ABSTRACT
The expansion of DC microgrids has prompted investigations into wind energy systems to harness the benefits of this configuration. Therefore, this study aims to analyze and compare the performances of predictive current control (PCC) and predictive flux and torque control (PTC) applied to a doubly-fed induction generator which has its stator windings connected to a DC microgrid by means of a diode bridge. This system is commonly known as DFIG-DC. The system’s performance was evaluated in terms of electromagnetic torque ripple, rotor flux ripple, and current distortion across a range of operating speeds. Although PCC and PTC applied to DFIG-DC have been discussed in previous works, a systematic comparison between them lacks in the literature, which is the main contribution of this paper. In addition, this work discusses the robustness of both methods under parametric errors of stator and rotor resistances, and magnetizing inductance, which has not been approached before.
KEYWORDS
DC microgrid; doubly-fed induction machine; predictive current control; predictive flux and torque control
I. INTRODUCTION
Advances in power electronics technology play a crucial role in facilitating the operation of DC microgrids. When compared with AC microgrids, DC microgrids have the following advantages: they do not need to synchronize the generating sources connected to the bus; they can supply loads of different frequencies using frequency inverters; inductance and capacitance are not present in the DC system, and therefore, the voltage drop is lower, allowing better voltage regulation; they are more efficient because they do not have reactive power and skin effect [1]-[4]. To take advantage of the benefits of this configuration, studies were carried out and implemented on wind energy systems in these grids [1], [4].
Considering the use of doubly-fed induction generators (DFIG), their stator windings are usually connected to the DC microgrids by means of diode-based rectifiers. Meanwhile, the rotor windings are connected to the same microgrid employing a full-controlled converter, which performs the machine control. This system (illustrated in Fig. 1) is named in the literature as DFIG-DC, and has stood out due to its robust performance and independent control for active and reactive power [5], [6]. According to [7], the most prominent applications of DFIG-DC are wind power generation and interconnection [8], distributed generation and DC microgrids [9], [10], islanded power systems for mines [11], and on-board power generation [12].
Studies show that DFIG-DC can be controlled by different techniques. Reference [13] uses a direct torque control (DTC) scheme based on a hysteresis controller. Reference [14] compares DTC with field-oriented control (FOC) focusing on torque oscillation cancellation. And [15] proposes a simple control technique suitable to regulate the power delivered to the DC grid based on the regulation of the rotor flux linkage.
Also, Finite Control Set-Model Predictive Control (FCS-MPC) has been employed in machine drive systems in general. In this technique, based on the system model, the controlled variables are predicted for each available switching state. In this way, a cost function is determined, and the switching state that minimizes this function is selected and applied, sending its correspondent gating signals to the converter switches [16]. Compared to Proportional-Integral (PI)-based methods, such as FOC, FCS-MPC has the advantages of providing simple multivariable control and straightforward implementation, avoiding the tuning process of PI controllers, and providing faster dynamic response.
Among the types of FCS-MPC, the most discussed for machine control are the predictive current control (PCC) and the predictive flux and torque control (PTC). Reference [17] compares the performance of PCC and PTC for a three-phase squirrel-cage induction machine (IM). Simulations and experiments were carried out for steady and transient state operation, as well as parametric variation. PCC presented lower current harmonic distortion, but higher torque ripple compared to PTC. Depending on the application, this may be an important advantage of PTC over PCC since, as discussed in [18]-[20], torque pulsations result in torsional vibrations and shaft failures. In this way, it is very important to reduce torque ripple in DFIG-DC or any system that employs electric machines. In addition, [17] also proved that PTC is more robust to an error in estimating the value of the magnetizing inductance of the induction machine. On the other hand, PCC proved to be more robust when there is an error in estimating the resistance of the stator winding.
Also, in [21], four FCS-MPC methods (linear PCC, nonlinear PCC, linear PTC and nonlinear PTC) are compared to control a squirrel-cage induction machine configured in open-end for common mode current suppression. And fault-tolerance performance when applying PCC to a squirrel-cage IM drive was also verified in [22]. It is proved that PCC provides proper postfault operation when the system is submitted to a single-phase open-circuit fault, assuring postfault sinusoidal magnetic flux and low torque ripple.
Regarding the use of DFIG, [23] discussed a FCS-MPC method that regulates real and reactive powers in a conventional type-III wind energy conversion system (WECS). And finally, when it comes to DFIG-DC, [24] proposed a sensorless PCC method that regulates the rotor currents without the need for a position sensor. However, it does not compensate for the delay introduced by the digital processors and does not perform any discussion on torque ripple. And [25] shows an optimized PTC in order to minimize system losses and obtain low torque ripple.
