Ultrasonic wave propagation in thermally treated concrete up to 400 ºC

Propagação de ondas ultrassônicas em concreto termicamente tratado até 400 ºC

Abstract

The ultrasonic pulse velocity, obtained by ultrasonic non-destructive testing, has been applied to evaluate the concrete integrity. The attenuation parameters have shown more sensitivity to damage detection in the microstructure of concrete since they consider the entire ultrasonic waveform. However, it is still necessary to evaluate the sensitivity of those parameters to thermally damaged concrete. This work aims to assess the behavior and the sensitivity of the following ultrasonic parameters: pulse and group velocities, maximum amplitude, total energy, accumulated energy, and time instants corresponding to 25%, 50%, and 75% of the energy, in detecting changes due to thermal degradation of the concrete. A sample of 39 cylindrical concrete specimens with 100 mm in diameter and 300 mm in length and C25 strength class was used. The sample was distributed into 5 groups heated between 20 and 400 ºC until the internal temperature of the specimens became homogeneous. The groups were cooled inside a muffle furnace until reaching 150 ºC. Subsequently, they were exposed to the ambient temperature and humidity of the laboratory environment for, at least, 24 hours prior to the tests of mass loss, ultrasound, and compressive strength. The results show that the ultrasonic parameters are sensitive to the thermal degradation of the concrete. The pulse velocity, the accumulated energy, and the time instants corresponding to percentages of the energy decrease monotonically as the temperature increases. The group velocity shows significant dispersions, while the maximum amplitude and the total energy increase at 200 ºC. The results led to the conclusion that the pulse velocity is the least sensitive parameter, while the time instants corresponding to 25%, 50%, and 75% of the energy are the most sensitive parameters in detecting changes due to thermal degradation of the concrete.

Keywords:
ultrasound; attenuation parameters; sensitivity; concrete; high temperatures

Resumo

A velocidade de pulso ultrassônico, obtida por meio do ensaio não destrutivo do ultrassom, tem sido usada para avaliar a integridade do concreto. Os parâmetros de atenuação têm apresentado maior sensibilidade na detecção de danos na microestrutura do concreto, visto que consideram todo o formato da onda ultrassônica. Porém, ainda é necessária a avaliação da sensibilidade desses parâmetros ao concreto danificado termicamente. Este trabalho tem como objetivo avaliar o comportamento e a sensibilidade dos seguintes parâmetros ultrassônicos: velocidades de pulso e de grupo, amplitude máxima, energia total, energia acumulada e tempos de propagação correspondentes a 25%, 50% e 75% da energia, na detecção de mudanças devidas à degradação térmica do concreto. Uma amostra de 39 corpos de prova cilíndricos de concreto de 100 mm de diâmetro e 300 mm de comprimento e de classe de resistência C25 foi usada. Ela foi distribuída em 5 grupos aquecidos entre 20 e 400 ºC, até que a temperatura interna dos corpos de prova se tornasse homogênea. Os grupos foram resfriados dentro do forno elétrico até 150 ºC. Em seguida, eles foram expostos à temperatura e à umidade do laboratório por, no mínimo, 24 horas antes dos ensaios de perda de massa, de ultrassom e de resistência à compressão. Os resultados mostram que os parâmetros do ultrassom são sensíveis à degradação térmica do concreto. A velocidade de pulso, a energia acumulada e os tempos correspondentes às porcentagens de energia decrescem monotonicamente conforme a temperatura aumenta. A velocidade de grupo apresenta dispersões significativas, enquanto a amplitude máxima e a energia total aumentam aos 200 ºC. Os resultados permitem concluir que a velocidade de pulso é o parâmetro que possui menor sensibilidade, enquanto os tempos correspondentes a 25%, 50% e 75% da energia são considerados os parâmetros de maior sensibilidade na detecção de mudanças devido à degradação térmica do concreto.

Palavras-chave:
ultrassom; parâmetros da atenuação; sensibilidade; concreto; altas temperaturas

1 INTRODUCTION

Ultrasonic testing is a non-destructive method based on the propagation of stress waves, which has been used in the analysis of concrete quality. It detects superficial and internal damage using a fast and simple procedure. Since it is a non-destructive method, it allows monitoring the internal structure of the concrete. Therefore, ultrasonic testing can help in selecting appropriate procedures for the repair and rehabilitation of concrete structures and in the concrete integrity assessment, even in cases of fire damage [11 International Atomic Energy Agency, Guidebook on non-destructive testing of concrete structures. Vienna: IAEA, 2002.], [22 T. R. Naik, V. M. Malhotra, and J. S. Popovics, Nondestructive testing of concrete, 2nd ed. Florida: CRC, 2004.].

The ultrasonic pulse velocity (UPV) is commonly used to indicate the damage degree, since velocities are generally lower in damaged concrete [33 S. A. Kumar and M. Santhanam, “Detection of concrete damage using ultrasonic pulse velocity method,” in Proc. National Seminar on Non-Destructive Evaluation, 2006.], [44 S. K. Handoo, S. Agarwal, and S. K. Agarwal, "Physicochemical, mineralogical, and morphological characteristics of concrete exposed to elevated temperatures," Cement Concr. Res., vol. 32, pp. 1009–1018, 2002.]. However, according to Santhanam [55 M. Santhanam, "Ultrasonic characterization of damage in concrete," Tech Sci. Press, vol. 3, no. 2, pp. 111–125, 2010.] and Shiotani and Aggelis [66 T. Shiotani and D. G. Aggelis, "Wave propagation in cementitious material containing artificial distributed damage," Mater. Struct., vol. 42, pp. 377–384, 2009.], this parameter does not give a complete evaluation of the concrete damage since ultrasonic pulse velocity (UPV) is measured from the first detectable wave disturbance. Signal processing applied to the ultrasound method made feasible the analysis of attenuation parameters, such as group velocity, maximum amplitude, and energy, by analyzing the ultrasonic waveforms [77 A. V. Hauwaert, J. F. Thimus, and F. Delannay, "Use of ultrasonics to follow crack growth," Ultrasonics, vol. 36, pp. 209–217, 1998.]. Ultrasound attenuation is the result of energy loss due to scattering from the concrete microstructure, which redirects the energy beam, and due to dissipation from the viscoelastic water/cement matrix, which is related to the energy absorption [88 P. Anugonda, J. S. Wiehn, and J. A. Turner, "Diffusion of ultrasound in concrete," Ultrasonics, vol. 39, pp. 429–435, 2001.].

According to Hauwaert [77 A. V. Hauwaert, J. F. Thimus, and F. Delannay, "Use of ultrasonics to follow crack growth," Ultrasonics, vol. 36, pp. 209–217, 1998.], the attenuation parameters are more sensitive to damage since they include information from the ultrasonic signal in an entire time window. Research has shown the sensitivity of attenuation parameters to the presence of cracks and non-homogeneities in concrete specimens with compressive strength of 20 to 70 MPa and 28 days to 4 years old [55 M. Santhanam, "Ultrasonic characterization of damage in concrete," Tech Sci. Press, vol. 3, no. 2, pp. 111–125, 2010.], [99 T. P. Phillipidis and D. G. Aggelis, "Experimental study of wave dispersion and attenuation in concrete," Ultrasonics, vol. 43, pp. 584–595, 2005.], [1010 F. C. Souza and R. C. A. Pinto, “Ultrasonic investigation on the effectiveness of crack repair in concrete,” Rev. IBRACON Estrut. Mater., vol. 13, no. 5, 2020.]. Santhanam [55 M. Santhanam, "Ultrasonic characterization of damage in concrete," Tech Sci. Press, vol. 3, no. 2, pp. 111–125, 2010.], Moradi-Marani [1111 F. Moradi-Marani, P. Rivard, C. P. Lamarche, and S. A. Kodjo, “Evaluating the damage in reinforced concrete slabs under bending test with the energy of ultrasonic waves,” Constr. Build. Mater., vol. 73, pp. 663–673, 2014.], Carelli [1212 J. M. Carelli, “Análise do comportamento de ondas ultrassônicas em elementos fissurados de concreto e argamassa,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2014.], Hofmann [1313 M. A. Hofmann, “Atenuação da energia do sinal ultrassônico na detecção de danos por fissuração no concreto,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2015.] and Silva [1414 P. M. Silva, “Análise da perda de rigidez em vigas de concreto armado devido à fissuração por esforços de flexão utilizando ensaio de ultrassom,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2017.] studied the behavior of attenuation parameters in cubic concrete specimens and reinforced concrete beams subjected to loading. The results have shown that attenuation parameters are more sensitive than pulse velocity to the presence of damage. Hauwaert [77 A. V. Hauwaert, J. F. Thimus, and F. Delannay, "Use of ultrasonics to follow crack growth," Ultrasonics, vol. 36, pp. 209–217, 1998.] analyzed cubic concrete specimens with saw-cut and reported that the maximum amplitude and the energy are more sensitive to the presence of microcracks. Camara [1515 R. M. Camara, “Estudo do efeito da variação de pressão de acoplamento no comportamento dos parâmetros ultrassônicos,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2017.] analyzed cubic concrete specimens with non-homogeneities and observed that the group velocity and the time instants corresponding to percentages of the energy are more sensitive to the presence of non-homogeneities. In addition, Aggelis et al. [1616 D. G. Aggelis, T. Shiotani, and D. Polyzos, "Characterization of surface crack depth and repair evaluation using Rayleigh waves," Cement Concr. Compos., vol. 31, pp. 77–83, 2009.] and Souza and Pinto [1010 F. C. Souza and R. C. A. Pinto, “Ultrasonic investigation on the effectiveness of crack repair in concrete,” Rev. IBRACON Estrut. Mater., vol. 13, no. 5, 2020.] simulated a repair process using epoxy for filling cracks in concrete specimens and reported that the maximum amplitude and the total energy increase, as the epoxy fills the crack.

