Abstract
The objective was to verify the influence of roof pitch, exposure and roofing material on the internal temperature of reduced models of animal production facilities. For the development of the research, 48 reduced models with dimensions 1.00 × 1.00 × 0.50m were used. The roof was shed-type, and models faced the North or South directions, with 24 models for each side of exposure. Ceramic, galvanized-steel and fibro tiles were used to build the roofs. Pitches varied between 20; 30; 40 and 50% for the ceramic tile and 10; 30; 40 and 50% for the other two. Inside the model, temperature readings were performed at every hour, for 12 months. The results were evaluated in a general linear model in a nested 3 × 4 × 2 factorial arrangement. As the roof pitch increased, the internal temperature within the model dropped, so utilizing sharper pitches (50%) for ceramic and fibro roofs with a larger area facing the South can provide lower temperatures within the animal production facilities. In regions where the cold is more stressful than the heat, having animal production facilities with larger roof exposure to the North may minimize the losses caused by cold stress.
ambience; aviculture; heat; shed
Resumo
Objetivou-se verificar a influencia da inclinação, exposição e tipo de material de cobertura sobre a temperatura interna de modelos reduzidos de instalação zootécnica, em condições ambientais das coordenadas geográficas “21°14´05 de latitude sul e 48°17´09´´ de longitude oeste. Para o desenvolvimento da pesquisa foram utilizados 48 modelos reduzidos nas dimensões de 1,00 x 1,00 x 0,50 metros. A cobertura foi de uma água, dispostos nas exposições Norte-Sul, sendo 24 modelos para cada face de exposição. Foram utilizadas na cobertura, telha de cerâmica, aço galvanizado e fibrocimento. Os níveis de inclinação foram de 20; 30; 40 e 50% para telha de cerâmica e de 10; 30; 40 e 50% para as demais. No interior dos modelos foram realizadas leituras de temperatura, a cada hora durante 12 meses. Os resultados obtidos foram avaliados num modelo linear geral no esquema fatorial aninhado 3 X 4 X 2. As médias obtidas foram comparadas pelo teste de Tukey a 5% de probabilidade. Com o aumento da inclinação do telhado, a temperatura interna dentro do modelo reduziu, de modo que inclinações mais acentuadas (50%) para coberturas de cerâmica e fibrocimento, com uma maior exposição de cobertura para o sul, pode proporcionar temperaturas mais baixas dentro das instalações zootécnicas. Em regiões onde o frio é mais estressante do que o calor, as instalações com maior exposição de cobertura para o Norte pode minimizar as perdas causadas pelo estresse causado pelo frio.
ambiência; avicultura; calor; galpão
INTRODUCTION
The animal production facility is aimed at providing comfort and protection to the animals for increased productivity. The constructions are directly exposed to the weather conditions, and so they must be built so as to reduce the environmental variables that negatively interfere with the welfare and performance of animals.
Conducting research on animal production facilities on a natural scale is costly and not very practical, which has led researchers such as Hann et al. (1961)HANN, L.; BOND, T.E.; KELLY, C.F. Use of models in thermal shades of livestock housing. Transactions of the ASAE, v.4, n.1, p.45-51, 1961., Forehlich et al. (1975)FOREHLICH, D.P.; HELLICKSON, M.A.; YOUNG, H.G. Ridge vents effects on model ventilation characteristics. Transactions of the ASAE, v.18, n.4, p.690-693, 1975. and Celis & Jara (1990)CELIS, J.G.; JARA, J.C. Aplication del analisis dimensional para estimar laventilacíon natural em galpones para aviários. Agro Ciência, v.6, n.1, p.31-36, 1990.to utilize distorted-scale models in their experiment involving this matter. In addition to reproducing the characteristics and thermal responses of natural facilities, these models reduce the experimental costs.
Among the many research studies applied in animal production facilities, those involving roof pitches are scarce, and the quantification of the incoming solar radiation on the pitched surfaces in relation to the flat surface, at different angles, is used in a large variety of applications (solar panels, architecture projects, agronomic research and micrometeorological studies). According to Coan et al. (2012)COAN, R.M.; TURCO, J.E.P.; PIVETTA; K.F.L.; COSTA; M.N. da.; MATEUS, C.M. D'A. Emerald zoyzia grass development regarding photo synthetically active radiation in different slopes. Revista Engenharia Agrícola, v.32, n.3, p.501-509, 2012., the total radiation hitting a surface varies according to the exposure and declivity.
Thus, the objective of this study was to verify the influence of pitch and the North- and South-exposure of ceramic, galvanized-steel and fibro tiles on the internal temperature of reduced models of animal production facilities during the fall and winter.
