Acessibilidade / Reportar erro

Fire design of composite ribbed slabs

Abstracts

The Brazilian standards of structures in fire prescribe minimum dimensions for the ribbed slabs to ensure fire resistance. However, a new composite ribbed slab is not covered by any of the Brazilian standards in fire. The objective of this work is to present unpublished results from numerical and thermal analyses for this type of slab. Ribbed slabs filled with cell concrete blocks, ceramic bricks and EPS supported by cimentitious board were studied. The constructive element is considerate as thermal insulation if it has the capacity to prevent the occurrence, on the face non exposed to fire, temperature increments greater than 140 ºC on the average or greater than 180 ºC at any point. The support function was determined limiting the temperature of the beams and slabs rebars to 500 ºC. The analyses were carried out with the ATERM and Super Tempcalc, software for two-dimensional thermal analysis by means of the finite element method. As a result, tables will be presented that link the fire resistance required time to slab dimensions and position of rebar. Prior to use in designing these results must be confirmed by experimental analysis, which is already being provided.

fire; thermal analysis; ribbed slabs; waffled slabs; composite slabs


As normas brasileiras de estruturas em situação de incêndio fornecem dimensões mínimas para as lajes nervuradas para assegurar as funções corta fogo e de estabilidade estrutural. Porém, uma nova laje mista nervurada lançada no mercado brasileiro não é coberta por qualquerdas normas brasileiras para a situação de incêndio. O objetivo deste trabalho é apresentar resultados inéditos, frutos de análises numéricastérmicas e estruturais para esse tipo de laje. Foram estudadas lajes com preenchimento de bloco de concreto celular, lajota cerâmica e EPSsuportado por placa cimentícia. O sistema construtivo é considerado como isolante térmico se possuir a capacidade de impedir a ocorrência,na face que não está exposta ao incêndio, de incrementos de temperatura maiores que 140 ºC na média dos pontos de medida ou maioresque 180 ºC em qualquer ponto de medida. A função estrutural foi determinada admitindo a limitação da temperatura das armaduras de vigas elajes em 500 ºC. As análises foram realizadas com auxílio dos programas ATERM e Super Tempcalc, programas computacionais para análisetérmica bidimensional de transferência de calor, por meio do método dos elementos finitos. Como resultado, serão apresentadas tabelas quecorrelacionarão o TRRF (tempo requerido de resistência ao fogo) às dimensões da laje e posição das armaduras. Antes do uso em projeto,esses resultados deverão ser confirmados por análise experimental.

incêndio; análise térmica; laje nervurada; laje mista


Fire design of composite ribbed slabs

I. Pierin; V. P. Silva

Escola Politécnica da Universidade de São Paulo, São Paulo, SP, Brasil. igorpierin@usp.br, valpigss@usp.br

ABSTRACT

The Brazilian standards of structures in fire prescribe minimum dimensions for the ribbed slabs to ensure fire resistance. However, a new composite ribbed slab is not covered by any of the Brazilian standards in fire. The objective of this work is to present unpublished results from numerical and thermal analyses for this type of slab. Ribbed slabs filled with cell concrete blocks, ceramic bricks and EPS supported by cimentitious board were studied. The constructive element is considerate as thermal insulation if it has the capacity to prevent the occurrence, on the face non exposed to fire, temperature increments greater than 140 ºC on the average or greater than 180 ºC at any point. The support function was determined limiting the temperature of the beams and slabs rebars to 500 ºC. The analyses were carried out with the ATERM and Super Tempcalc, software for two-dimensional thermal analysis by means of the finite element method. As a result, tables will be presented that link the fire resistance required time to slab dimensions and position of rebar. Prior to use in designing these results must be confirmed by experimental analysis, which is already being provided.

Keywords: fire, thermal analysis, ribbed slabs, waffled slabs, composite slabs.

1. Introduction

ABNT NBR 14323:2013 Brazilian standard [1] presents recommendations for steel and concrete composite slabs in a fire situation. ABNT NBR 6118:2007 [2] defines the ribbed slabs and prescribes minimum dimensions for the rib section to waive the verification of flange bending. ABNT NBR 15200:2012 [3] provides minimum dimensions, by means of tables, to ensure fire resistance.

A new kind of steel and concrete composite slab has been released in the market. It is a ribbed slab, manufactured by Tuper, the steel formwork (Figure 1) of which is placed at the base of the rib (Figure 2), working as a formwork and a bottom reinforcement.