In concrete structures subjected to fire, the damage detected by the ultrasound method is related to physicochemical changes in the cement paste and the aggregates, as well as their thermal incompatibility [1717 B. Fernandes, A. M. Gil, F. L. Bolina, and B. F. Tutikian, "Microstructure of concrete subjected to elevated temperatures: Physico-chemical changes and analysis techniques," IBRACON Struct. Mater. J., vol. 10, no. 4, pp. 838–863, 2017.], [1818 Q. Ma, R. Guo, Z. Zhao, Z. Lin, and K. He, "Mechanical properties of concrete at high temperature—A review," Constr. Build. Mater., vol. 93, pp. 371–383, 2015.]. The first effects of the temperature rise occur when concrete is heated around 100 ºC. The cement paste starts to lose the free water present in the pores, followed by capillary, adsorbed, and interlayer waters, contributing to the porosity and the calcite increase [1717 B. Fernandes, A. M. Gil, F. L. Bolina, and B. F. Tutikian, "Microstructure of concrete subjected to elevated temperatures: Physico-chemical changes and analysis techniques," IBRACON Struct. Mater. J., vol. 10, no. 4, pp. 838–863, 2017.], [1919 R. C. A. Lima, L. F. Caetano, and L. S. Filho, "Microstructural changes in high density concretes exposed to high temperatures," IBRACON Mater. J., vol. 10, no. 1, pp. 7–14, 2005.], [2020 M. Castellote, C. Alonso, C. Andrade, X. Turrillas, and J. Campo, "Composition and microstructural changes of cement pastes upon heating, as studied by neutron diffraction," Cement Concr. Res., vol. 34, pp. 1633–1644, 2004.]. In addition, ettringite starts to decompose [2020 M. Castellote, C. Alonso, C. Andrade, X. Turrillas, and J. Campo, "Composition and microstructural changes of cement pastes upon heating, as studied by neutron diffraction," Cement Concr. Res., vol. 34, pp. 1633–1644, 2004.], [2121 M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Thermal and mechanical properties of concrete and its constituents at elevated temperatures: A review," Constr. Build. Mater., vol. 270, pp. 121398, 2021.]. Between 105 and 110 ºC, chemically bound water from the calcium silicate hydrate (CSH) starts to be released [1818 Q. Ma, R. Guo, Z. Zhao, Z. Lin, and K. He, "Mechanical properties of concrete at high temperature—A review," Constr. Build. Mater., vol. 93, pp. 371–383, 2015.], [2222 O. Arioz, "Effects of elevated temperatures on properties of concrete," Fire Saf. J., vol. 42, no. 8, pp. 516–522, 2007.]. At 180 ºC, CSH gel starts to dissociate and, consequently, the cement paste loses its binding property, and its porosity increases [2121 M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Thermal and mechanical properties of concrete and its constituents at elevated temperatures: A review," Constr. Build. Mater., vol. 270, pp. 121398, 2021.]. Between 200 and 300 ºC, capillary water evaporates completely [1919 R. C. A. Lima, L. F. Caetano, and L. S. Filho, "Microstructural changes in high density concretes exposed to high temperatures," IBRACON Mater. J., vol. 10, no. 1, pp. 7–14, 2005.]. Above 300 ºC, the siliceous aggregates lose their strength more expressively, resulting in the shrinkage, the appearance of microcracks, and the reduction in the mechanical properties of the concrete [2222 O. Arioz, "Effects of elevated temperatures on properties of concrete," Fire Saf. J., vol. 42, no. 8, pp. 516–522, 2007.

23 B. Georgali and P. E. Tsakiridis, "Microstructure of fire damaged concrete. A case study," Cement Concr. Compos., vol. 27, pp. 255–259, 2005.
-2424 G. A. Khoury, "Effect of fire on concrete and concrete structures," Prog. Struct. Eng. Mater., vol. 2, no. 4, 2000.]. At 350 ºC, calcium hydroxide starts to decompose into lime and water [1818 Q. Ma, R. Guo, Z. Zhao, Z. Lin, and K. He, "Mechanical properties of concrete at high temperature—A review," Constr. Build. Mater., vol. 93, pp. 371–383, 2015.]. From 400 ºC, Portlandite crystals start to dehydroxylate, contributing to shrinkage and microcracks in the cement paste [1717 B. Fernandes, A. M. Gil, F. L. Bolina, and B. F. Tutikian, "Microstructure of concrete subjected to elevated temperatures: Physico-chemical changes and analysis techniques," IBRACON Struct. Mater. J., vol. 10, no. 4, pp. 838–863, 2017.], [2323 B. Georgali and P. E. Tsakiridis, "Microstructure of fire damaged concrete. A case study," Cement Concr. Compos., vol. 27, pp. 255–259, 2005.]. Above 500 ºC, most changes in concrete are considered irreversible [2222 O. Arioz, "Effects of elevated temperatures on properties of concrete," Fire Saf. J., vol. 42, no. 8, pp. 516–522, 2007.].

Studies that use ultrasonic testing to assess the integrity of heated concrete usually limit their analysis to the ultrasonic pulse velocity (UPV) [44 S. K. Handoo, S. Agarwal, and S. K. Agarwal, "Physicochemical, mineralogical, and morphological characteristics of concrete exposed to elevated temperatures," Cement Concr. Res., vol. 32, pp. 1009–1018, 2002.], [2525 H. W. Chung, "Ultrasonic testing of concrete after exposure to high temperatures," NDT Int., vol. 18, no. 5, pp. 275–278, 1985.], [2626 D. S. Silva, “Propriedades mecânicas residuais após incêndio em concretos usados na construção civil na grande Florianópolis,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2009.]. However, Yamada et al. [2727 K. Yamada, H. Tsuchiya, and Y. Kosaka, "Quality evaluation of concrete exposed to high temperature by ultrasonic spectroscopy," J. Soc. Mater. Sci., vol. 38, no. 431, pp. 959–965, 1989.] stressed the importance of detailed waveform analysis. Therefore, they also evaluated the behavior of the maximum amplitude and the total energy of the ultrasonic signal in concretes heated up to 600 ºC. They verified that, in most cases, these parameters decrease as the temperature increases and reported that an accurate evaluation of their sensitivity to temperature changes is required. The authors are not aware of studies that assess the behavior of group velocity, accumulated energy, and time instants corresponding to percentages of the energy in heated concrete.

