ABSTRACT
The production of wind energy has grown significantly in recent years, and this trend is expected to persist. Intermittent climate variability, as well as the connectivity of wind power generating systems with the grid, cause power quality challenges such as impoverished voltage regulation and harmonics. The power system’s performance is impacted while wind power is incorporated into the grid. Elevating the power quality is done with the Distribution Static Synchronous Compensator (DSTATCOM). In this article performance improvement of DSTATCOM is analysed using proposed Tunicate Swarm Algorithm (TSA) in grid connected wind energy system. Performance of proposed system is validated with the comparative analysis of particle swarm optimisation and conventional PI based DSTATCOM. In this article various algorithms such as TSA, PSO and conventional PI controller are employed to find reference current to study the performance of DSTATCOM. Performance of the system is analysed in terms of active power (P), reactive power (Q), DC link voltage (Vdc) and harmonics.
Keywords:
DSTATCOM; DFIG; WECS; Tunicate Swarm Algorithm; PSO
1. INTRODUCTION
These days, it is vital to look for renewable energy resources as alternative energy sources due to the steadily rising demand for electrical energy and the rapid depletion of conventional energy supplies. Since wind energy is clean, abundant, and can be harnessed for significant power output, it is considered as extremely crucial and promising renewable energy source. However, there are some drawbacks to wind energy as well. For example, its unpredictable nature makes it highly dependent on changes in the surrounding environment, like wind speed. As a result, the incorporation of wind energy into a wind hybrid producing power system can reduce individual variances, boost total output energy, and provide the electrical grid with more dependable, higher-quality power [1]. However, a number of issues regarding the dynamic performance of these systems during grid voltage sags and transient grid failures have been brought up by the growing ubiquity of grid-connected PV/wind hybrid power systems [2].
One of the most difficult tasks in recent times has been installing energy-efficient hybrid energy systems in rural places. In particular, these systems have made PQ problems more noticeable, therefore it is critical for researchers to choose the size and control strategy for this reliable and affordable alternative energy source as well they can [3]. The primary challenge for a hybrid system is grid integration because renewable energy sources fluctuate, which causes PQ problems [4, 5]. The simulation analyses of SPV grid-connected system covered in [6,7,8] show how to evaluate new technological issues related to STATCOM and PQ disturbances under dynamic load situations. In particular, the utility grid’s P and Q demand is decreased by variable Q supply. Using a sliding mode controller, the extreme power from the SPV system can be extracted in 3ms without overshooting and while ignoring PQ disturbances.
The numerical validations presented in [9, 10] reduce the total expenses of energy losses and spend on investments for proper sizing and optimum positioning of the D-STATCOM. It is worth noting that the performance of a STATCOM is determined not solely by the converters, but also by how they are regulated [11,12,13]. As a result, numerous control mechanisms have been used to manage this device. The most commonly utilized are Voltage- Oriented Control and Direct Power Control. A voltage-oriented control (VOC) technique is akin to FOC-based control in that it employs a double loop control architecture. In reference [14,15,16], authors used VOC, which necessitates control over the direct (d) and quadrature (q) current components transferred among the grid and the STATCOM. For this technique, the current is directed according to the d or q-axis, while the voltage is concerned with along the opposite axis that is orthogonal to the current axis, resulting in a dephasing that assures no active power transaction among the grid and the STATCOM. The VOC methodology integrates a direct current link voltage control loop with a current control loop utilizing a proportional-integral controller. Cascade control loop design methodologies have also been proposed for MPPT implementation in DFIG-based WECS to improve power extraction efficiency across varying wind profiles [17], reflecting the continued research interest in refining control strategies for DFIG-based systems, which forms the broader context for the DC-link voltage control approach proposed in this work. A comparison analysis is performed [18], demonstrating the advantages of genetic algorithms and bacteria foraging algorithms by decreasing voltage swings by 10% and 15%, respectively. In this comparison, the performance is evaluated in relation to proportional integral (PI) controllers. Presenting and analyzing fuzzy-PI controlled behaviour and fuzzy-Proportional Integral Derivative (PID) are done in the same line [19, 20].
Although PI, fuzzy-PI, GA, and BFA based control schemes have shown improvement in DSTATCOM performance, these approaches largely depend on manual tuning or gradient-based adjustment of controller gains, which makes them prone to slow convergence, sensitivity to initial parameter selection, and susceptibility to entrapment in local optima under rapidly varying wind and grid conditions. PSO, though widely applied for DC-link voltage regulation, similarly suffers from premature convergence and reduced search diversity in later iterations, limiting its ability to consistently track the optimal PI gains under dynamic disturbances. These limitations create a clear gap for a controller-tuning method that balances exploration and exploitation more effectively while remaining computationally simple. Recent metaheuristic-based approaches have also been explored for DSTATCOM optimization in renewable-energy-integrated distribution networks, including Gray Wolf Optimization based DSTATCOM sizing [21], Hippopotamus Optimization Algorithm based integration of DSTATCOM with EV charging stations and renewable sources [22], and other bio-inspired algorithms for DSTATCOM based power-quality improvement [23], further underscoring the growing relevance of swarm-based optimization for DSTATCOM performance enhancement.