Due to the characteristics of this ribbed composite slab, none of the aforementioned standards covers its design in fire situation. This work aims to investigate the behavior of these ribbed slabs at high temperatures, in order to analyze their thermal insulation, according to the procedure recommended by ABNT NBR 5628:2001 [4] and a fire resistance, based on the 500 ºC limit temperature in the reinforcement [5], [6].

The slabs under study are filled with either ceramic tiles (Figure 3), cellular concrete blocks (Figure 4) or EPS on cementitious plates (Figure 5). This study assumes the perfect contact between the filler and the rib wall; hence, all the results should be experimentally confirmed. The advantage of performing a numerical analysis is that the behavior of a large number of alternatives can be previously foreseen, lowering the waste with experimental tests.




2. Parameters adopted for the thermal analysis of slabs

2.1 Thermal action

The fire model used in the analysis was the standard fire (ISO-fire) (Equation 1)). According to [4] and [7], the coefficient of heat transfer by convection, αc, was taken equal to 25 W/m2 ºC on the faces heated directly by the fire and the resulting emissivity εres, 0.7.

On the face not exposed to direct heat, a combination of convection and radiation was made, simulated by αc = 9 W/m2 ºC. In Equation 1, θg is the gas temperature expressed in degrees Celsius (ºC), θ, o is the room temperature equal to 20 ºC and t is time in min.

2.2 Properties of materials

2.2.1 Concrete

In the thermal analysis of structures, knowledge of thermal properties such as density, thermal conductivity and specific heat is needed. These values vary with temperature and, for concrete, the formulation presented in ABNT NBR 15200:2012 [3] was adopted, and the density at room temperature was equal to 2400 kg/m3, as recommended by ABNT NBR 6118: 2007 [2]. The humidity adopted was equal to 1.5% by weight.

2.2.2 Steel

Properties were adopted as recommended by ABNT NBR 14323:2013 [1] and also presented in [6].

2.2.3 Ceramic tile

For ceramic tiles, there is no consensus on the values to be adopted for the properties needed for thermal analysis. Table 1 shows the values of the thermal properties taken from the literature. Where no tests are available, ABNT NBR 15220-2:2005 [8] indicates the properties of the ceramic tiles at room temperature, also shown in Table 1.

The thermal conductivity of the regular concrete decreases with temperature; thus, if it is supposed that the same occurs with the ceramic tile, the conductivity value at room temperature can be considered in favor of safety. Therefore, the highest thermal conductivity (1.05 W/m ºC) and the lowest capacitance (density × specific heat = 1000 kg/m3 × 835 J/kg ºC= 835000 J/m3 ºC) will be used.

2.2.4 Cellular concrete block

Also, for cellular concrete blocks, there is no consensus on the values to be adopted for their properties in thermal analysis. Table 2 shows the physical and thermal properties provided by some manufacturers and by the literature.

The thermal conductivity of the regular concrete decreases with temperature; hence, if it is supposed that the same occurs with the cellular concrete, the conductivity value at room temperature can be considered in favor of safety. Therefore, the highest thermal conductivity (0.3 W/m ºC) and the lowest capacitance (density × specific heat = 300 kg/m3 × 850 J/kg ºC= 255000 J/m3 ºC) will be used.

2.2.5 Cementitious plate

After extensive research on the physical and thermal properties of cement plates, few results were found, with great variability between them, as shown in Table 3.

Due to the high deviation of values, a study was carried out to verify the influence of the thermal properties on the slab temperature field.

According to the thermal properties presented in this item, seven simulations were performed, in which the properties of the cementitious plates were varied, as shown in Table 4. In the sixth simulation, thermal properties of concrete were adopted for the cementitious plate. In the seventh simulation, the presence of the cementitious plate was disregarded, i.e., the side faces of the rib and the lower face of the flange were directly exposed to fire.

To check the influence of the physical and thermal properties on the slab temperature field, the temperature variation was analyzed at three points, as shown in Figure 6: point A - rib upper left corner, point B -midpoint of the upper concrete face (flange) and point C - steel plate.


By means of Super Tempcalc thermal analysis software [19], the graphs showing the temperature variation versus fire exposure time for points A, B and C were plotted. See Figures 7 and 8.



As can be seen in Figures 7 and 8, the protection provided by the cementitious plate is, despite its small thickness, not negligible when compared to simulation # 7 (no cementitious plate). On the other hand, the physical-thermal properties, simulations # 1 to 6, do not profoundly affect the results. For this being a numeric study and the wide variability found in the values of the plate properties, we decided to admit the properties of simulation # 1 in favor of safety.