This work aims to assess the behavior and the sensitivity of the following ultrasonic parameters: pulse and group velocities, maximum amplitude, total energy, accumulated energy, and time instants corresponding to 25%, 50%, and 75% of the energy, in detecting changes due to thermal degradation of the concrete.

2 MATERIALS AND EXPERIMENTAL PROGRAM

In this section, the methodologies applied to the casting and curing of concrete specimens, the ultrasonic testing and the calculation of ultrasonic parameters, the compressive strength testing, and the statistical analysis of the data are presented.

2.1 Concrete mixture

A conventional concrete with a C25 strength class was used. It was produced with: Brazilian Portland cement CP II-Z-32, natural fine sand (sand 1), natural medium sand (sand 2), natural siliceous coarse aggregate, and water from the city of Florianópolis/SC main water supply. The particle size distribution and the physical characteristics of the sands and the coarse aggregate are presented in Figure 1 and Table 1, respectively. They were determined according to the Brazilian standard NBR 7211:2009 [2828 Associação Brasileira de Normas Técnicas, Agregados para concreto - Especificação NBR 7211 2009, 2009.]. The mix proportions and the characteristics of the concrete are presented in Table 2.

Figure 1
Particle size distribution (a) sands (logarithmic scale); (b) coarse aggregate.
Table 1
Physical characteristics of the sands and the coarse aggregate.
Table 2
Concrete mixture and characteristics.

2.2 Sample and specimens

The sample consisted of 47 cylindrical concrete specimens with 100 mm in diameter and 300 mm in length, as recommended by RILEM TC 129 MHT [2929 International Union of Laboratories and Experts in Construction Materials, Systems and structures, test methods for mechanical properties of concrete at high temperatures Rilem TC 129 MHT Part 3-9, 1995.] for concrete specimens exposed to high temperatures. They were cast and compacted according to the Brazilian standard NBR 5738:2015 [3030 Associação Brasileira de Normas Técnicas, Moldagem e cura de corpos de prova cilíndricos ou prismáticos de concreto NBR 5738 2015, 2015.]. During this process, type K thermocouples were inserted in the geometric centers of 5 specimens to measure their internal temperature throughout the preliminary heating tests.

After 24 hours of casting, the concrete specimens were demolded and stored in a humid chamber for 6 days, as recommended by RILEM TC 129 MHT [2929 International Union of Laboratories and Experts in Construction Materials, Systems and structures, test methods for mechanical properties of concrete at high temperatures Rilem TC 129 MHT Part 3-9, 1995.]. Following the curing period, they were exposed to the ambient temperature and humidity of the laboratory environment for another 56 days, to simulate a concrete aging process close to the real and to decrease the interference that late hydration reactions of cement could cause during the concrete heating process [3131 P. K. Mehta and P. J. M. Monteiro Concreto - estrutura, propriedades e materiais, 2nd ed. São Paulo: Ibracon, 2014.], [3232 Laboratoire Central des Ponts et Chaussées, Recommendations for preventing disorders due to Delayed Ettringite Formation. Descartes: Ifsttar, 2009. Accessed: Nov. 06, 2020. [Online]. Available: https://www.ifsttar.fr/fileadmin/user_upload/editions/ifsttar/guidetechnique/2018-GTI5.A-guidetechnique-Ifsttar.pdf
https://www.ifsttar.fr/fileadmin/user_up...
].

After 28 days of curing, 7 specimens were subjected to compressive strength tests and showed an average compressive strength of 29 MPa, with a standard deviation of 1.2 MPa. After 63 days of curing, the concrete specimens were divided into 6 groups and exposed to temperatures between 20 and 500 °C, as specified in Table 3. Once the specimens had cooled, they were subjected to the following tests: mass loss, ultrasound, and compressive strength, as presented in the flow chart illustrated in Figure 2.

Table 3
Number of specimens.
Figure 2
Tests sequence

2.3 Heating tests

A muffle furnace with internal dimensions of 460 mm × 610 mm × 590 mm, 12 kW power, and heating capacity up to 1340 °C was used. Preliminary heating tests were performed using one cylindrical concrete specimen (groups II to VI), with an inserted type K thermocouple, for each temperature level (100, 200, 300, 400, and 500 °C). They were heated at a rate of 10 °C/min to avoid internal stresses caused by the thermal gradient between the outer and inner parts of the concrete specimens.

During the preliminary heating tests, the internal temperature of the concrete specimens was measured by connecting the thermocouples to a data acquisition system. The obtained data allowed to determine the time required to achieve a homogeneous temperature throughout the specimens. The specimens heated up to 500 °C suffered an explosive spalling precluding the application of the ultrasonic test. Therefore, the following heating tests were performed up to 400 °C.

Groups II to V, composed of 7 concrete specimens each, were heated according to the heating cycles determined based on the preliminary tests, shown in Table 4. After the thermal treatment, the groups were cooled inside the muffle furnace, until they had reached 150 °C. Subsequently, they were exposed to the ambient temperature and humidity of the laboratory environment for, at least, 24 hours prior to the tests of mass loss, ultrasound, and compressive strength.

Table 4
Heating cycles.

2.4 Mass loss measurements

The mass loss of the specimens was determined by Equation 1. The specimens of Group I were weighed once, while the specimens of groups II to V were weighed before the heating tests and after the cooling process.

ML= [(mimf)/mf]. 100,(1)

where ML is the mass loss (%), mi is the mass of the concrete specimen before the heating test (g), and mf is the mass of the concrete specimen after the heating test and the cooling process (g).

2.5 Ultrasonic testing

The ultrasonic tests were conducted with two piezoelectric transducers, a source, and a receiver of 20 mm diameter, coupled to the opposite faces of the specimen in a direct transmission arrangement. They excite longitudinal (P) waves with a frequency band of 200 kHz. The electric impulses generated by the ultrasonic instrument had a pulse amplitude of 500 V and a pulse width of 2.5 μs. The signal response was sampled with a sampling rate of 2 MHz and a recording time window of 5 ms.

Before starting the tests, the specimens of groups I to V were prepared according to the Brazilian standard NBR 8802:2019 [3333 Associação Brasileira de Normas Técnicas, Concreto endurecido – Determinação da velocidade de propagação de onda ultrassônica NBR 8802 2015, 2019.]. Subsequently, the ultrasonic instrument was calibrated through the coupling of the transducers to the calibration rod, using a coupling gel between the surfaces. Twenty measurements were performed for each specimen, to ensure sufficient data and to reduce the variability in the results. Based on the average of the data signals obtained for each specimen, the following parameters were analyzed: pulse and group velocities, maximum amplitude, total energy, accumulated energy, and time instants corresponding to 25%, 50%, and 75% of the energy (Figure 3).

Figure 3
Parameters of a representative ultrasonic wave.

2.5.1 Ultrasonic parameters

The pulse velocity and the maximum amplitude parameters were obtained directly from the ultrasonic signal data, while the group velocity, the total energy, the accumulated energy, and the time instants corresponding to percentages of energy were calculated. The group velocity of the waveforms was calculated using Equation 2, according to Washer et al. [3434 G. A. Washer, R. E. Green, and R. B. Pond, "Velocity constants for ultrasonic stress measurement in prestressing tendons," Res. Nondestruct. Eval., vol. 14, pp. 81–94, 2002.]. The distance between the transducers, which is the specimen length (300 mm), and the transit time for the maximum amplitude of the waveform were considered [1212 J. M. Carelli, “Análise do comportamento de ondas ultrassônicas em elementos fissurados de concreto e argamassa,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2014.], [1313 M. A. Hofmann, “Atenuação da energia do sinal ultrassônico na detecção de danos por fissuração no concreto,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2015.].

Vg=L/tam,(2)

where Vg is the group velocity (m/s), L is the distance between the two transducers (m), and tam is the transit time for the maximum amplitude of the waveform (s).

The total energy of the waveform was calculated by the module of the area under the signal [66 T. Shiotani and D. G. Aggelis, "Wave propagation in cementitious material containing artificial distributed damage," Mater. Struct., vol. 42, pp. 377–384, 2009.], [1010 F. C. Souza and R. C. A. Pinto, “Ultrasonic investigation on the effectiveness of crack repair in concrete,” Rev. IBRACON Estrut. Mater., vol. 13, no. 5, 2020.], as shown in Equation 3.