This article proposes the TSA to achieve effective performance. TSA has been compared to well-known metaheuristic algorithms such as Spotted Hyena optimization, Grey Wolf optimization, Particle Swarm optimization (PSO), Multiverse optimization, Sine Cosine Algorithm, Gravitational Search Algorithm, Genetic Algorithm, Emperor Penguin optimization, and jSO, revealing that TSA outperformed all other algorithms [24].
PI and PSO controllers are selected as benchmarks in this study since PI represents the conventional industry-standard control practice widely adopted in DSTATCOM applications, while PSO is one of the most extensively used swarm-based optimization techniques for controller-gain tuning in power quality studies, thereby providing a fair and relevant baseline for evaluating the proposed TSA-based controller. Recently developed algorithms such as Grey Wolf Optimization, Sine Cosine Algorithm, and Multiverse Optimization, though promising, were not included in the present comparison to keep the scope of the study focused on demonstrating the improvement of TSA over the most commonly deployed conventional and swarm-based controllers; their evaluation is considered a direction for future work. Hence in this research TSA is proposed in D-STATCOM for DC link voltage control. It is validated with the comparison of PSO and PI controller-based D-STATCOM.
The main contributions of this work can be summarized as follows:
-
A Tunicate Swarm Algorithm based tuning approach is proposed for the DC-link voltage PI controller of a DSTATCOM operating in a grid-connected DFIG based WECS.
-
The performance of the TSA-tuned DSTATCOM is benchmarked against conventional PI and PSO-tuned DSTATCOM under a PCC voltage sag condition caused by wind speed variation.
-
The comparative improvement offered by TSA is quantified in terms of DC-link voltage drop, oscillation, and current THD, and is further explained from a control-theoretic standpoint.
2. DFIG WIND ENERGY SYSTEM
A DFIG-based configuration is adopted in this study over a Permanent Magnet Synchronous Generator (PMSG)-based WECS for several practical reasons. In a DFIG system, the power electronic converter (RSC-GSC) is rated only around 25–30% of the total generator capacity, since the stator is directly connected to the grid and only the rotor power is processed through the converter, unlike a PMSG-based system where a full-scale back-to-back converter rated at 100% of the generator capacity is required. This partial-scale converter arrangement makes DFIG-based WECS more cost-effective and results in lower converter losses. Furthermore, DFIG remains the most widely deployed wind turbine technology in existing utility-scale wind farms, making the study of DSTATCOM-based power quality enhancement in DFIG-based WECS directly relevant to the majority of grid-connected wind installations in service today. The direct grid connection of the DFIG stator also means that voltage and power quality disturbances at the point of common coupling (PCC) are more directly reflected in the machine’s terminal behaviour, making DFIG-based WECS a more demanding and representative test case for evaluating the effectiveness of the proposed DSTATCOM-based compensation scheme. While a PMSG-based WECS, with its full-scale converter, offers greater inherent controllability of grid-side behaviour, this also means the converter itself can partially mask the power quality benefits of an external compensator such as DSTATCOM, whereas the DFIG configuration more clearly demonstrates the standalone contribution of the proposed DSTATCOM-TSA scheme in mitigating grid voltage sag effects.
Advances in turbine blade aerodynamic design, such as novel airfoil profiles for improving small-scale wind turbine efficiency [25], further complement control-side improvements such as the one proposed in this work, together contributing to the overall performance of DFIG-based WECS.
The grid connected WECS using DFIG is exposed in Figure 1. A mechanical shaft system links the WT to the DFIG, which is made up of a minimal-speed turbine shaft associated with a fast speeds DFIG shaft by a gearbox. Figure 1 depicts the WECS, which is made up of a DFIG with stator windings that are directly coupled to the grid and rotor windings that are linked to the grid by couple of ac/dc consecutive converters.
The converters on both the rotor and grid sides are voltage-source converters controlled by pulse width modulation (PWM). Though the grid-side converter (GSC) preserves the DC bus voltage (Vdc), the rotor-side converter (RSC) frequently provides torque control in addition to terminal voltage or PF control. The consecutively power converter is utilised to provide dynamic control of the DFIG. A PID controller manages the converter function to maximise active and reactive power while sustaining grid voltage.
2.1. RSC control technique
The best way to regulate torque and stator Q when using DFIG’s RSC as the driving force is to use the vector control methods [26]. To optimise power from variable wind speed, the maximum power point tracking scheme is also incorporated into the RSC side control method. With the DFIG technology, a steady system voltage is ensured via the stator terminal’s direct connection to the grid. As a result, the stator’s flux remains constant. The torque generated can be adjusted by varying the iqr component of the rotor current. Reactive power of the stator can be independently controlled by varying the inductance component of the rotor current in line. Therefore, by choosing the proper flux phasor orientation, it is feasible to control the torque and Q of the stator by adjusting the rotor direct and quadrature axis currents.