MATERIAL AND METHODS
The experiment was conducted at the Department of Rural Engineering and the Department of Animal Morphology and Physiology of the Faculty of Agrarian and Veterinary Sciences (FCAV/UNESP), located in Jaboticabal, SP, Brazil. During the trial period, the average temperature was 22,6ºC, maximum temperature of 30,1ºC and a minimum of 17,0ºC, with an average rainfall of 1225mm. Forty-eight reduced models with dimensions 1.00 × 1.00 × 0.50m were built, thereby having the same air volume as the interior of all models. Wooden rods of different sizes were built to incline them. The material utilized was plywood with 6.0mm of thickness on the sides and on the bottom so as to avoid the effect of the climate variables from outdoors as much as possible, so that the alterations in the internal environment did not undergo major effects originated from the roof.
The reduced models of plywood were painted with waterproof white paint to increase their reflectivity and endurance against weathering. Roofs were shed-like. Half of the models faced the North, and the other 24 faced the South direction, with two replications per pitch. The models were covered with 0.5mm tick roman ceramic; 0.5mm thick galvanized steel; and 6.00mm thick fibro tiles. The pitches of the roofs varied between 20; 30; 40 and 50% for the ceramic tile and 10; 30; 40 and 50% for the others. The pitch of 10% was not used in the ceramic roof because according to the technical engineering specifications, ceramic tiles cannot be set up with pitches lower than 20%. The models were built on the Campus of UNESP Jaboticabal, located at 21°14´05´´ South latitude, 48°17´09´´ West longitude and 615.01m altitude, utilizing an area of 160m2 (Agro meteorological station of the Rural Engineering Department -FCAV/UNESP).
Was evaluated the ceramic, galvanized steel and fibro tiles and different roof pitches and their (North/South) exposure as to their influence on the internal temperature. The data on the external environment of the experiment were collected by a conventional, automated meteorological station at the Department of Exact Sciences of UNESP/Jaboticabal. To obtain the data on the internal temperature of the models, one type T thermocouple model 105T with accuracy of ± 1°C was properly positioned at the center of the model and another at two centimeters below the roof, held by wood supports. The data on internal temperature of the models were read at every hour, for one year, using data acquisition system Datalogger (Campbell Scientific Inc). After collecting the data for one year, they were filtered to exclude the days that had a ratio of insolation above 85% (obtained from the meteorological station of Department of Exact Sciences of UNESP/Jaboticabal) so as to avoid the cloudy and rainy days.
From the dataset, one critical winter day was selected for analysis of the variation of temperature throughout the day according to the pitches, roofing materials and exposures. The estimated solar radiation data were collected at the Meteorological Station of the Department of Rural Engineering of FCAV/UNESP in a structure called "Experimental Watershed", described in detail by Turco & Rizzatti (2006)TURCO, J.E.P.; RIZZATTI, G.S. Avaliação de modelo matemático para estimar a radiação solar incidente sobre superfícies com diferentes exposições e declividades. Revista Engenharia Agrícola, v.26, n.1, p.257-267, 2006.. The results were evaluated in a General linear model by statistical package SAS version 9.1 (SAS, 2001) on a nested 3 × 4 × 2 factorial arrangement for the roofing material, roof pitch and North/South exposure values, respectively. The effects of roofing material and exposure, however, were nested in the pitch factor. The means were compared by the Tukey test at 5% of probability by following the statistical model below:
Where:
Yijkl = observation of roof i, with pitch j and exposure k;
m = overall mean;
Ci = effect of roofing material i, where i = 1, 2, 3;
Ej = effect of exposure j, where j = 1, 2;
CE(ik) = effect of the interaction between roofing material i and exposure j;
Ik : (CiEj) = effects of the interaction pitch k nested between roofing material i and exposure j; and
eijk = error associated with each observation.
RESULTS AND DISCUSSION
When the pitch of the South-facing roof is increased, there was a decrease in the incoming global solar radiation (Table 1), which is due to the lower incidence of estimated global solar radiation on pitched surfaces facing the South.
Estimated global solar radiation for the pitches of 10, 20, 30, 40 and 50% on the North (N)- and South (S)-facing roofs during the hottest day of the experimental period in Jaboticabal city
During the critical winter days, there was a more marked difference in temperature variation as regards the North- and South-facing roofs (Figures 1, 2 and 3), because the inclination of the sun changes throughout the year, and is maximized in the fall and winter. This demonstrates that the incidence of incoming solar radiation in the fall and winter in the North-facing roof is much higher. This fact can be of great importance, especially in the starter phases of poultry and pig rearing, or in areas that have very low temperature averages like certain regions in the south of Brazil.
Temperature variation in the shed during the critical winter day with the fibro roof (FN- North; FS - South) with pitches of 10 and 50%
Temperature variation in the shed during the critical winter day with the ceramic roof (CN - North; CS - South) with pitches of 20 and 50%
Temperature variation in the shed during the critical winter day with the galvanized-steel roof (AN - North; AS - South) with pitches of 10 and 50%
However, analyzing the temperature variations between the roofing materials, observe that they were not very common on the critical winter day, i.e., there was no difference between roofing materials, except for the galvanized-steel tile.