E = t 0 t i A t d t , (3)

where E is the total energy (V.ms), A(t) is the amplitude of the signal at time t (V), t is the time (ms), t0 is the starting time of the first wave group (ms), and ti is the time corresponding to the end of the first wave group (ms).

The accumulated energy of the waveforms, within the time window of 5 ms, was calculated as the sum of percentages of the energy at intervals of 0.5 μs [66 T. Shiotani and D. G. Aggelis, "Wave propagation in cementitious material containing artificial distributed damage," Mater. Struct., vol. 42, pp. 377–384, 2009.]. The slope of the curves was calculated by Equation 4. A range of 0.1% to 50% of the energy was considered.

m= y2y1/x2x1,(4)

where m is the slope of the curve, y2 is 50% of the energy (%), y1 is 0.1% of the energy (%), x2 is the time corresponding to 50% of the energy (ms), and x1 is the time corresponding to 0.1% of the energy (ms).

The time instants corresponding to 25%, 50%, and 75% of the energy were obtained by verifying the time that these percentages of energy occurred.

2.6 Compressive strength measurements

After the ultrasonic tests, the specimens of groups I to V were tested with at least 63 days old, according to the Brazilian standard NBR 5739:2018 [3535 Associação Brasileira de Normas Técnicas, Concreto – Ensaio de compressão de corpos de prova cilíndricos NBR 5739 2018, 2018.]. The compressive strength of the concrete was calculated by Equation 5.

σ = F m a x / A , (5)

where σ is the compressive strength of concrete (MPa), Fmax is the maximum force applied to the specimen during the test (N), and A is the cross-section area of the specimen (mm2).

After obtaining the concrete average compressive strength, the characteristic compressive strength of Group I (20 °C) was calculated according to the Brazilian standard NBR 12655:2015 [3636 Associação Brasileira de Normas Técnicas, Concreto de cimento Portland — Preparo, controle, recebimento e aceitação — Procedimento NBR 12655 2015, 2015.]. Then, the reduction coefficients of the compressive strength were calculated by Equation 6.

kc,θ= fc,θ/fck,(6)

where kc,θ is the reduction coefficient of the concrete compressive strength, fc,θ is the compressive strength (MPa) at temperature θ (°C), and fck is the characteristic compressive strength (MPa) at ambient temperature.

2.7 Statistical analysis methods

The influence of temperature on the mass loss, ultrasonic and compressive strength data was statistically analyzed, using a software package. Firstly, the occurrence of outliers was verified, and these data were eliminated [3737 R. M. Bethea and R. R. Rhinehart, Applied engineering statistics, 1st ed. New York: Marcel Dekker, 1991.]. Subsequently, the Kolmogorov-Smirnov normality test was performed, at 5% significance [3838 D. C. Montgomery and G. C. Runger, Applied statistics and probability for engineers, 3rd ed. New York: Wiley, 2003.]. For data normality, the analysis of variance test (ANOVA) and Tukey’s tests were performed at 5% probability of error [3838 D. C. Montgomery and G. C. Runger, Applied statistics and probability for engineers, 3rd ed. New York: Wiley, 2003.]. When the assumption of normality was violated, Kruskal-Wallis and multiple comparisons tests were performed at 5% probability of error [3838 D. C. Montgomery and G. C. Runger, Applied statistics and probability for engineers, 3rd ed. New York: Wiley, 2003.].

3 RESULTS AND DISCUSSIONS

In this section, the following results are presented and discussed: mass loss, residual compressive strength, ultrasonic pulse velocity (UPV), group velocity, maximum amplitude, total energy, accumulated energy, and time instants corresponding to 25%, 50%, and 75% of the energy.

3.1 Mass loss

The mass losses of the concrete specimens due to thermal treatment are illustrated in Figure 4. Groups II to V present an average mass loss of 1%, 6%, 7%, and 7%, respectively. The Tukey test revealed statistically significant differences among group means, except between the following groups: I and II (20-100 ºC), III and IV (200-300 ºC), III and V (200-400 ºC), IV and V (300-400 ºC).

Figure 4
Mass losses of the concrete specimens.

The mass loss increases non-linearly as the temperature increases. Similar results were obtained by Malik [3939 M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Microstructural changes in concrete: Postfire scenario," J. Mater. Civ. Eng., vol. 33, no. 2, 2021.] and Silva [4040 D. S. Silva, “Propriedades mecânicas residuais após incêndio em concretos usados na construção civil na grande Florianópolis,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2009.], which analyzed concretes with a compressive strength between 40 and 50 MPa. The data show that, up to 100 °C, the average mass loss is 1%, since at this temperature the water starts to change its phase from liquid to gaseous [1919 R. C. A. Lima, L. F. Caetano, and L. S. Filho, "Microstructural changes in high density concretes exposed to high temperatures," IBRACON Mater. J., vol. 10, no. 1, pp. 7–14, 2005.]. At 200 °C, the average mass loss is more significant, corresponding to 6%, since the physically adsorbed and free waters have already completely evaporated and the chemically bound water starts to be released [1818 Q. Ma, R. Guo, Z. Zhao, Z. Lin, and K. He, "Mechanical properties of concrete at high temperature—A review," Constr. Build. Mater., vol. 93, pp. 371–383, 2015.], [1919 R. C. A. Lima, L. F. Caetano, and L. S. Filho, "Microstructural changes in high density concretes exposed to high temperatures," IBRACON Mater. J., vol. 10, no. 1, pp. 7–14, 2005.], [3939 M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Microstructural changes in concrete: Postfire scenario," J. Mater. Civ. Eng., vol. 33, no. 2, 2021.]. Also, the CSH gel starts to dissociate and, consequently, the cement paste porosity increases [2121 M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Thermal and mechanical properties of concrete and its constituents at elevated temperatures: A review," Constr. Build. Mater., vol. 270, pp. 121398, 2021.]. At 300 °C, all types of water start to evaporate, and the mass loss is 7%.

Regarding the mass loss measurement, the thermal treatment caused changes in the mass of concrete specimens. The results indicate that the concrete porosity increases, and the chemical compounds were decomposed. These alterations change the compressive strength and the ultrasonic waveform of the concrete. However, a thermogravimetric analysis might be done to verify the chemical changes due to the mass loss.

3.2 Compressive strength of the concrete

The compressive strengths of the concrete specimens are illustrated in Figure 5. Groups I to V exhibit an average compressive strength and a coefficient of variation of 35 (15%), 28 (17%), 27.5 (15%), 28 (5%), and 24 (6.5%) MPa, respectively. The Tukey test revealed statistically significant differences between the following groups: I and II (20- 100 °C), I and III (20-200 °C), I and IV (20-300 °C), I and V (20-400 °C), indicating that the thermal treatment affects the compressive strength of the concrete.

Figure 5
Compressive strength of the concrete specimens.

The data show that the compressive strength decreases as the temperature increases, as observed by Handoo et al. [44 S. K. Handoo, S. Agarwal, and S. K. Agarwal, "Physicochemical, mineralogical, and morphological characteristics of concrete exposed to elevated temperatures," Cement Concr. Res., vol. 32, pp. 1009–1018, 2002.], Silva [4040 D. S. Silva, “Propriedades mecânicas residuais após incêndio em concretos usados na construção civil na grande Florianópolis,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2009.], and Ergün et al. [4141 A. Ergün, G. Kürklü, B. M. Serhat, and M. Y. Mansour, "The effect of cement dosage on mechanical properties of concrete exposed to high temperatures," Fire Saf. J., vol. 55, pp. 160–167, 2013.]. This behavior results from the evaporation of all types of water present in the concrete, the dissociation of the CSH gel, the dehydroxylation of the Portlandite, the shrinkage of the cement paste, and the thermal incompatibility between the cement paste and the aggregates [1717 B. Fernandes, A. M. Gil, F. L. Bolina, and B. F. Tutikian, "Microstructure of concrete subjected to elevated temperatures: Physico-chemical changes and analysis techniques," IBRACON Struct. Mater. J., vol. 10, no. 4, pp. 838–863, 2017.