2.2. GSC control technique
A PID controller adds the P to the DC-link current by contrasting the Vdc reference voltage to the Vdc real [27]. The d axis current Ids and the Idl are derived by converting the 3-phase stator and load current into their corresponding 2 phase d-q components. Since it does not consume grid reactive electricity, Idg, the d axis grid current, Iqg, is set to zero. The d-q component of the currents Idg and Iqg is transformed to the 3Ø reference grid current Igrid*. The regulated value of Iabc is obtained by subtracting Igrid* from the real grid current Igrid. This accounts for the harmonics caused by the non-linear load. In the GSC control technique, the Iabc is used as a reference space phasor vector for the PWM. The Hysteresis Current Control technique (HCC) makes use of feedback current control approaches. HCC employ the hysteresis band boundary to ascertain the PWM signals required by converters.
3. DSTATCOM
The DSTATCOM device, the subject of investigation in this study, is slated for placement adjacent to a grid-connected wind farm. Its function is to reduce grid disturbances and fluctuations and enhance the operational stability of wind turbines. Figure 2 illustrates the DSTATCOM and the model that corresponds to it.
By deploying Kirchhoff’s voltage law to the corresponding model of the DSTATCOM and disregarding the total shunt transformer resistance (Rsh), the following results are obtained:
The equation for the complex apparent power S– delivered by the DSTATCOM at the interface point is as follows:
where the conjugates of I, E, and V are, respectively, I*, E*, and V*. The expression (3) provides the complex apparent power S̲.
By applying Equations (2) and (3), the following can be deduced:
Not sharing active power with the grid (therefore, no losses) makes it possible to express the following:
It can be inferred that the DSTATCOM voltage and the PCC voltage should be in phase. Equation (7) describes the power q transferred amid the grid and DSTATCOM under these conditions.
It can infer that:
-
when V is greater than E and Q is negative, the DSTATCOM functions in form of capacitance
-
when V is lesser than E and Q is positive, the DSTATCOM functions in form of inductive.
-
when V is equal to E and Q is nil, the DSTATCOM is functioning empty.
Because the power P transferred amid the grid and DSTATCOM is kept constant at null, the current and voltage offered by the DSTATCOM are in quadrature. Equation (8) describes the probable voltage dips (ΔV = Er – E) in the line linking the grid bus system to the common connection point PCC (Figure 3).
In the case of a Very High Voltage grid where x is greater than 10 r, expression (8) can be reduced as follows: Equation (9).
Reactive power is the primary cause of voltage changes, as seen by expression (9). In the event that the PCC voltage falls below the nominal voltage, as indicated by ΔV = (Er − E) is positive value, the DSTATCOM employs Q to offset the voltage variance. The DSTATCOM is operating capacitively. The DSTATCOM operates inductively when the PCC voltage rises over the nominal voltage, represented by ΔV = (Er − E) < 0. This is accomplished by using Q to refund the voltage expansion. It can be stated the DSTATCOM to apply or consume Q by detecting the RMS PCC voltage. Therefore, the current consumed or implemented by the D STATCOM must be measured in order to ascertain its value of power. Because wind turbines produce variable amounts of active electricity by nature, voltage fluctuations often occur in the vicinity of the wind turbine connection point on the grid connection bus. To ensure quick and accurate voltage regulation, DSTATCOM deployment is encouraged close to wind farms [28].
3.1. Voltage oriented control of DSTATCOM
Measuring the PCC voltages (va, vb, vc) and DSTATCOM currents (ia, ib, ic) is the Voltage Oriented Control method. Then, in order to compare these variables with their references in the same frame, Idref and Iqref , they will be changed in the (d, q) reference frame. The DC voltage and the PCC voltage control loops, respectively, produce these two references. The current’s comparators’ faults will be fed into the PI regulators, which enable the generation of DSTATCOM control signals via an SVM block. Figure 3 provides a detailed presentation of the VOC principle.
VOC is a simple method of control requires only park and Clark transformations. Compare to other control methods it does not require any hysteresis controller, any additional unit for sector selection for inverter control. Along with this absence of calculating active and reactive power makes this method as very simple.
3.2. DC link voltage control
In order to provide optimal DSTATCOM performance, unaltered current waveforms must be obtained at a minimum of Vdc. The six power switches on the DSTATCOM need to be negatively biassed to all AC voltage supply levels in order to guarantee globally control. To secure the power switches, it is necessary to guarantee a Vdc that exceeds the maximum Vdc produced solely by the switchgear. Vdc error is processed by PI controller and produces Idref which is furtherly computed for SVM reference. Process of Vdc controller is shown in Equation (10).
Accuracy of Idref decides the control of VSC. Henceforth in this paper various optimisation algorithm such as particle swarm optimisation and Tunicate swarm algorithm are proposed to tune KP and Ki values of PI controller.