3. Analyses of slabs with ceramic tile

3.1 Type 12-4 slab

Making use of Super Tempcalc thermal analysis software [19], the thermal behavior of a ribbed concrete slab filled with ceramic tile was analyzed. Initially, the following were considered (see Figure 3): thickness of the flange equal to 4 cm, rib height from the flange equal to 8 cm, rib width equal to 10 cm, 8.0 cm high ceramic tile and 1.95 mm thick metal joist. The holes of the ceramic tile were supposed to be filled with air. The temperature fields were analyzed for 30, 60, 90, 120, 150 and 180 minutes of exposure to standard fire. As an example, Figures 9 and 10 show the thermal field and isotherms, respectively, for 60 minutes.



3.2 Other flange or flange+lining thicknesses

In order to evaluate the thermal insulation provided by the ceramic tile, the concrete flange thickness was varied from 4 to 8 cm. Since the thermal and physical properties of cement and sand mortar are similar to those of concrete, the thickness of the flange used in computer models may be substituted, in practice, by the actual flange thickness plus one layer of cement and sand mortar. The rib height with no flange was maintained equal to 8 cm. The maximum and average temperatures obtained on the slab upper surface for 4, 5, 6, 7 and 8 cm flange thicknesses are presented in Tables 5 and 6. Table 7 was constructed from Tables 5 and 6 associating the flange thickness to the time of fire resistance for thermal insulation. Table 8 presents the distances between the lower face of the rib and the lowest (d1) and the highest (d2) points of the isotherm of 500 ºC and the minimum distance between the isotherm of 500 ºC and the top of the steel recess (d3), as shown in Figure 11.


For fire resistance higher than 120 minutes, the 500 ºC isotherm crosses the flange. The reinforcement should be placed in the flange and in the middle of the rib, which is not feasible. From the analyses performed, Table 9 is proposed. Values were rounded in view of the difficulty of attaining millimeter precision in the construction work.

It is observed that the values of c1 in Table 9 are considered high. However, for structural purposes, they can be compensated by increasing the rib height. This will in no way affect the results found herein.

4. Analyses of slab with cellular concrete blocks

4.1 Type 12-4 slab

The analysis of the thermal behavior of ribbed concrete slab filled with cellular concrete blocks was performed. Initially, the following was considered (see Figure 3): concrete slab thickness equal to 4 cm, height of the concrete block equal to 8 cm, width of the beam equal to 10 cm and metal joist thickness equal to 1.95 mm. Due to the slab continuity, only one rib was modeled, with flange collaborating width equal to 30 cm. By means of ATERM program [20], the thermal analysis of the slab was performed for 30, 60, 90, 120, 150 and 180 min. As an example, the field of temperature and isotherms for 60 min of standard fire is presented in Figures 12 and 13.



Table 10 shows the maximum and average temperatures obtained on the upper surface for times equal to 30-180 min of exposure to fire. Average temperatures on the rib area of the upper face are also shown. The temperature variation along the upper face for periods of 30 to 180 minutes is shown in Figure 14, where the shaded area indicates the rib region. The highest temperatures are observed to occur in this region. The ribbed slab under study with 4 cm flange and filled with 8 cm high cellular concrete blocks is found to meet the requirements of thermal insulation for fire resistance up to 120 min.


4.2 Other thicknesses of flange or flange+linings

For a better evaluation of the slab thermal insulation, a concrete flange thickness of 5 cm was adopted. Thermal analysis was redone and it was found that, as shown in Table 10, the slab studied meets the requirements for thermal insulation for fire resistance up to 150 min. Further analysis performed for a thickness of 6 cm proved that the condition of thermal insulation is met for fire resistance up to 180 min, as shown in Table 10.

For using the simplified method of 500 ºC limit temperature in reinforcement, Table 11 presents the distance between the underside of the rib and the lowest point (d1) and the highest point (d2) of the 500 ºC isotherm and the minimum distance between the 500 ºC isotherm and the top of the steel recess (d3), for the slab with 4 cm flange, as shown in Figure 15.


From the study performed, one can infer that safety is obtained if the bars centroid keep a distance from the rib underside face greater than 2.4 cm. For 60 min of fire resistance, this rises to 2.8 cm. For fire resistance higher than 90 min, the values found are not of practical use. Thus, the next analysis will cover blocks of greater height.