18 Q. Ma, R. Guo, Z. Zhao, Z. Lin, and K. He, "Mechanical properties of concrete at high temperature—A review," Constr. Build. Mater., vol. 93, pp. 371–383, 2015.

19 R. C. A. Lima, L. F. Caetano, and L. S. Filho, "Microstructural changes in high density concretes exposed to high temperatures," IBRACON Mater. J., vol. 10, no. 1, pp. 7–14, 2005.

20 M. Castellote, C. Alonso, C. Andrade, X. Turrillas, and J. Campo, "Composition and microstructural changes of cement pastes upon heating, as studied by neutron diffraction," Cement Concr. Res., vol. 34, pp. 1633–1644, 2004.

21 M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Thermal and mechanical properties of concrete and its constituents at elevated temperatures: A review," Constr. Build. Mater., vol. 270, pp. 121398, 2021.

22 O. Arioz, "Effects of elevated temperatures on properties of concrete," Fire Saf. J., vol. 42, no. 8, pp. 516–522, 2007.
-2323 B. Georgali and P. E. Tsakiridis, "Microstructure of fire damaged concrete. A case study," Cement Concr. Compos., vol. 27, pp. 255–259, 2005.]. At 400 °C, the compressive strength reduces 30%, due to the chemical transformations of the cement paste, the breakup of some siliceous aggregates, and the presence of cracks in the transition zone [1717 B. Fernandes, A. M. Gil, F. L. Bolina, and B. F. Tutikian, "Microstructure of concrete subjected to elevated temperatures: Physico-chemical changes and analysis techniques," IBRACON Struct. Mater. J., vol. 10, no. 4, pp. 838–863, 2017.], [1818 Q. Ma, R. Guo, Z. Zhao, Z. Lin, and K. He, "Mechanical properties of concrete at high temperature—A review," Constr. Build. Mater., vol. 93, pp. 371–383, 2015.].

The reduction coefficients of the compressive strength of thermally treated concrete are shown in Table 5. Between 100 and 300 °C, the reduction coefficients of concrete specimens decrease more expressively, when compared to the reduction coefficients of Brazilian standard NBR 15200:2014 [4242 Associação Brasileira de Normas Técnicas, Projeto de estruturas de concreto em situação de incêndio NBR 15200 2012, 2012.]. These differences are probably related to several choices used in this research, especially the rate of heating, the time of exposure to heat, and the cooling process since these factors lead to concrete degradation.

Table 5
The reduction coefficients of the compressive strength of concrete.

3.3 Ultrasonic waveforms

The ultrasonic waveforms on a single concrete specimen of each group (I to V), in a time window of 1.5 ms, are illustrated in Figure 6. The specimen of group I (20 °C) exhibits higher amplitudes when compared to those of groups II to V (100, 200, 300, and 400 °C). As the temperature increases, the delay increases, and the amplitudes decrease. This behavior is evident from 300 °C. The observed changes on the waveforms are related to the signal attenuation caused by the presence of microcracks and by the increase in the concrete porosity, due to heating [99 T. P. Phillipidis and D. G. Aggelis, "Experimental study of wave dispersion and attenuation in concrete," Ultrasonics, vol. 43, pp. 584–595, 2005.]. Carelli [1212 J. M. Carelli, “Análise do comportamento de ondas ultrassônicas em elementos fissurados de concreto e argamassa,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2014.] and Hofmann [1313 M. A. Hofmann, “Atenuação da energia do sinal ultrassônico na detecção de danos por fissuração no concreto,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2015.] identified a similar behavior when comparing reinforced concrete beams before and after the presence of cracks.

Figure 6
Ultrasonic waveform between 20 °C and 400 °C.

3.4 Average pulse velocities

The average pulse velocities are illustrated in Figure 7. Groups I to V have an average pulse velocity and a coefficient of variation of 4464 (1.1%), 4299 (1.8%), 3835 (1.0%), 3427 (2.8%), and 2872 (2.5%) m/s, respectively. The Tukey test revealed statistically significant differences among group means.

Figure 7
Average pulse velocities.

The data show that the average pulse velocity decreases linearly as the temperature increases. An average decrease of 4% (100 °C), 14% (200 °C), 23% (300 °C), and 36% (400 °C) is observed. Similar results were obtained by Handoo et al. [44 S. K. Handoo, S. Agarwal, and S. K. Agarwal, "Physicochemical, mineralogical, and morphological characteristics of concrete exposed to elevated temperatures," Cement Concr. Res., vol. 32, pp. 1009–1018, 2002.], which analyzed cubic concrete specimens heated for 5 hours. They verified that the average pulse velocity of the concrete group heated at 400 ºC decreased 33% compared to the average obtained for the unheated group. This is an expected behavior, since high temperatures cause physicochemical changes in the concrete, such as water evaporation, the dehydration of chemical compounds, and the thermal incompatibility between the cement paste and the aggregates [1717 B. Fernandes, A. M. Gil, F. L. Bolina, and B. F. Tutikian, "Microstructure of concrete subjected to elevated temperatures: Physico-chemical changes and analysis techniques," IBRACON Struct. Mater. J., vol. 10, no. 4, pp. 838–863, 2017.

18 Q. Ma, R. Guo, Z. Zhao, Z. Lin, and K. He, "Mechanical properties of concrete at high temperature—A review," Constr. Build. Mater., vol. 93, pp. 371–383, 2015.

19 R. C. A. Lima, L. F. Caetano, and L. S. Filho, "Microstructural changes in high density concretes exposed to high temperatures," IBRACON Mater. J., vol. 10, no. 1, pp. 7–14, 2005.

20 M. Castellote, C. Alonso, C. Andrade, X. Turrillas, and J. Campo, "Composition and microstructural changes of cement pastes upon heating, as studied by neutron diffraction," Cement Concr. Res., vol. 34, pp. 1633–1644, 2004.

21 M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Thermal and mechanical properties of concrete and its constituents at elevated temperatures: A review," Constr. Build. Mater., vol. 270, pp. 121398, 2021.

22 O. Arioz, "Effects of elevated temperatures on properties of concrete," Fire Saf. J., vol. 42, no. 8, pp. 516–522, 2007.
-2323 B. Georgali and P. E. Tsakiridis, "Microstructure of fire damaged concrete. A case study," Cement Concr. Compos., vol. 27, pp. 255–259, 2005.], [4343 I. Hager, "Behavior of cement concrete at high temperature," Bull. Pol. Acad. Sci., vol. 61, no. 1, 2013.-4444 S. A. Hassan, "Effect of high elevated temperatures on the compressive strength and ultrasonic pulse velocity of high strength concrete," J. Eng. Dev., vol. 11, no. 1, pp. 58–69, 2007.]. These cause mass changes, as observed by the mass loss results, also porosity and microcracks, which increase the time to the first detectable disturbance of the wave, consequently, the UPV values decrease [4545 J. H. Bungey, S. G. Millard, and M. G. Grantham, Testing of concrete in structures, 4th ed. New York: Taylor & Francis, 2006.].

3.5 Average group velocities

The average group velocities are illustrated in Figure 8. After the elimination of outliers [3737 R. M. Bethea and R. R. Rhinehart, Applied engineering statistics, 1st ed. New York: Marcel Dekker, 1991.], groups I to V present an average group velocity and a coefficient of variation of 2320 (19%), 1854 (8%), 1444 (21%), 1826 (37%), and 1025 (38%) m/s, respectively. The Tukey test revealed statistically significant differences between the following groups: I and III (20-200 °C), I and V (20-400 °C), II and V (100-400 °C), IV and V (300-400 °C). Therefore, the group velocity can capture the changes undergone by the thermally treated concrete specimens.

Figure 8
Average group velocities.

The data show that the average group velocity decreases as the temperature increases. However, the average of Group IV (300 °C) is higher than the average obtained for Group III (200 °C). Also, this parameter decreases significantly in the presence of damage when compared to pulse velocity, as evidenced by the reductions of 20% (100 °C), 38% (200 °C), 21% (300 °C), and 56% (400 °C). Similar results were reported by Carelli [1212 J. M. Carelli, “Análise do comportamento de ondas ultrassônicas em elementos fissurados de concreto e argamassa,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2014.] and Shiotani and Aggelis [66 T. Shiotani and D. G. Aggelis, "Wave propagation in cementitious material containing artificial distributed damage," Mater. Struct., vol. 42, pp. 377–384, 2009.], which analyzed concrete and mortar specimens with artificially induced cracks and cubic mortar specimens containing artificial damage, respectively.