4. PARTICLE SWARM OPTIMIZATION
PSO is an evolutionary meta-heuristic computation practice that draws inspiration from the ways in which fish schools and flocks of birds cooperate to find food or avoid predators. The PSO is a technique for artificial intelligence that relies on self-organized, decentralised collective behaviour. The PSO methodology uses the population candidate solutions to identify the best possible solution for a given problem [19]. The optimality level is determined by a fitness function. The PSO approach is based on the idea that every particle searches D-dimensional space for the target. The optimum and perfect position will be instantly adopted by the other particles [29].
In order to accomplish their goal, each particle (xij), which is specified by its beginning velocity and position at random, attempts to explore the research space by repeatedly moving into test positions.
In this case, n is the swarm size, Pbest is the best prior position of the ith particle, ω is the factor of inertia weight, (C1 and C2) are the constants of acceleration, (r1 and r2) are arbitrary integers inside [0-1], and Gbest is the best entity in the whole population. Vij(t) symbolises the particle ith velocity with a j size at iteration t. In this study, a performance metric called the integral absolute error criterion (IAE) is used to minimise the fitness function. The IAE is defined by this expression:
The deviation with the reference input and the real output quantity is used to calculate the signal error, or e(t). The goal function is determined by the weighted total of errors. The IAE performance criterion is linked to the target function. Consequently, PSO algorithm is defined as follow:
-
Kp and Ki are the particles.
-
The swarm comprises of 10 particles.
-
Particles are arbitrarily initiated within 0 and 100.
-
The cost function is IAE.
-
The greatest number of cycles is fifty.
The conventional PSO is used, with the parameters w = 1 and c1 = c2 = 2. To prevent a local optimum and stagnation issue brought on by an established velocity step size, w is initially set to its standard value, w = 1, and is then progressively reduced (1% at every cycle).
5. TUNICATE SWARM ALGORITHM (TSA)
This section provides a detailed description of the suggested algorithm’s mathematical modelling and sources of inspiration.
5.1. Optimization method and mathematical model
Tunicate is able to pinpoint food reserves in the ocean. However, the source of food in the designated search space is uncertain. Two tunicate behaviors the optimal and secondary are used in this work to determine the food source (FS). Swarm intelligence and jet propulsion are these behaviours. A tunicate must meet three requirements in order to be mathematically modelled for jet propulsion behaviour: it must avoid disputes with other search agents (SA), travel in the direction of the best search agent (SAbest), and remain close to the most effective search agent. On the other hand, the swarm behaviour will adjust other search agents’ placements depend on the ideal answer.
Avoiding the disputes amid Sas: Vector ; is applied to estimate the new SA position in order to avert disputes amid search agents, or further tunicates.
But, represents the force of gravity, and illustrates the transpiration of water flow in the dark sea. The random numbers that make the parameters c1, c2, and g3 are between 0 and 1. The symbol representing the social dynamics between search agents is . Here’s how to determine the vector :
where the beginning and subsequent speeds of social contact are represented by Pmin and Pmax. The values of Pmin and Pmax are taken into consideration in this work as 1 and 4, correspondingly.
Movement towards the direction of best neighbour: The search agents go in the track of the best neighbour following evading neighbour conflicts.
where x denotes the current iteration, S is the FS’s position, or optimal, and is the distance, or tunicate, among the FS and the SA. The position of the tunicate is designated by the vector , where rand is an arbitrary value in the interval [0, 1].
Get closer to the best search agent: The SA can continue to move in the direction of the FS, or optimal search agent.
where is the tunicate’s updated position in relation to the location of the FS S.
Swarm behaviour: The pair of optimal solutions are retained, and the orderings of other SAs are adjusted conferring to the locations of the SAbest, in an effort to mathematically emulate the swarm behaviour of tunicates. The swarm behaviour of tunicates is defined by the subsequent formula:
Figure 4 illustrates the process by which search agents can adjust their placements based on the location of .
The tunicate’s location defines the final position, which would be at random inside a cylindrical or cone-shaped structure. Algorithm1 displays the pseudo code for the suggested TSA method. The following are some crucial details of the TSA algorithm:
-
A, , and help the solutions act erratically in a certain search space and are in charge of preventing disputes among various search agents.
-
Improvements in the stages of prospecting and exploiting could be achieved by adjusting vectors A, and .
-
The TSA algorithm’s collective behaviour is defined by the tunicate’s thrust and swarm behaviours within a certain search arena.
5.2. Procedure and flowchart of TSA
The proposed TSA’s stages and flowchart are listed below (shown Figure 5).
-
Phase I: Establish the population of tunicates, .
-
Phase II: Determine the starting parameters and the most iterations that can be made.
-
Phase III: Determine each SA’s fitness value.
-
Phase IV: The optimal SA is investigated in the specified search space after the fitness value has been calculated.
-
Phase V: Use Equation (20), update each SA’s position.
-
Phase VI: Modify the revised SA so that it covers more ground in the specified search arena.
-
Phase VII: Determine the current fitness value of the SA. Apprise if a better answer exists than the preceding best option.
-
Phase VIII: The procedure emanates to an end if the halting requirement is met. If not, revert and do Phases V through VIII.
-
Phase IX: Return the most optimised solution obtained thus far.