Type 16-4, 20-4, and 25-4 slabs were also analyzed, which corresponds to 4 cm thick flange and 16, 20 and 25 cm rib + flange height (respectively, 12, 16 and 21 cm high blocks). Table 12 shows the maximum and average temperatures obtained on the slab upper face, for times equal to 30-180 minutes of exposure to fire. Average temperatures on the rib area of the upper face are also shown.

Table 13 presents the distances between the rib lower face and the lowest (d1) and highest (d2) points of the 500 ºC isotherm as well as the minimum distance between the 500 ºC isotherm and the top of the steel recess (d3), as shown in Figure 15. Based on Table 13, one can build Table 14, related to thermal insulation.

By observing Table 13, the values of d1 are verified to be quite the same, i.e. slightly dependent on the rib height. Thus, the minimum values of c1, the distance from the reinforcement CG to the rib base shown in Table 15 are proposed. The values were rounded due to the difficulty in obtaining millimeter precision in the field.

It is observed that the values of c1 from Table 15, considered high for structural purposes, can be compensated by increasing the rib height. This in no way affects the results herein.

5. Analyses of slabs with EPS blocks on a cementitious plate

5.2 Type 12-4 slab

Analyses were made on the thermal behavior of ribbed concrete slab filled with EPS block resting on cementitious plate, employing Super Tempcalc [19] software. The presence of EPS was disregarded due to the fact that this material is quickly consumed by the heat. Initially, the following was considered (see Figure 5): thickness of the concrete slab equal to 4 cm, rib height from the flange equal to 8 cm, rib width equal to 10 cm, cementitious plate thickness equal to 6.0 mm and thickness of the metal joist equal to 1.95 mm. The temperature fields were analyzed for 30, 60, 90, 120, 150 and 180 minutes of exposure to standard fire. As examples, Figures 16 and 17 show, respectively, the thermal field and isotherms for 60 minutes.



5.2 Other flange or flange+lining thicknesses

To evaluate the thermal insulation of the slab with cementitious plate, the thickness of the concrete flange was varied from 4 to 8 cm. Having in mind that the thermal and physical properties of cement and sand mortar are similar to those of concrete, the flange thickness used in computer models can be substituted, in practice, by the flange actual thickness plus one layer of cement and sand mortar. The rib height was supposed equal to 8 cm. The maximum and average temperatures on the upper surface of the slab, for thicknesses of 4, 5, 6, 7 and 8 cm, are presented in Tables 16 and 17. From Tables 16 and 17, Table 18 was constructed for thermal insulation. For information, the values standardized by ABNT NBR 15200:2012, for the case of lack of the cement plate, are provided.

Table 19 was built for use with the simplified method of 500 ºC limit temperature in the reinforcements and presents the distances between the rib lower face and the lowest (d1) and the highest (d2) points of isotherm 500 ºC and the minimum distance between 500 ºC isotherm and the top of the steel recess (d3), as shown in Figure 18.

For fire resistance higher than 120 min, the 500 ºC isotherm crosses the flange. The reinforcement should be placed in the flange and in the middle of the rib which is not feasible. Observing Table 8, Table 20 is proposed. Values were rounded in view of the difficulty in attaining millimeter precision in the field.

The values of c1 from Table 20 are considered high but, for structural purposes, can be compensated by increasing the rib height. This does not at all affect the results yielded in this work.

6. Comparisons to the brazilian standard

By comparing the filled slabs to the unfilled ones, they should follow the recommendations of ABNT NBR 15200:2012 [3]; Table 21 presents a summary of the results of this study and, in the last column, the requirements of the Brazilian standard fire resistance in function of the thermal insulation.

Table 22 presents a summary of the results of this study and, in the last column, the Brazilian requirements for minimum c1.

7. Conclusions

This paper examined ribbed composite slabs filled with ceramic tiles, cellular concrete blocks and EPS on cement plate at high temperature. Conditions of thermal insulation and resistant capacity were analyzed.

The presence of any of the 3 types of filler studied improves the performance of the slab in fire, increasing the fire resistance time and decreasing the value of c1minimum in relation to similar slabs with no filling. Based solely on thermo-structural numerical analysis, values of fire resistance time are proposed, as a function of thermal insulation capacity and c1, assuming the limit temperature at reinforcement equal to 500 ºC.