Regarding the temperature variation during the critical winter days according to the pitches, there were lower temperatures at the pitches of 50% of ceramic, fibro and galvanized-steel tiles. Solar radiation is a key element in the climatic characterization of regions, because it is the main cause of all meteorological phenomena, at the study site, the estimated average daily values of global solar radiation at the soil level in the fall and winter are 437.0 and 383.3cal/cm2/day, respectively (PEDRO JÚNIOR et al., 1989PEDRO JÚNIOR, M.J.; ALFONSI, R.R.; CAMARGO, M.B.P.Disponibilidade de radiação solar global para o estado de São Paulo. Campinas, SP: Instituto Agronômico de Campinas, 1989. (Boletim Técnico, 123).).
No interaction between the roof pitch, exposure and different roofing materials (Table 2). Analyze separately the exposure and the roof pitch, we note (Figure 4and 5) that as we increase the roof pitch in southern exposure occurred a decrease in the internal temperature of the models both in the fall and winter, corroborating the interaction occurred between the type of roofing material and exposure (Table 3), despite hedging and exposure are nested on gradient factor.
Variation of the internal temperature (ºC) in function of pitch factor for the different roofing materials [Ceramic (A and B), Fibro (C and D), and Galvanized steel (E and F)] and exposures [North (A, C and E) and South (B, D and F)] in the Fall season
Variation of the internal temperature (ºC) in function of pitch factor for the different roofing materials [Ceramic (A and B), Fibro (C and D), and Galvanized steel (E and F)] and exposures [North (A, C and E) and South (B, D and F)] in the Winter season
By elevating the roof pitch, we modify the height between the apertures for entry and exit of air, thereby affecting the environmental thermal conditioning within the shed, changing the coefficient accordingly to the exchange of heat by radiation between the animal and the roof. Results of improvement in the thermal comfort indices of sheds when the pitch was increased have also been observed by Tinôco (2001)TINÔCO, I.F.F. Avicultura Industrial: Novos Conceitos de Materiais, Concepções e Técnicas Construtivas Disponíveis para Galpões Avícolas Brasileiros. Revista Brasileira de Ciência Avícola, v.3, n.1, p.1-26, 2001.. Although the ceramic tiles did not differ statistically from fibro in the present study, results demonstrating the efficiency of the ceramic tiles, in the literature, are plenty (PARKER, 1963PARKER, B.F. Heat transmission caracteristics of sloped roofs exposed to solar radiation. Transactions of the ASAE, v.8, n.1, p.1-5, 1963.; SEVEGNANI et al., 1994SEVEGNANI, K.B.; GHELFI FILHO, H.; SILVA, I.J.O. da. Comparação de vários materiais de cobertura através de índices de conforto térmico.Scientia Agricola, v.51, n.1, p.1-7, 1994.; JÁCOME et al. 2007JÁCOME, I.M.T.D.; FURTADO, D.A.; LEAL, A.F.; SILVA, J.H.V.; MOURA, J.F.P. Avaliação de índices de conforto térmico de instalações para poedeiras no Nordeste do Brasil. Revista Brasileira de Engenharia Agrícola e Ambiental, v.11, n.5, p.527-531, 2007.; FURTADO et al., 2003FURTADO, D.A.; AZEVEDO de, P.V.; TINOCO, I.F.F. Análise do conforto térmico em galpões avícolas com diferentes sistemas de acondicionamento.Revista Brasileira de Engenharia Agrícola e Ambiental, v.7, n.3, p.559-564, 2003.; SANTOS et al., 2005SANTOS, P.A. dos; YANAGI JUNIOR, T.; TEIXEIRA, V H. Ambiente térmico no interior de modelos de galpões avícolas em escala reduzida com ventilação natural e artificial dos telhados. Revista Engenharia Agrícola, v.25, n.3, p.575-584, 2005.).
The total global solar radiation hitting a surface varies according to the North-South exposure and declivity, demonstrating that one can obtain better thermal performance results in the ceramic and fibro tiles by increasing the pitch with greater exposure to the South when aiming at reducing the temperature, and to the North, to increase it.
This feature is best expressed in Table 3, between roofing material and exposure, due to the inclination of the sun to be more pronounced at these stations. It can be seen that in the southern exposure were presented the lowest mean internal temperature of the reduced models. However, it is worth stressing that the temperatures observed in the fall and winter seasons were above the thermal-comfort range for poultry (when the internal average temperatures of the models were above 28.0ºC), and considering Curtis (1983)CURTIS, S.E. Environmental management in animal agriculture. Ames: The Iowa State University, 1983. 409p., who stated that the thermal comfort zone of poultry is between 18 and 28ºC. Therefore, we must be very careful in the hottest seasons and also in the seasons considered less critical (fall and winter), so that animal performance is not impaired. Thus, depending on the dimension and duration of the heat stress suffered by birds, undesirable events such as decrease in weight gain or even prostration and death may occur.