The TSA is configured with the same population size (10 search agents), search bounds (0–100 for Kp and Ki), and maximum number of iterations (50) as the PSO algorithm, to ensure a fair and consistent comparison between the two optimization techniques. The values of Pmin and Pmax used in the TSA formulation are set to 1 and 4, respectively, as detailed in Section 5.1.
In this analysis PI controller variables are the agent’s position for fitness function of Equation (13).
6. SIMULATION RESULTS AND ANALYSIS
6.1. Simulation parameters
Table 1 presents the system and simulation parameters used in the DFIG-DSTATCOM model, and Table 2 presents the controller configuration and corresponding performance results for the Conventional PI, PSO-tuned, and TSA-tuned cases.
Grid connected DFIG based WECS is analysed under fault at t = 1.5s – 2s. Fault creates a change in RMS voltage at PCC as shown in Figure 6.
Impact of DSTATCOM using conventional PI, PSO and proposed TSA are analysed for the above change in PCC voltage condition. Performance of PI controlled DSTATCOM for change in PCC voltage by change in wind speed is shown in Figure 7 in terms of P, Q, Vdc, Line Voltage (Vabc) and THD Current (THDI).
From the Figure 7(a) it is noted that active power of 54.75MW is maintained at same value even after small oscillation during change in PCC voltage. Reactive power is raised to 11.5232MVAR to compensate voltage fluctuation at PCC as shown in Figure 7(b). During drop in PCC voltage DC link voltage is oscillated about 8.5V and settled to 1149.84V as shown in Figure 7(c). Line voltage is slightly varied to 0.998 p.u. from 1 p.u. during 1.5s to 2s as shown in Figure 7(d). As presented in Figure 7(e) THD of current is 4.56%. Performance of PSO controlled DSTATCOM for change in PCC voltage by change in wind speed is shown in Figure 8.
From the Figure 8(a) it is noted that active power of 54.81MW is maintained at same value even after small oscillation during change in PCC voltage. Reactive power is raised to 11.5233MVAR to compensate voltage fluctuation at PCC as shown in Figure 8(b). During drop in PCC voltage DC link voltage is oscillated about 7.32V and settled to 1149.87V as shown in Figure 8(c). Line voltage is slightly varied to 0.9991 p.u. from 1 p.u. during 1.5s to 2s as shown in Figure 8(d). As presented in Figure 8(e) THD of current is 3.52%. Performance of TSA controlled DSTATCOM for change in PCC voltage by change in wind speed is shown in Figure 9.
Performance of proposed TSA controlled DSTATCOM. (a) P; (b) Q; (c) Vdc; (d) Vabc; (e) THDI.
From the Figure 9(a) it is noted that active power of 54.9MW is maintained at same value even after small oscillation during change in PCC voltage. Reactive power is raised to 11.5234MVAR to compensate voltage fluctuation at PCC as shown in Figure 9(b). During drop in PCC voltage DC link voltage is oscillated about 6.2V and settled to 1149.9V as shown in Figure 9(c). Line voltage is slightly varied to 0.9995 p.u. from 1 p.u. during 1.5s to 2s as shown in Figure 9(d). As presented in Figure 9(e) THD of current is 2.32%. Evaluation of all systems under consideration is shown in Table 3.
From the comparative performance Figure 10 and Table 3 it is observed that in period of drop in PCC voltage, drop in DC voltage is 0.16V, 0.13V and 0.1V by PI, PSO and proposed TSA controlled DSTATCOM system respectively. Oscillation in DC voltage at the moment of drop in PCC voltage by proposed TSA controlled DSTATCOM system is 6.2V which less compared to 8.5V, 7.32V by PI and PSO controlled DSTATCOM. Comparative harmonic performance of all analysed systems is shown in Table 4.
Comparative analysis of the performance of all examined controllers in DSTATCOM. (a) P; (b) Q; (c) Vdc.
From the comparative performance Table 4 it is observed that proposed TSA controlled DSTATCOM system offers minimum THD of 2.32%, while it is 3.52% and 4.56% by PSO and PI controlled DSTATCOM respectively.
As summarized in Table 5, the proposed TSA controlled DSTATCOM achieves a 37.5% and 23.1% reduction in DC-link voltage drop compared to the PI and PSO controlled systems, respectively. Similarly, the DC-link voltage oscillation during the disturbance is reduced by 27.1% and 15.3% compared to the PI and PSO controlled DSTATCOM, respectively. In terms of harmonic performance, the TSA controlled DSTATCOM offers a 49.1% and 34.1% reduction in THD compared to the PI and PSO controlled systems, respectively, confirming the superior performance of the proposed controller across all evaluated parameters.