In this context, the present paper discusses the application of PCC and PTC to the DFIG-DC system. This is an extended version of conference paper [26]. The main contributions of this new version are: 1) Deeper discussion of PCC and PTC methods applied to the DFIG-DC system; 2) Comparative analysis between the methods in terms of stator and rotor currents harmonic distortion, torque ripple, flux ripple, and transient response based on simulation and experimental results in different operation scenarios. This comparison has not been done in the literature; 3) Analysis of the robustness of the methods in the presence of parametric errors or variations, which is not present in the literature either.
The paper is divided as follows: Section II presents the mathematical model of the system; Sections III and IV detail the mathematical modeling used for predictive current control and predictive torque and flux control, respectively; In Section V, the selection of the switching state is explained; The simulation and experimental results of the DFIG-DC system comparing PCC and PTC are shown in Section VI and VII respectively; Section VIII presents the conclusion.
II. SYSTEM MODEL
The mathematical model of the DFIG in the dq rotor reference frame can be described by [25], [27]:
The subscripts s and r represent the stator and rotor parameters, respectively, is the rotor electrical speed, and are the stator and rotor resistance, respectively, and are the inductances of the stator and rotor windings, respectively, is magnetizing inductance. , and are vectors of voltage, current and flux, respectively, where is the vector of variable x in rotor reference frame with x = v, i and λ, n = s (stator) or r (rotor), and . and are the electromagnetic and mechanical torque, respectively, is the friction coefficient, is the moment of inertia, P is the machine number of pairs of poles.
A. Speed control and electromagnetic torque reference
The machine speed is regulated using a conventional PI controller. It generates, at its output, the electromagnetic torque reference, which is used to obtain the current references in PCC, and for the cost function in PTC. Considering the mechanical torque as a disturbance, the electromagnetic torque reference is expressed by:
where is the speed error, resulting from the difference between the speed reference and the measured speed . The proportional and integral gains are defined by (8) and (9), where is the mechanical time constant of the machine (), is a mechanical gain, is the control accommodation time and is the damping factor.
III. PREDICTIVE CURRENT CONTROL
The predictive current control (PCC) strategy used in this work consists in regulating the rotor current of DFIG-DC system using the FCS-MPC technique in the rotor reference frame. Then, (1)-(4) are rearranged using the forward Euler discretization method, determining the predicted rotor currents, as detailed in [25], [26]. The compensation of the Digital Signal Processor (DSP) delay is implemented, as discussed in [25], [28]. Then, the predicted rotor currents in the rotor reference frame in two steps ahead, represented by the notation k + 2, is shown in (10) and (11),
where is the sampling time and is the leakage factor []; and are the predicted rotor currents for instant k + 1; , , and are the same values as at instant k [26]. The voltages and are obtained once again by Park's Transformation from the tested phase rotor voltages, which are determined by the RSC, as will be explained in Section V. The rotor flux arises from the predicted flux in the first step is given by:
where the rotor flux comes from the observer developed by [29]; arise from the present switching state of the rotor converter and obtained by measuring the DFIG rotor currents.
In this control method, the stator phase voltages are imposed in the algorithm as the fundamental component of the SSR voltages which has an amplitude of . This approximation does not harm the applied control method [30], [31]. Thus, the fundamental components of the phase voltages across the stator windings are:
where m= 1, 2 and 3, E is the DC-link voltage and rad/s, is the synchronous speed, which determines the synchronous frequency as 50 Hz.
As described in [32], the reference dq rotor currents can be obtained from the stator voltage reference frame in order to control the DFIG electromagnetic torque and obtain unity power factor. They are determined from (14) and (15), where is the amplitude of the dq stator voltage. is the electromagnetic reference torque that comes from a conventional PI rotor speed controller, as explained in Section II.A and the index e indicates the stator voltage reference frame.
Subsequently, the reference currents are obtained in the rotor reference frame by means of referential transformation, as expressed below:
where is the position of the stator voltage vector and is the position of the rotor.
The cost function chosen for the PCC uses the squared current error given as:
Finally, the PCC control diagram is represented in Fig. 2, as discussed in this section.