The data also show significant dispersions like those obtained by Camara [1515 R. M. Camara, “Estudo do efeito da variação de pressão de acoplamento no comportamento dos parâmetros ultrassônicos,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2017.] when analyzing cubic concrete specimens, with and without non-homogeneities. This behavior is probably due to the dependence of the group velocity on the time corresponding to the maximum amplitude of the waveforms, which can vary among concrete specimens due to their heterogeneity [1212 J. M. Carelli, “Análise do comportamento de ondas ultrassônicas em elementos fissurados de concreto e argamassa,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2014.], [1515 R. M. Camara, “Estudo do efeito da variação de pressão de acoplamento no comportamento dos parâmetros ultrassônicos,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2017.]. Further studies are required to assess the behavior of group velocity in thermally degraded concrete, evaluating different approaches for its calculation.

3.6 Average maximum amplitudes

The average of the maximum amplitudes of the waveforms are illustrated in Figure 9. After the elimination of outliers [3737 R. M. Bethea and R. R. Rhinehart, Applied engineering statistics, 1st ed. New York: Marcel Dekker, 1991.], groups I to V show an average maximum amplitude and a coefficient of variation of 500 (0%), 273 (20%), 319 (14%), 139 (14%), and 80 (28%) V, respectively. The multiple comparisons test revealed statistically significant differences among group means, denoting that the maximum amplitude can capture the changes undergone by concrete specimens heated up to 400 °C.

Figure 9
Average maximum amplitudes.

The unheated concrete specimens show waveforms with greater maximum amplitudes. At 100 °C, the average maximum amplitude decreases around 45% and a relative minimum of 176 V is verified. This result is probably associated with the greater porosity of this concrete specimen [4545 J. H. Bungey, S. G. Millard, and M. G. Grantham, Testing of concrete in structures, 4th ed. New York: Taylor & Francis, 2006.]. At 200 °C, the average maximum amplitude reduces only 36% when compared to the unheated group. At 300 and 400 °C, there is an even more significant decrease in the maximum amplitude due to the intensive attenuation of the signal. Yamada et al. [2727 K. Yamada, H. Tsuchiya, and Y. Kosaka, "Quality evaluation of concrete exposed to high temperature by ultrasonic spectroscopy," J. Soc. Mater. Sci., vol. 38, no. 431, pp. 959–965, 1989.] observed similar behavior in concrete specimens with a water/cement ratio of 0.7 heated up to 600 °C.

The heating up to 100 ºC causes the evaporation of free water and the increase of cement paste porosity, which decreases the maximum amplitude of the waveform. Above 100 ºC, the loss of free water in the pores, the decomposition of ettringite and the dissociation of CSH gel, contribute to increasing the concentration of calcite [2020 M. Castellote, C. Alonso, C. Andrade, X. Turrillas, and J. Campo, "Composition and microstructural changes of cement pastes upon heating, as studied by neutron diffraction," Cement Concr. Res., vol. 34, pp. 1633–1644, 2004.-2121 M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Thermal and mechanical properties of concrete and its constituents at elevated temperatures: A review," Constr. Build. Mater., vol. 270, pp. 121398, 2021.]. Ngala and Page [4646 V. T. Ngala and C. L. Page, "Effects of carbonatation on pore structure and diffusional properties of hydrated cement pastes," Cement Concr. Res., vol. 27, no. 7, pp. 995–1007, 1997.] and Shi et al. [4747 C. Shi, Y. Li, J. Zhang, W. Li, L. Chong, and Z. Xie, "Performance enhancement of recycled concrete aggregate," J. Clean. Prod., vol. 112, pp. 466–472, 2016.] states that calcite fills the pores and the voids of cement paste. Therefore, this reaction is probably responsible for the amplitude recovery at 200 ºC. Between 300 and 400 ºC, the chemically bound and capillary waters have already evaporated, increasing the porosity [1919 R. C. A. Lima, L. F. Caetano, and L. S. Filho, "Microstructural changes in high density concretes exposed to high temperatures," IBRACON Mater. J., vol. 10, no. 1, pp. 7–14, 2005.]. Also, the thermal incompatibility between the cement paste and the aggregate increases the number of microcracks in the transition zone [1717 B. Fernandes, A. M. Gil, F. L. Bolina, and B. F. Tutikian, "Microstructure of concrete subjected to elevated temperatures: Physico-chemical changes and analysis techniques," IBRACON Struct. Mater. J., vol. 10, no. 4, pp. 838–863, 2017.-1818 Q. Ma, R. Guo, Z. Zhao, Z. Lin, and K. He, "Mechanical properties of concrete at high temperature—A review," Constr. Build. Mater., vol. 93, pp. 371–383, 2015.]. Consequently, the maximum amplitude of the waveform continues to decrease.

3.7 Average total energies

The average total energies of the waveforms are illustrated in Figure 10. After the elimination of outliers [3737 R. M. Bethea and R. R. Rhinehart, Applied engineering statistics, 1st ed. New York: Marcel Dekker, 1991.], groups I to V show an average total energy and a coefficient of variation of 61 (4%), 29 (4%), 42 (11%), 25 (13%), and 15 (6%) V·ms, respectively. The Tukey test revealed statistically significant differences among group means, except between groups II and IV (100-300 °C). This demonstrates that the total energy can capture the changes undergone by the thermally treated concrete.

Figure 10
Average total energies.

The data show that the average total energy decreases linearly as the temperature increases, except for Group II (100 ºC), which presents a relative minimum. This behavior is like the one presented by the average maximum amplitude, since the energy is related to the amplitudes of the waveform, as observed in Equation 3.

An average decrease of 52% (100 °C), 31% (200 °C), 59% (300 °C), and 75% (400 °C) is observed when compared to the average at 20 ºC. Yamada et al. [2727 K. Yamada, H. Tsuchiya, and Y. Kosaka, "Quality evaluation of concrete exposed to high temperature by ultrasonic spectroscopy," J. Soc. Mater. Sci., vol. 38, no. 431, pp. 959–965, 1989.] reported similar results when analyzing concrete prisms with water/cement ratios of 0.5, 0.6, and 0.7 heated up to 600 °C. According to Anugonda et al. [88 P. Anugonda, J. S. Wiehn, and J. A. Turner, "Diffusion of ultrasound in concrete," Ultrasonics, vol. 39, pp. 429–435, 2001.], the loss of energy is due to the combination of scattering and dissipation of the ultrasonic waves, which was observed in Figure 6. In thermally treated concrete, the energy is absorbed by microcracks, and voids developed due to high temperatures [1717 B. Fernandes, A. M. Gil, F. L. Bolina, and B. F. Tutikian, "Microstructure of concrete subjected to elevated temperatures: Physico-chemical changes and analysis techniques," IBRACON Struct. Mater. J., vol. 10, no. 4, pp. 838–863, 2017.], [4848 D. G. Aggelis and T. Shiotani, "Effect of inhomogeneity parameters on wave propagation in cementitious material," ACI Mater. J., vol. 105, no. 2, pp. 187–193, 2008.].

3.8 Average accumulated energies

The average accumulated energies of waveforms are illustrated in Figure 11. The transmitted energy reduces gradually as the temperature increases. The average slopes of the curves decrease 3% (100 °C), 39% (200 °C), 55% (300 °C), and 65% (400 °C). The curves of groups I (20 °C) and II (100 °C) show similar behavior. However, the groups heated above 100 °C show low-sloped curves. Also, at 0.25 ms, Group I reach 50% of the energy, while groups II to V reach 48%, 34%, 23%, and 13% of the energy, respectively. Therefore, accumulated energy can capture the changes undergone by concrete specimens heated up to 400 °C.

Figure 11
Average accumulated energies of the waveforms.