The improved performance of the TSA-tuned controller can be attributed to the manner in which the PI gains (Kp, Ki) of the DC-link voltage loop are optimized. In the conventional PI controller, fixed gains obtained through manual tuning result in a control response that is not adapted to the dynamics of the system during a disturbance, leading to a larger initial swing in Idref and, consequently, higher oscillation in Vdc and increased current distortion. PSO improves upon this by iteratively searching for gain values that minimize the IAE criterion; however, its tendency toward premature convergence and reduced diversity among particles in later iterations restricts how closely the search settles near the true optimum, leaving a residual error in the tuned gains. TSA, through its combined jet-propulsion and swarm-based search behaviour, maintains a broader exploration of the Kp-Ki search space in the early iterations while converging more precisely toward the optimal gain values in later iterations. This translates directly into a faster and more accurately damped Idref response to the change in Vdc error following the PCC voltage sag, which in turn produces a smaller and more rapidly settling oscillation in the DC-link voltage. Since the harmonic content injected by the DSTATCOM is closely linked to how smoothly Idref tracks its reference during the transient, the reduced oscillation achieved by the TSA-tuned controller directly translates into the lower THD observed in Table 4, in contrast to the comparatively slower and less precisely damped response of the PI and PSO controlled systems.
While the present study evaluates the proposed TSA controlled DSTATCOM under a PCC voltage sag caused by a sudden wind speed variation, the underlying control mechanism is not restricted to this specific disturbance. Since the TSA is employed to tune the gains of the DC-link voltage PI loop rather than being designed for a particular fault type, the improved damping and faster settling response observed in this study are expected to extend to other operating conditions that similarly perturb the DC-link voltage, such as sudden load changes, unbalanced grid voltage sags, or short-duration wind gusts, as these disturbances act on the same Vdc control loop that TSA optimizes. Validation of the proposed method under a broader set of test cases, including varying fault durations, multiple wind speed profiles, and unbalanced fault conditions, is identified as an important direction for future work and will be pursued in subsequent studies.
7. CONCLUSION
The role of distributed generation (DG) in the production of electric energy is evolving. In India wind energy plays vital role in renewable energy and in DG. This paper analyses PQ improvement in grid connected wind energy system using DSTATCOM. In conventional method of DSTATCOM PI controller is employed as DC voltage controller. In order to enrich the accuracy of compensation in this article Tunicate Swarm Algorithm is proposed. Performance of proposed system is validated with the comparative analysis of PSO and conventional PI controlled DSTATCOM. Performance of the system is analysed in terms of PQ, Vdc, and harmonics. During the drop in PCC voltage, the DC voltage drops by 0.16V, 0.13V, and 0.1V for the PI, PSO, and proposed TSA controlled DSTATCOM systems, respectively. The oscillation in DC voltage at the moment of a dip in PCC voltage by the suggested TSA controlled DSTATCOM system is 6.2V, which is smaller than 8.5V and 7.32V by the PI and PSO controlled DSTATCOM, respectively. TSA controlled DSTATCOM system offers minimum THD of 2.32%, while it is 3.52% and 4.56% by PSO and PI controlled DSTATCOM respectively. From the entire analysis it is evident that proposed TSA offers enriched performance in the aspects of both voltage control as well as in THD.
Despite the improved performance demonstrated in this study, the proposed method has certain limitations. The evaluation is restricted to a single operating scenario, namely a PCC voltage sag caused by a change in wind speed, and the comparison is limited to conventional PI and PSO controlled DSTATCOM. Additionally, the computational overhead of TSA relative to the conventional PI controller, as well as its real-time implementation feasibility on practical hardware platforms, has not been assessed in the present work. Future research will focus on validating the proposed TSA controlled DSTATCOM under a wider range of operating conditions, including unbalanced grid faults, sudden load variations, and combined wind-load disturbances, benchmarking TSA against other recent metaheuristic algorithms such as Grey Wolf Optimization and Sine Cosine Algorithm, and assessing its real-time implementation on hardware-in-the-loop platforms.
8. ACKNOWLEDGMENTS
The author would like to express his heartfelt gratitude to the supervisor for his guidance and unwavering support during this research.
9. DATA AVAILABILITY
The data generated and analyzed during the current study are available from the corresponding author upon reasonable request.
10. BIBLIOGRAPHY
-
[1] AHMED, M.M.R., MIRSAEIDI, S., KOONDHAR, M.A., et al., “Mitigating uncertainty problems of renewable energy resources through efficient integration of hybrid solar PV/wind systems into power networks”, IEEE Access : Practical Innovations, Open Solutions, v. 12, pp. 30311–30328, 2024. doi: https://doi.org/10.1109/ACCESS.2024.3370163.
» https://doi.org/10.1109/ACCESS.2024.3370163 - [2] CHOUDHURY, S., SAHOO, G.K., “A critical analysis of different power quality improvement techniques in microgrid”, e-Prime, v. 8, pp. 100520, 2024.
-
[3] ISANBAEV, V., BAÑOS, R., MARTÍNEZ, F., et al., “Monitoring energy and power quality of the loads in a microgrid laboratory using smart meters”, Energies, v. 17, n. 5, pp. 1251, 2024. doi: https://doi.org/10.3390/en17051251.