IV. PREDICTIVE FLUX AND TORQUE CONTROL
The predictive flux and torque control (PTC) for DFIGDC consists in controlling the rotor flux magnitude and the electromagnetic torque. The predicted rotor flux components in k+2, when discretized by forward Euler method and compensating for the delay, are:
where and come from (12); the currents and comes from instant k + 1; and are obtained through the switching state of the rotor converter during the commutation tests of the predictive control, as will be explained in Section V. Finally, the predicted rotor flux module is determined by:
The electromagnetic torque is calculated through the rotor current and the rotor flux, according to (5). In this way, the prediction of torque is given by
where , , and come from the equations (10), (11), (19) and (20), respectively. In PTC, stator voltages used in (10) and (11) are measured directly from the machine by sensors and then transformed into dq rotor reference frame.
The selected cost function considers two control objectives: 1) Imposing a constant electromagnetic torque; and 2) Regulating the amplitude of the rotor flux. The PTC cost function is based on torque and rotor flux errors and is given by:
In this case, there is a weighting factor for the rotor flux expressed by . The PTC control diagram is represented in Fig. 3.
V. SWITCHING STATE SELECTION
For the two-level inverter used in the RSC for PCC and PTC, the switching state voltage is given by and . To determine the predicted control variables for the instant k+2, these voltages are inserted into Equations (10), (11), (19) and (20), through the variables and . After testing all combinations, the voltage vector that minimizes the cost function is applied on the converter switches.
VI. SIMULATION RESULTS
Simulations of the DFIG-DC system were performed using a 560-W DFIG through softwares PSIM®, Matlab® and DevC++®. The values of DFIG, system and control parameters used in the simulations are shown in the Tables 1 and 2, respectively.
Figure 4 shows the steady-state simulation results for PCC and PTC for a speed reference of rad/s. Data on speed, torque, rotor flux, rotor currents and stator voltage and current were obtained. Total harmonic distortion (THD), flux and torque ripple were also computed. The THD is calculated by:
where is the rms value of the phase current and is the rms value of the phase current fundamental component.
The ripple is determined by (25), where ripple is given in percentage; N is the number of samples; and are the values of each sample and the average of the signal, respectively.
Simulation results for steady-state predictive control for = 300rad/s. (a) PCC machine speed. (b) PTC machine speed. (c) PCC torque. (d) PTC torque. (e) PCC rotor flux. (f) PTC rotor flux. (g) PCC rotor currents in the rotor reference frame. (h) PTC rotor currents in the rotor reference frame. (i) PCC stator phase voltage and phase current. (j) PTC stator phase voltage and phase current.
Figs. 4(a) and 4(b) show the rotor speed and its reference for PCC and PTC, respectively. Observe that both methods are capable of regulating properly the rotor speed.
It can be seen from Figs. 4(c), for PCC, and 4(d), for PTC, that the torque has an average value of -2N.m, and that the torque ripple produced by PTC is less than that produced by PCC. The negative value of torque means that the machine operates as generator. Concerning the rotor flux, PTC regulates its value to its reference value (see Fig. 4(f)). And PCC, although it does not directly regulate the rotor flux, provides an average value of around 0.86 Wb, as shown in Fig. 4(e).
Figs. 4(g) and 4(h) show the rotor current in the dq rotor reference frame. It is evident for PCC that the rotor current closely tracks its reference with low distortion. In contrast, PTC exhibits higher current ripple. Another detail is that the synchronous frequency is different in each technique. PCC has a fixed synchronous frequency of = 314 rad/s (50 Hz). Therefore, it is noted that for the reference speed of 300 rad/s, the PCC is in subsynchronous operating mode. On the other hand, PTC does not have a fixed synchronous frequency, which depends on the point of operation. For this simulation, it is clear that the PTC is in supersynchronous operating mode, since current leads current .
The stator voltage and current can be seen in Fig. 4(i) for PCC and Fig. 4(j) for PTC. Note that the currents are 180° out-of-phase with the voltage, as the machine operates as generator with a unity power factor. Furthermore, PCC stator currents have a sinusoidal waveform despite being connected to a diode bridge.
Simulations results for speeds of 270 rad/s and 340 rad/s, as well as simulation THD values, can be seen in [26]. However, torque and flux ripples comparison is shown in Table 3.
Table 3 shows the electromagnetic torque and rotor flux ripple values for three different steady-state speeds (270, 300, 340 rad/s). For all scenarios, PTC obtained a smaller value in both torque and flux ripple. Considering rad/s in which PCC obtained the lowest ripple value, PTC presents torque and flux ripple 36.48% and 18.80% lower than PCC, respectively.