At the beginning of the time window, groups without or with small damage show greater amplitudes, as observed in Figure 6. As the damage increases, the amplitude of the waveforms reduces since the energy accumulates more gradually over time. Consequently, the slopes of the curves are lower [1212 J. M. Carelli, “Análise do comportamento de ondas ultrassônicas em elementos fissurados de concreto e argamassa,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2014.]. Similar results were reported by Santhanam [55 M. Santhanam, "Ultrasonic characterization of damage in concrete," Tech Sci. Press, vol. 3, no. 2, pp. 111–125, 2010.] and Shiotani and Aggelis [66 T. Shiotani and D. G. Aggelis, "Wave propagation in cementitious material containing artificial distributed damage," Mater. Struct., vol. 42, pp. 377–384, 2009.] when analyzing cubic concrete specimens subjected to different load levels and cubic mortar specimens containing artificial damage.

3.9 Average time instants corresponding to 25%, 50%, and 75% of the energy

The average time instants corresponding to 25%, 50%, and 75% of the energy waveforms are illustrated in Figure 12. The time instants corresponding to percentages of the energy increases monotonically as the temperature increases. The Tukey test revealed statistically significant differences among group means, except between groups I and II (20-100 °C). Therefore, the time corresponding to percentages of the energy can capture the changes undergone by the thermally treated concrete specimens.

Figure 12
Averages time instants corresponding to percentages of the energy.

The average time instants to reach those energy levels increase significantly above 100 °C. They increase 3% between 20 and 100 ºC and 45%, 79% and 132% between the room temperature and 200, 300 and 400 °C, respectively. This is caused by signal attenuation, due to the presence of microcracks and voids in the thermally treated concrete specimens [4545 J. H. Bungey, S. G. Millard, and M. G. Grantham, Testing of concrete in structures, 4th ed. New York: Taylor & Francis, 2006.]. This behavior was also reported by Hofmann [1313 M. A. Hofmann, “Atenuação da energia do sinal ultrassônico na detecção de danos por fissuração no concreto,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2015.] and Silva [1414 P. M. Silva, “Análise da perda de rigidez em vigas de concreto armado devido à fissuração por esforços de flexão utilizando ensaio de ultrassom,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2017.] when analyzing reinforced concrete beams before and after the appearance of cracks.

3.10 Ultrasonic parameters sensitivity

To evaluate the sensitivity of the ultrasonic parameters to temperature changes, they were normalized from the values obtained at room temperature, as shown in Table 6. All parameters are sensitive to temperatures changes. The pulse and group velocities, the maximum amplitude, the total energy, and the slope of the accumulated energy curve decrease as the temperature increases, while the time instants corresponding to percentages of the energy increase.

Table 6
Normalized ultrasonic parameters.

The attenuation parameters change more significantly in the presence of thermal damage when compared to pulse velocity, especially the time instants corresponding to percentages of the energy and the maximum amplitude, since these parameters consider the information from the ultrasonic waveform in the entire time window [55 M. Santhanam, "Ultrasonic characterization of damage in concrete," Tech Sci. Press, vol. 3, no. 2, pp. 111–125, 2010.], while pulse velocity is measured by the first detectable disturbance of the wave [66 T. Shiotani and D. G. Aggelis, "Wave propagation in cementitious material containing artificial distributed damage," Mater. Struct., vol. 42, pp. 377–384, 2009.]. According to Aggelis and Shiotani [4848 D. G. Aggelis and T. Shiotani, "Effect of inhomogeneity parameters on wave propagation in cementitious material," ACI Mater. J., vol. 105, no. 2, pp. 187–193, 2008.], even though the wave energy scattering affects the amplitudes, some energy remains scattered in the forward direction. This explains why non-homogeneities, have a limited influence on the pulse velocity, when compared to the attenuation parameters.

The pulse velocity, the slope of the accumulated energy curves and the time instants corresponding to percentages of the energy show a characteristic behavior. The group velocity increases at 300 °C, probably, due to its dependence on the time corresponding to the maximum amplitude, which varies between concrete specimens. The total energy and the maximum amplitude increase at 200 °C, probably due to the presence of calcite [2020 M. Castellote, C. Alonso, C. Andrade, X. Turrillas, and J. Campo, "Composition and microstructural changes of cement pastes upon heating, as studied by neutron diffraction," Cement Concr. Res., vol. 34, pp. 1633–1644, 2004.]. Further research should be undertaken to investigate these topics.

Regarding the ultrasonic parameters, the pulse velocity is the least sensitive parameter, followed by the group velocity, which shows significant dispersions. The slope of the accumulated energy curve, the maximum amplitude and the total energy detects the thermal damage, since the first decreases monotonically as the temperature increases, while the second and the third are very sensitive to thermal damage. However, the time instants corresponding to 25%, 50%, and 75% of the energy are the most sensitive parameters, denoting that they can be the best indicator of thermally damaged concrete. Despite these promising results, further studies are recommended before field applications.

4 CONCLUSIONS

In this research, the behavior of pulse and group velocities, maximum amplitude, total energy, accumulated energy, and time instants corresponding to percentages of the energy were analyzed in concrete groups heated at five temperature levels in a range of 20 to 400 ºC. The sample consisted of 39 cylindrical concrete specimens measuring 100 mm in diameter and 300 mm in length, distributed into five groups, with an average compressive strength of 29 MPa at room temperature. The results lead to the following conclusions:

  • the pulse velocity decreases as the temperature increases, however, it is the least sensitive parameter;

  • the group velocity is more sensitive than pulse velocity, but shows significant dispersions;

  • the maximum amplitude and the total energy are very sensitive to thermal damage, but further studies must be done to investigate the increase of these parameters at 200 °C;

  • the slope of the accumulated energy curve is sensitive to changes in heated concrete since it decreases as the temperature increases;

  • the time instants corresponding to 25%, 50%, and 75% of the energy are the most sensitive parameters in detecting changes due to thermal degradation of the concrete.

ACKNOWLEDGEMENTS

The authors thank the Coordination for the Improvement of Higher Education Personnel (CAPES) for sponsoring this research.

  • Financial support: Coordination for the Improvement of Higher Education Personnel (CAPES).
  • Data Availability: The data that support the findings of this study are available from the corresponding author, ACCV, upon reasonable request.