In view of the unprecedented nature of this research, and, especially, of the existence of the large space filled with heated air inside the holes of the ceramic tile and the vacuum caused by the burning of EPS, the results for thermal insulation and reinforcement position presented here should be experimentally confirmed before being used in design. Similarly, tightness warranty must be analyzed experimentally, since it has not been targeted in this study. The numerical procedure led to results that may be useful to guide future studies.

8. Acknowledgments

The authors thank FAPESP - Fundação de Amparo à Pesquisa do Estado de São Paulo/ São Paulo Research Foundation, to CNPq - Conselho Nacional de Desenvolvimento Científico e Tecnológico/ Brazilian National Council of Scientific and Technological Development and Tuper.

9. Bibliography

  • [01] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 14323: Projeto de estruturas de aço e estruturas mistas de ao e concreto em situação de incêndio - procedimento. Rio de Janeiro, 2013.
  • [02] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6118: Projeto de estruturas de concreto - procedimento. Rio de Janeiro, 2007.
  • [03] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 15200: Projeto de estruturas de concreto em situação de incêndio. Rio de Janeiro, 2012.
  • [04] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 5628: Componentes construtivos estruturais - determinação da resistência ao fogo. Rio de Janeiro, 2001.
  • [05] EUROPEAN COMMITTEE FOR STANDARDIZATION. EN 1991-2-2: Eurocode 1: actions on structures - part 1.2: general actions - actions on structures exposed to fire. Brussels: CEN, 2002.
  • [06] SILVA, V. P. Projeto de estruturas de concreto em situação de incêndio. São Paulo: Edgard Blücher, 2012.
  • [07] INTERNATIONAL ORGANIZATION FOR STANDARDIZATION. ISO 834: Fire-resistance tests: elements of building construction -part 1.1: general requirements for fire resistance testing. Geneva, 1999. 25 p. (Revision of first edition ISO 834:1975).
  • [08] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 15220-2: Desempenho térmico de edificações Parte 2: Método de cálculo da transmitância térmica, da capacidade térmica, do atraso térmico e do fator solar de elementos e componentes de edificações. Rio de Janeiro. 2005.
  • [09] CADORIN, J. F. Compartment Fire Models for Structural Engineering, PhD Thesis, Faculté de Sciences Appliqués, Université de Liège. 2003.
  • [10] INCROPERA. F. P.; DEWITT, D. P. Introduction to heat transfer. 901 p. Wiley. 2002.
  • [11] SIPOREX. Available in <http://www.siporex.com.br/> Access in: 14/8/2012.
    » link
  • [12] COSTRUPOR. Disponível em <http://www.construpor.com.br/index.php?p=item2-1> Acesso em: 14/8/2012.
    » link
  • [13] SUPERBLOCO (Sical). Disponível em <http://www.superbloco.com.br/main/bloco_sical.php> Acesso em: 14/8/2012.
    » link
  • [14] BARREIRA, E.; FREITAS, V. P. Evaluation of building materials using infrared thermography. Construction and Building Materials. Volume 21-1 , p. 218-224. January 2007.
  • [15] GAWIN, D. J.; KOSNY, J. WILKES, K. Thermal Conductivity of Moist Cellular Concrete Experimental and Numerical Study. American Society of Heating, Refrigerating and Air-Conditioning Engineers - ASHRAE. 2004.
  • [16] KNAUF. Disponível em <www.knauf.com.br> Acesso em: 14/8/2012.
    » link
  • [17] BRASILIT. Disponível em <www.brasilit.com.br> Acesso em: 14/8/2012.
    » link
  • [16] ETERNIT. Disponível em <www.eternit.com.br> Acesso em: 14/8/2012.
    » link
  • [19] FIRE SAFETY DESIGN (FSD). TCD 5.0 User's manual. Lund: Fire Safety Design AB, 2007.
  • [20] PIERIN; I. A instabilidade de perfis formados a frio em situação de incêndio. Tese de Doutorado. Escola Politécnica. Universidade de São Paulo. 2011.

Publication Dates

  • Publication in this collection
    22 Apr 2014
  • Date of issue
    Apr 2014

History

  • Accepted
    20 Feb 2014
  • Received
    11 Dec 2013
IBRACON - Instituto Brasileiro do Concreto Instituto Brasileiro do Concreto (IBRACON), Av. Queiroz Filho, nº 1700 sala 407/408 Torre D, Villa Lobos Office Park, CEP 05319-000, São Paulo, SP - Brasil, Tel. (55 11) 3735-0202, Fax: (55 11) 3733-2190 - São Paulo - SP - Brazil
E-mail: arlene@ibracon.org.br