4 ϕ 16 mm

Figure 16b
N-Mx curves of the cross-section 30 cm x 30 cm with 8 ϕ 16 mm

It is observed that the longer the exposure time to fire, the lower the strength of the column, with a reduction of more than 50% of the axial compressive strength (relative to its capacity at room temperature) when the column is exposed 120 minutes.

Figure 17a, 17.b, 17.c and 17.d show the Mx-My curves of the two cross sections under study for the 30, 60, 90 and 120 min temperature fields of exposure to fire ISO 834 (1999) [12[12] INTERNATIONAL ORGANIZATION FOR STANDARIZATION ISSO 834-1:1999(E). Fire-resistance tests - Elements of building construction - Part 1: General requirements. Ginebra, 1999.], considering the isotherm method of 500 °C, for 3 constant axial loads.

Figure 17a
Mx - My curves of the cross-section with 4 ϕ 16 mm for NNcmax20 = 0.20

Figure 17b
Mx - My curves of the cross-section with 4 ϕ 16 mm for NNcmax20 = 0.40

Figure 17c
Mx - My curves of the cross-section with 8 ϕ 16 mm for NNcmax20 = 0.20

Figure 17d
Mx - My curves of the cross-section with 8 ϕ 16 mm for NNcmax20 = 0.40

In the previous figures Ncmax20 is the maximum axial strength in compression at room temperature of the column.

The column strength decreases when temperature and/or axial loading increase.

It should be noted that each point marked on the interaction curves corresponds to a calculated solution of the system of Equations 3.

It is also noted that in this article the thermal deformation restrictions were not considered.

The decrease of the maximum axial strength of centered compression of the sections shown in Figures 14.a and 14.b for the standard fire exposure times shown in Figures 15.a, 15.b, 15.c and 15.d is shown in Table 1.

Table 1
Decrease of axial strength as a function of time of exposure to fire

In this paper all the coefficients of strength and the effects of decreasing the concrete strength with time (Rüsch effect, etc.) were considered unitary since they were problems associated with exceptional short-term situations.

The code developed by the authors of this paper is being developed in addition to the method of the 500 ºC isotherm, in order to perform mechanical analysis considering the variation of stress-strain diagrams as a function of temperature and the variation of stresses in the cross section (Figure 18).

Figure 18
Stress field of the cross-section 30 cm x 30 cm with 4 ϕ 16 mm under axial compression

7. Conclusions

In order to perform numerical modeling of short columns of reinforced concrete in a fire situation, the use of the 500 °C isotherm method proved to be a suitable strategy.

The computational code developed for this article was able to generate ultimate limit state curves using the method of the 500 °C isotherm, combined with a method that solves the integrals and systems of equations using a discretization of the cross section.

As expected, the results showed that the longer the exposure time to fire the higher the temperature in the cross section, therefore the lower the strength of the column. The results also showed that the higher the compressive force on the column, the shorter the time it reaches the ultimate limit state.

Finally, it is emphasized that the mathematics used to study the phenomena studied involves systems of equations with integral of non-linear equations. The resolution of these systems of equations was possible using approximate methods with discretization of the cross section considered in the academic environment as advanced methods.

8. Acknowledgments

The authors thank CAPES “Coordenação de Aperfeiçoamento de Pessoal de Nível Superior”, CNPq “Conselho Nacional de Pesquisa e Desenvolvimento Científico” and FAPESP “Fundação de Amparo à Pesquisa do Estado de São Paulo”.

9. References

  • [1]
    FÉDÉRATION INTERNATIONALE DU BÉTON. Fire design of concrete structures - structural behavior and assessment. State of art report. Lausanne, 2008.
  • [2]
    FÉDÉRATION INTERNATIONALE DU BÉTON. Fire design of concrete structures - materials, structures and modelling. State of art report. Lausanne, 2007.
  • [3]
    MESEGUER, A. G.; CABRÉ, F. M.; PORTERO, J. C. A. Jimenez Montoya - Hormigón Armado. Gustavo Gili, Barcelona, España, 2009.
  • [4]
    EUROPEAN COMMITTEE FOR STANDARIZATION. EN 1992-1-1. Eurocode 2: Design of concrete structures - part 1.2 General rules and rules for buildings. Brussels: CEN, 2004.
  • [5]
    RODRIGUEZ, J.A.; ARISTIZABAL, O.D. Biaxial Interaction Diagrams for Short RC Columns of Any Cross Section. Journal of Structural Engineering. v. 125, p. 672-683, 1999.
  • [6]
    SUAZNABAR, J.S.; SILVA, V.P.; PIERIN, I. Estudo dos Domínios de Deformação em Seções Transversais de Concreto Armado em Situação de Incêndio. 56 Congresso Brasileiro do Concreto. Natal, 2014.
  • [7]
    SUAZNABAR, J.S.; SILVA, V.P. Flexão composta de pilares curtos de concreto armado sob incêndio não simétrico. 3 Congresso Ibero-Latino-Americano Sobre Segurança Contra Incêndios. Porto Alegre, 2015.
  • [8]
    SUAZNABAR, J.S.; SILVA, V.P. Code for combined axial and flexural load on short RC columns: failure surfaces. XXXVI Jornadas Sudamericanas de Ingeniería Estructural. Montevideo, 2014.
  • [9]
    EUROPEAN COMMITTEE FOR STANDARIZATION. EN 1992-1-2. Eurocode 2: Design of concrete structures - part 1.2 General rules - structural fire design. Brussels: CEN, 2004.
  • [10]
    ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 15200: Projeto de estruturas de concreto em situação de incêndio. Rio de Janeiro, 2012.
  • [11]
    ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6118: Projeto de estruturas de concreto: Procedimento. Rio de Janeiro, 2014.
  • [12]
    INTERNATIONAL ORGANIZATION FOR STANDARIZATION ISSO 834-1:1999(E). Fire-resistance tests - Elements of building construction - Part 1: General requirements. Ginebra, 1999.