» https://doi.org/10.3390/en17051251 -
[4] SHAH, S.K.H., HELLANY, A., NAGRIAL, M., et al., “Influence of environmental changes on power quality disturbances in hybrid renewable energy system”, Energy Reports, v. 9, pp. 164–173, 2023. doi: https://doi.org/10.1016/j.egyr.2023.08.047.
» https://doi.org/10.1016/j.egyr.2023.08.047 - [5] SHARMA, V., GARG, P., SHARMA, A., et al., “A comprehensive review: Mitigating techniques for power variability due to integration of renewable energy sources with grid”, Journal of Electronic and Electrical Engineering, n. Sep, pp. 152–163, 2023.
-
[6] BOGHDADY, T.A., MOHAMED, Y.A., “Reactive power compensation using STATCOM in a PV grid connected system with a modified MPPT method”, Ain Shams Engineering Journal, v. 14, n. 8, pp. 102060, 2023. doi: https://doi.org/10.1016/j.asej.2022.102060.
» https://doi.org/10.1016/j.asej.2022.102060 -
[7] KUMAR, V., SINGH, M., “Reactive power compensation using derated power generation mode of modified P&O algorithm in grid-interfaced PV system”, Renewable Energy, v. 178, pp. 108–117, 2021. doi: https://doi.org/10.1016/j.renene.2021.06.035.
» https://doi.org/10.1016/j.renene.2021.06.035 -
[8] EL-GOHAREY, H.S., MAMDOUH, W.M., “On-line analysis of power quality problems in non-sinusoidal/non-linear distribution systems”, Ain Shams Engineering Journal, v. 14, n. 9, pp. 102266, 2023. doi: https://doi.org/10.1016/j.asej.2023.102266.
» https://doi.org/10.1016/j.asej.2023.102266 -
[9] MONTOYA, O.D., MOLINA-CABRERA, A., GIRAL-RAMÍREZ, D.A., et al., “Optimal integration of D-STATCOM in distribution grids for annual operating costs reduction via the discrete version sine-cosine algorithm”, Results in Engineering, v. 16, pp. 100768, 2022. doi: https://doi.org/10.1016/j.rineng.2022.100768.
» https://doi.org/10.1016/j.rineng.2022.100768 -
[10] SIRJANI, R., JORDEHI, A.R., “Optimal placement and sizing of distribution static compensator (D-STATCOM) in electric distribution networks: A review”, Renewable & Sustainable Energy Reviews, v. 77, pp. 688–694, 2017. doi: https://doi.org/10.1016/j.rser.2017.04.035.
» https://doi.org/10.1016/j.rser.2017.04.035 -
[11] SRIDHAR, V., UMASHANKAR, S., “A comprehensive review on CHB MLI based PV inverter and feasibility study of CHB MLI based PV-STATCOM”, Renewable & Sustainable Energy Reviews, v. 78, pp. 138–156, 2017. doi: https://doi.org/10.1016/j.rser.2017.04.111.
» https://doi.org/10.1016/j.rser.2017.04.111 -
[12] WANG, L., LAM, C.S., WONG, M.C., “A hybrid-STATCOM with wide compensation range and low DC-link voltage”, IEEE Transactions on Industrial Electronics, v. 63, n. 6, pp. 3333–3343, Jun. 2016. doi: https://doi.org/10.1109/TIE.2016.2523922.
» https://doi.org/10.1109/TIE.2016.2523922 -
[13] GUI, Y., WANG, X., BLAABJERG, F., “Vector current control derived from direct power control for grid-connected inverters”, IEEE Transactions on Power Electronics, v. 34, n. 9, pp. 9224–9235, Sep. 2018. doi: https://doi.org/10.1109/TPEL.2018.2883507.
» https://doi.org/10.1109/TPEL.2018.2883507 -
[14] JIN, Y., XIAO, Q., DONG, C., et al., “A novel submodule voltage balancing scheme for modular multilevel cascade converter—Double-star chopper-cells (MMCC-DSCC) based STATCOM”, IEEE Access : Practical Innovations, Open Solutions, v. 7, pp. 83058–83073, 2019. doi: https://doi.org/10.1109/ACCESS.2019.2924609.
» https://doi.org/10.1109/ACCESS.2019.2924609 - [15] DU, Y., HU, P., DENG, J., et al., “Research on a novel STATCOM based on hybrid cascaded multi-level converter and its coordination control strategy”, Journal of Engineering, v. 2019, n. 16, pp. 2332–2336, 2019.
-
[16] ARYA, S.R., PATEL, M.M., ALAM, S.J., et al., “Phase lock loop–based algorithms for DSTATCOM to mitigate load created power quality problems”, International Transactions on Electrical Energy Systems, v. 30, n. 1, pp. e12161, 2020. doi: https://doi.org/10.1002/2050-7038.12161.
» https://doi.org/10.1002/2050-7038.12161 -
[17] SREENIVASULU, P., HUSSAIN, J., “Design of cascade control loops for DFIG based wind energy conversion system control”, Matéria (Rio de Janeiro), v. 30, pp. e20240962, 2025. doi: https://doi.org/10.1590/1517-7076-rmat-2024-0962.