As explained before, for results concerning harmonic distortion, the THD values can be obtained in the conference paper [26]. It is shown that PCC has a lower THD in all scenarios with an average of 44% lower in stator current and 49% lower in rotor current compared to PTC.
Therefore, PCC presents better quality in both rotor and stator currents when compared to PTC. And PTC, in turn, presents a better result of rotor flux and electromagnetic torque, with smaller ripples in relation to those observed for PCC.
VII. EXPERIMENTAL RESULTS
Experimental results for the DFIG-DC system are presented comparing PCC and PTC methods. Fig. 5 shows the experimental setup and Fig. 6 describes the experimental setup scheme. The computer applies the program to the Digital Signal Processor (DSP) TMS320F28335, which processes and controls the system signals. The oscilloscope used was Agilent, model DSO-X 3014A. In order to emulate a DC microgrid, an autotransformer feeds the DC bus through a diode bridge, keeping a constant voltage. Another autotransformer feeds a 550-W squirrel-cage induction motor (SCIM), which has the function of imposing the mechanical torque of the system. The DFIG has its rotor and stator terminals connected to their respective power converters, RSC and SSR. There is also the DC bus, and a resistive load necessary to dissipate the power generated by the DFIG-DC, as there is no possibility of it being drained by the grid in this experiment.
Experiments were carried out for steady state, speed transients and parametric variations of the stator and rotor resistance, and of the magnetizing inductance.
A. Steady-state results
The steady-state experimental results are illustrated in Figs. 7 to 9 acquired by the DSP and the oscilloscope. Three different experimental scenarios were carried out in order to compare the performance of PCC and PTC. The DC-link voltage was fixed at 250 V and the speed references were 270 rad/s (scenario 1), 300 rad/s (scenario 2) and 340 rad/s (scenario 3), respectively. For all cases, the synchronous frequency for PCC was fixed at 50 Hz, so that it was possible to observe the subsynchronous and supersynchronous behavior of the machine. Furthermore, the rotor flux for PTC was fixed at its nominal value of 0.93 Wb.
1) Scenario 1
Figs. 7(a) and 7(b) show the steady-state rotor speed for PCC and PTC, respectively. Both techniques manage to regulate properly the rotor speed to the reference of 270 rad/s, making the system operate below the synchronous speed in the subsynchronous mode.
Experimental results for steady-state predictive control for =270rad/s (scenario 1). (a) PCC machine speed. (b) PTC machine speed. (c) PCC torque. (d) PTC torque. (e) PCC rotor flux. (f) PTC rotor flux. (g) PCC rotor phase current. (h) PTC rotor phase current. (i) PCC stator phase voltage and phase current. (j) PTC stator phase voltage and phase current.
The electromagnetic torque of both methods presents similar behavior with an average of -2 N.m, as shown in Fig. 7(c), for PCC, and Fig. 7(d), for PTC. The rotor flux is shown in Figs. 7(e) and 7(f) for PCC and PTC, respectively. Note that rotor flux was properly regulated with PTC, also presenting lower ripple compared to PCC.
Concerning the rotor currents, it is noticeable that their frequencies are different between PCC, Fig. 7(g), and PTC, Fig. 7(h), because the value of the synchronous speed varies depending on the operation point for PTC, while it is constant for PCC. Also, Figs. 7(i) and 7(j) show the stator current and voltage for PCC and PTC, respectively. It is possible to see that operation with unity power factor was assured.
2) Scenario 2
In this scenario, the machine operates at 300 rad/s for PCC and PTC, as shown in Figs. 8(a) and 8(b), respectively. It is noted that the speed is regulated adequately for both methods.
Experimental results for steady-state predictive control for =300rad/s (scenario 2). (a) PCC machine speed. (b) PTC machine speed. (c) PCC torque. (d) PTC torque. (e) PCC rotor flux. (f) PTC rotor flux. (g) PCC rotor phase current. (h) PTC rotor phase current. (i) PCC stator phase voltage and phase current. (j) PTC stator phase voltage and phase current.
The electromagnetic torque is shown in Figs. 8(c) and 8(d) for PCC and PTC, respectively. The average value is close to -2 N.m. The rotor flux is shown in Figs. 8(e) and 8(f) for PCC and PTC, respectively. It can be seen that the flux control for PTC follows the reference and presents lower ripple compared to PCC.