CITATIONS

  • 1
    International Atomic Energy Agency, Guidebook on non-destructive testing of concrete structures Vienna: IAEA, 2002.
  • 2
    T. R. Naik, V. M. Malhotra, and J. S. Popovics, Nondestructive testing of concrete, 2nd ed. Florida: CRC, 2004.
  • 3
    S. A. Kumar and M. Santhanam, “Detection of concrete damage using ultrasonic pulse velocity method,” in Proc. National Seminar on Non-Destructive Evaluation, 2006.
  • 4
    S. K. Handoo, S. Agarwal, and S. K. Agarwal, "Physicochemical, mineralogical, and morphological characteristics of concrete exposed to elevated temperatures," Cement Concr. Res., vol. 32, pp. 1009–1018, 2002.
  • 5
    M. Santhanam, "Ultrasonic characterization of damage in concrete," Tech Sci. Press, vol. 3, no. 2, pp. 111–125, 2010.
  • 6
    T. Shiotani and D. G. Aggelis, "Wave propagation in cementitious material containing artificial distributed damage," Mater. Struct., vol. 42, pp. 377–384, 2009.
  • 7
    A. V. Hauwaert, J. F. Thimus, and F. Delannay, "Use of ultrasonics to follow crack growth," Ultrasonics, vol. 36, pp. 209–217, 1998.
  • 8
    P. Anugonda, J. S. Wiehn, and J. A. Turner, "Diffusion of ultrasound in concrete," Ultrasonics, vol. 39, pp. 429–435, 2001.
  • 9
    T. P. Phillipidis and D. G. Aggelis, "Experimental study of wave dispersion and attenuation in concrete," Ultrasonics, vol. 43, pp. 584–595, 2005.
  • 10
    F. C. Souza and R. C. A. Pinto, “Ultrasonic investigation on the effectiveness of crack repair in concrete,” Rev. IBRACON Estrut. Mater., vol. 13, no. 5, 2020.
  • 11
    F. Moradi-Marani, P. Rivard, C. P. Lamarche, and S. A. Kodjo, “Evaluating the damage in reinforced concrete slabs under bending test with the energy of ultrasonic waves,” Constr. Build. Mater., vol. 73, pp. 663–673, 2014.
  • 12
    J. M. Carelli, “Análise do comportamento de ondas ultrassônicas em elementos fissurados de concreto e argamassa,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2014.
  • 13
    M. A. Hofmann, “Atenuação da energia do sinal ultrassônico na detecção de danos por fissuração no concreto,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2015.
  • 14
    P. M. Silva, “Análise da perda de rigidez em vigas de concreto armado devido à fissuração por esforços de flexão utilizando ensaio de ultrassom,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2017.
  • 15
    R. M. Camara, “Estudo do efeito da variação de pressão de acoplamento no comportamento dos parâmetros ultrassônicos,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2017.
  • 16
    D. G. Aggelis, T. Shiotani, and D. Polyzos, "Characterization of surface crack depth and repair evaluation using Rayleigh waves," Cement Concr. Compos., vol. 31, pp. 77–83, 2009.
  • 17
    B. Fernandes, A. M. Gil, F. L. Bolina, and B. F. Tutikian, "Microstructure of concrete subjected to elevated temperatures: Physico-chemical changes and analysis techniques," IBRACON Struct. Mater. J., vol. 10, no. 4, pp. 838–863, 2017.
  • 18
    Q. Ma, R. Guo, Z. Zhao, Z. Lin, and K. He, "Mechanical properties of concrete at high temperature—A review," Constr. Build. Mater., vol. 93, pp. 371–383, 2015.
  • 19
    R. C. A. Lima, L. F. Caetano, and L. S. Filho, "Microstructural changes in high density concretes exposed to high temperatures," IBRACON Mater. J., vol. 10, no. 1, pp. 7–14, 2005.
  • 20
    M. Castellote, C. Alonso, C. Andrade, X. Turrillas, and J. Campo, "Composition and microstructural changes of cement pastes upon heating, as studied by neutron diffraction," Cement Concr. Res., vol. 34, pp. 1633–1644, 2004.
  • 21
    M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Thermal and mechanical properties of concrete and its constituents at elevated temperatures: A review," Constr. Build. Mater., vol. 270, pp. 121398, 2021.
  • 22
    O. Arioz, "Effects of elevated temperatures on properties of concrete," Fire Saf. J., vol. 42, no. 8, pp. 516–522, 2007.
  • 23
    B. Georgali and P. E. Tsakiridis, "Microstructure of fire damaged concrete. A case study," Cement Concr. Compos., vol. 27, pp. 255–259, 2005.
  • 24
    G. A. Khoury, "Effect of fire on concrete and concrete structures," Prog. Struct. Eng. Mater., vol. 2, no. 4, 2000.
  • 25
    H. W. Chung, "Ultrasonic testing of concrete after exposure to high temperatures," NDT Int., vol. 18, no. 5, pp. 275–278, 1985.
  • 26
    D. S. Silva, “Propriedades mecânicas residuais após incêndio em concretos usados na construção civil na grande Florianópolis,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2009.
  • 27
    K. Yamada, H. Tsuchiya, and Y. Kosaka, "Quality evaluation of concrete exposed to high temperature by ultrasonic spectroscopy," J. Soc. Mater. Sci., vol. 38, no. 431, pp. 959–965, 1989.
  • 28
    Associação Brasileira de Normas Técnicas, Agregados para concreto - Especificação NBR 7211 2009, 2009.
  • 29
    International Union of Laboratories and Experts in Construction Materials, Systems and structures, test methods for mechanical properties of concrete at high temperatures Rilem TC 129 MHT Part 3-9, 1995.
  • 30
    Associação Brasileira de Normas Técnicas, Moldagem e cura de corpos de prova cilíndricos ou prismáticos de concreto NBR 5738 2015, 2015.
  • 31
    P. K. Mehta and P. J. M. Monteiro Concreto - estrutura, propriedades e materiais, 2nd ed. São Paulo: Ibracon, 2014.
  • 32
    Laboratoire Central des Ponts et Chaussées, Recommendations for preventing disorders due to Delayed Ettringite Formation Descartes: Ifsttar, 2009. Accessed: Nov. 06, 2020. [Online]. Available: https://www.ifsttar.fr/fileadmin/user_upload/editions/ifsttar/guidetechnique/2018-GTI5.A-guidetechnique-Ifsttar.pdf
    » https://www.ifsttar.fr/fileadmin/user_upload/editions/ifsttar/guidetechnique/2018-GTI5.A-guidetechnique-Ifsttar.pdf
  • 33
    Associação Brasileira de Normas Técnicas, Concreto endurecido – Determinação da velocidade de propagação de onda ultrassônica NBR 8802 2015, 2019.
  • 34
    G. A. Washer, R. E. Green, and R. B. Pond, "Velocity constants for ultrasonic stress measurement in prestressing tendons," Res. Nondestruct. Eval., vol. 14, pp. 81–94, 2002.
  • 35
    Associação Brasileira de Normas Técnicas, Concreto – Ensaio de compressão de corpos de prova cilíndricos NBR 5739 2018, 2018.
  • 36
    Associação Brasileira de Normas Técnicas, Concreto de cimento Portland — Preparo, controle, recebimento e aceitação — Procedimento NBR 12655 2015, 2015.
  • 37
    R. M. Bethea and R. R. Rhinehart, Applied engineering statistics, 1st ed. New York: Marcel Dekker, 1991.
  • 38
    D. C. Montgomery and G. C. Runger, Applied statistics and probability for engineers, 3rd ed. New York: Wiley, 2003.
  • 39
    M. Malik, S. K. Bhattacharyya, and S. V. Barai, "Microstructural changes in concrete: Postfire scenario," J. Mater. Civ. Eng., vol. 33, no. 2, 2021.
  • 40
    D. S. Silva, “Propriedades mecânicas residuais após incêndio em concretos usados na construção civil na grande Florianópolis,” M.S. thesis, Universidade Federal de Santa Catarina, Florianópolis, 2009.
  • 41
    A. Ergün, G. Kürklü, B. M. Serhat, and M. Y. Mansour, "The effect of cement dosage on mechanical properties of concrete exposed to high temperatures," Fire Saf. J., vol. 55, pp. 160–167, 2013.
  • 42
    Associação Brasileira de Normas Técnicas, Projeto de estruturas de concreto em situação de incêndio NBR 15200 2012, 2012.
  • 43
    I. Hager, "Behavior of cement concrete at high temperature," Bull. Pol. Acad. Sci., vol. 61, no. 1, 2013.
  • 44
    S. A. Hassan, "Effect of high elevated temperatures on the compressive strength and ultrasonic pulse velocity of high strength concrete," J. Eng. Dev., vol. 11, no. 1, pp. 58–69, 2007.
  • 45
    J. H. Bungey, S. G. Millard, and M. G. Grantham, Testing of concrete in structures, 4th ed. New York: Taylor & Francis, 2006.
  • 46
    V. T. Ngala and C. L. Page, "Effects of carbonatation on pore structure and diffusional properties of hydrated cement pastes," Cement Concr. Res., vol. 27, no. 7, pp. 995–1007, 1997.
  • 47
    C. Shi, Y. Li, J. Zhang, W. Li, L. Chong, and Z. Xie, "Performance enhancement of recycled concrete aggregate," J. Clean. Prod., vol. 112, pp. 466–472, 2016.
  • 48
    D. G. Aggelis and T. Shiotani, "Effect of inhomogeneity parameters on wave propagation in cementitious material," ACI Mater. J., vol. 105, no. 2, pp. 187–193, 2008.

Edited by

Editors: Lia Pimentel, Guilherme Aris Parsekian.

Publication Dates

  • Publication in this collection
    01 Nov 2021
  • Date of issue
    2022

History

  • Received
    06 Nov 2020
  • Accepted
    21 Sept 2021
IBRACON - Instituto Brasileiro do Concreto Instituto Brasileiro do Concreto (IBRACON), Av. Queiroz Filho, nº 1700 sala 407/408 Torre D, Villa Lobos Office Park, CEP 05319-000, São Paulo, SP - Brasil, Tel. (55 11) 3735-0202, Fax: (55 11) 3733-2190 - São Paulo - SP - Brazil
E-mail: arlene@ibracon.org.br