» https://doi.org/10.1590/1517-7076-rmat-2024-0962 -
[18] BAKIR, H., KULAKSIZ, A.A., “Modelling and voltage control of the solar-wind hybrid micro-grid with optimized STATCOM using GA and BFA”, Engineering Science and Technology, an International Journal, v. 23, n. 3, pp. 576–584, 2020. doi: https://doi.org/10.1016/j.jestch.2019.07.009.
» https://doi.org/10.1016/j.jestch.2019.07.009 -
[19] NAFEH, A.A., HEIKAL, A., EL-SEHIEMY, R.A., et al., “Intelligent fuzzy-based controllers for voltage stability enhancement of AC-DC micro-grid with D-STATCOM”, Alexandria Engineering Journal, v. 61, n. 3, pp. 2260–2293, 2022. doi: https://doi.org/10.1016/j.aej.2021.07.012.
» https://doi.org/10.1016/j.aej.2021.07.012 -
[20] AKBARI, E., SEYYEDI, A.Z., “Power quality enhancement of distribution grid using a photovoltaic based hybrid active power filter with three level converters”, Energy Reports, v. 9, pp. 5432–5448, 2023. doi: https://doi.org/10.1016/j.egyr.2023.04.368.
» https://doi.org/10.1016/j.egyr.2023.04.368 -
[21] MOHAMMEDI, R.D., KOUZOU, A., MOSBAH, M., et al., “Allocation and sizing of DSTATCOM with renewable energy systems and load uncertainty using enhanced Gray Wolf optimization”, Applied Sciences (Basel, Switzerland), v. 14, n. 2, pp. 556, 2024. doi: https://doi.org/10.3390/app14020556.
» https://doi.org/10.3390/app14020556 -
[22] ABDELAZIZ, M.A., ALI, A.A., SWIEF, R.A., et al., “Optimizing energy-efficient grid performance: integrating electric vehicles, DSTATCOM, and renewable sources using the Hippopotamus Optimization Algorithm”, Scientific Reports, v. 14, n. 1, pp. 28974, 2024. doi: https://doi.org/10.1038/s41598-024-79381-4. PubMed PMID: 39578503.
» https://doi.org/10.1038/s41598-024-79381-4 -
[23] KUMAR, N.V.V., MANOHAR, T.G., “Meta heuristic algorithm based novel Dstatcom architecture for power quality improvement”, International Journal of Experimental Research and Review, v. 38, pp. 119–131, 2024. doi: https://doi.org/10.52756/ijerr.2024.v38.011.
» https://doi.org/10.52756/ijerr.2024.v38.011 -
[24] KAUR, S., AWASTHI, L.K., SANGAL, A.L., et al., “Tunicate swarm algorithm: A new bio-inspired based metaheuristic paradigm for global optimization”, Engineering Applications of Artificial Intelligence, v. 90, pp. 103541, 2020. doi: https://doi.org/10.1016/j.engappai.2020.103541.
» https://doi.org/10.1016/j.engappai.2020.103541 -
[25] KARTHIKEYAN, U., HUSSAIN, J., “Enhancing the efficiency of wind energy conversion systems using Novel airfoil based small scale wind turbine”, Matéria (Rio de Janeiro), v. 30, pp. e20240827, 2025. doi: https://doi.org/10.1590/1517-7076-rmat-2024-0827.
» https://doi.org/10.1590/1517-7076-rmat-2024-0827 -
[26] SOMAYAJULA, D., CROW, M.L., “An ultracapacitor integrated power conditioner for intermittency smoothing and improving power quality of distribution grid”, IEEE Transactions on Sustainable Energy, v. 5, n. 4, pp. 1145–1155, Oct. 2014. doi: https://doi.org/10.1109/TSTE.2014.2334622.
» https://doi.org/10.1109/TSTE.2014.2334622 -
[27] PUCHALAPALLI, S., SINGH, B., TIWARI, S.K., et al., “Design and analysis of grid-interactive DFIG based WECS for regulated power flow”, IEEE Transactions on Industry Applications, v. 56, n. 5, pp. 5396–5407, 2020. doi: https://doi.org/10.1109/TIA.2020.3011059.
» https://doi.org/10.1109/TIA.2020.3011059 -
[28] MAHMOUD, M.M., SALAMA, H.S., BAJAJ, M., et al., “Integration of wind systems with SVC and STATCOM during various events to achieve FRT capability and voltage stability: Towards the reliability of modern power systems”, International Journal of Energy Research, v. 2023, n. 1, pp. 8738460, 2023. doi: https://doi.org/10.1155/2023/8738460.
» https://doi.org/10.1155/2023/8738460 -
[29] YARAT, S., SENAN, S., ORMAN, Z., “A comparative study on PSO with other metaheuristic methods”, In: Mercangöz, B.A. (ed), Applying Particle Swarm Optimization, Cham, Springer, pp. 49-72, 2021. doi: https://doi.org/10.1007/978-3-030-70281-6_4.
» https://doi.org/10.1007/978-3-030-70281-6_4