Analyzing the thermal performance of the galvanized-steel roof, the results are most probably due to the higher conductivity of the metallic materials, i.e., metals have a greater capacity of receiving heat or cold, but are also easier to disperse them, so they would heat faster than other materials and consequently get cold faster as well. Despite having more reflectance, the metallic roof showed the highest temperatures, which can be explained by the low emissivity of the material, making its internal environment more uncomfortable. It is possible that the heat-exchange capacity was not obtained at the data collection due to the low air renewal within the model, which probably played a part in the negative result of the galvanized-steel roof. As the roof pitch increased, the internal temperature within the model dropped, so utilizing sharper pitches (50%) for ceramic and fibro roofs with a larger area facing the South can provide lower temperatures within the animal production facilities. In regions where the cold is more stressful than the heat, having animal production facilities with larger roof exposure to the North may minimize the losses caused by cold stress.
ACKNOWLEDGEMENTS
We thanks the São Paulo Research Foundation (FAPESP) for funding this research project and for the fellowship received by Marcos Eli Buzanskas (2013/19335-2).
REFERENCES
- CELIS, J.G.; JARA, J.C. Aplication del analisis dimensional para estimar laventilacíon natural em galpones para aviários. Agro Ciência, v.6, n.1, p.31-36, 1990.
- COAN, R.M.; TURCO, J.E.P.; PIVETTA; K.F.L.; COSTA; M.N. da.; MATEUS, C.M. D'A. Emerald zoyzia grass development regarding photo synthetically active radiation in different slopes. Revista Engenharia Agrícola, v.32, n.3, p.501-509, 2012.
- CURTIS, S.E. Environmental management in animal agriculture Ames: The Iowa State University, 1983. 409p.
- FOREHLICH, D.P.; HELLICKSON, M.A.; YOUNG, H.G. Ridge vents effects on model ventilation characteristics. Transactions of the ASAE, v.18, n.4, p.690-693, 1975.
- FURTADO, D.A.; AZEVEDO de, P.V.; TINOCO, I.F.F. Análise do conforto térmico em galpões avícolas com diferentes sistemas de acondicionamento.Revista Brasileira de Engenharia Agrícola e Ambiental, v.7, n.3, p.559-564, 2003.
- HANN, L.; BOND, T.E.; KELLY, C.F. Use of models in thermal shades of livestock housing. Transactions of the ASAE, v.4, n.1, p.45-51, 1961.
- JÁCOME, I.M.T.D.; FURTADO, D.A.; LEAL, A.F.; SILVA, J.H.V.; MOURA, J.F.P. Avaliação de índices de conforto térmico de instalações para poedeiras no Nordeste do Brasil. Revista Brasileira de Engenharia Agrícola e Ambiental, v.11, n.5, p.527-531, 2007.
- PARKER, B.F. Heat transmission caracteristics of sloped roofs exposed to solar radiation. Transactions of the ASAE, v.8, n.1, p.1-5, 1963.
- PEDRO JÚNIOR, M.J.; ALFONSI, R.R.; CAMARGO, M.B.P.Disponibilidade de radiação solar global para o estado de São Paulo Campinas, SP: Instituto Agronômico de Campinas, 1989. (Boletim Técnico, 123).
- SANTOS, P.A. dos; YANAGI JUNIOR, T.; TEIXEIRA, V H. Ambiente térmico no interior de modelos de galpões avícolas em escala reduzida com ventilação natural e artificial dos telhados. Revista Engenharia Agrícola, v.25, n.3, p.575-584, 2005.
- SEVEGNANI, K.B.; GHELFI FILHO, H.; SILVA, I.J.O. da. Comparação de vários materiais de cobertura através de índices de conforto térmico.Scientia Agricola, v.51, n.1, p.1-7, 1994.
- STATISTICAL ANALISYS SYSTEM –SAS. User’s Guide. Version 9.1. Cary: SAS Institute, 2001. 943 p.
- TINÔCO, I.F.F. Avicultura Industrial: Novos Conceitos de Materiais, Concepções e Técnicas Construtivas Disponíveis para Galpões Avícolas Brasileiros. Revista Brasileira de Ciência Avícola, v.3, n.1, p.1-26, 2001.
- TURCO, J.E.P.; RIZZATTI, G.S. Avaliação de modelo matemático para estimar a radiação solar incidente sobre superfícies com diferentes exposições e declividades. Revista Engenharia Agrícola, v.26, n.1, p.257-267, 2006.