The rotor currents, shown in Figs. 8(g), for PCC, and 8(h), for PTC, present smaller distortions in the former in relation to the latter. Furthermore, it can be seen that the frequency of the rotor current in PCC is much lower when compared to the previous scenario due to the fact that the machine speed is closer to synchronous speed, but still in subsynchronous mode. The frequency of this current in PTC is approximately the same as the previous one. However, the sequence of the phases is different, which proves that it has switched to supersynchronous mode. As for stator current and voltage, in both cases, they present a 180º phase difference between them, with the PCC presenting better current quality. The result of these variables for PCC can be seen in Fig. 8(i) and for PTC in Fig. 8(j).
3) Scenario 3
Figs. 9(a) and 9(b) show the machine speed and its reference for 340 rad/s for PCC and PTC, respectively. Both adjust the rotor speed properly.
Experimental results for steady-state predictive control for =340rad/s (scenario 3). (a) PCC machine speed. (b) PTC machine speed. (c) PCC torque. (d) PTC torque. (e) PCC rotor flux. (f) PTC rotor flux. (g) PCC rotor phase current. (h) PTC rotor phase current. (i) PCC stator phase voltage and phase current. (j) PTC stator phase voltage and phase current.
The electromagnetic torque can be visualized in Figs. 9(c) and 9(d) for PCC and PTC, respectively. The rotor flux is shown in Figs. 9(e) and 9(f) for PCC and PTC, respectively. PTC continues to present lower ripple than PCC.
Through the rotor currents, shown in Figs. 9(g) and 9(h) for PCC and PTC, respectively, it is possible to state that the machine is operating in supersynchronous mode, due to the change in the phase sequence when compared to scenario 1. In addition, it is observed that the frequency of the currents in PTC is very high, as it has moved even further away from the synchronous speed. The stator voltage and current can be seen in Fig. 9(i), for PCC, and in Fig. 9(j), for PTC. As in previous scenarios, unity power factor is guaranteed. The results of this scenario are also compatible with the simulation shown in the conference paper [26].
For the analysis of the torque and rotor flux ripple, an extra steady-state experiment was performed with more sample points (1000 points) in a shorter period of time (total of 0.1 seconds). Table 4 reports these values for PCC and PTC. It can be seen that PTC presents lower values of both torque and flux ripple in all scenarios, confirming the simulation results.
Table 5 shows the average switching frequency (), and the stator and rotor currents THD for each scenario and each strategy. It is noted that PCC obtained a lower THD in all scenarios for both rotor and stator currents in relation to PTC. This demonstrates that current control has the advantage of generating better current quality. For the average switching frequencies, it can be seen that there is no significant change between each scenario, nor between the strategies.
Average switching frequency and stator and rotor currents THD for PCC and PTC-experimental results.
Therefore, it is concluded, regarding the experimental results in steady state, that PCC obtained better performance in terms of quality of rotor and stator currents, while PTC presented better results in terms of torque and flux ripple. Both strategies managed to control the speed of the machine in all scenarios, whether configured in subsynchronous or supersynchronous mode, in addition to obtaining unity power factor. The results of experimental scenarios 1 and 3 are compatible with the simulations shown in the conference paper [26], and those of scenario 2 are in full accordance with the simulation results presented in Fig. 4.
B. Transient-state results
The system was also evaluated under speed transients, changing the reference speed from 270 rad/s to 340 rad/s and, a few seconds later, to 300 rad/s. The bus voltage used was 250V. PTC reference rotor flux was set at 0.93 Wb, PCC synchronous frequency was 50 Hz.
Fig. 10 shows the results for the case in which the system is submitted to speed step variations, acquired by the DSP and the oscilloscope. Initially the reference speed is 270 rad/s until eight seconds. At this point it is changed to 340 rad/s and, in eleven seconds, changed to 300 rad/s, as can be seen in Fig. 10(a) and 10(b) for PCC and PTC, respectively. It is noted that both techniques present a quick response to speed variations. The high undershoot in the PCC at the instant of speed reduction is noteworthy.
Experimental results of predictive control during speed transient. (a) PCC machine speed. (b) PTC machine speed. (c) PCC torque. (d) PTC torque. (e) PCC rotor flux. (f) PTC rotor flux. (g) PCC rotor and stator phase current. (h) PTC rotor and stator phase current.
The electromagnetic torque, at times of speed variation, presents different behaviors as can be seen in Figs. 10(c) and 10(d) for PCC and PTC, respectively. When the speed increases, the torque tends to be positive. However, the control limits it to zero to ensure energy generation until the reference speed is reached. At the moment of changing the speed reference to a lower value, the torque presents a high negative peak. PTC has a lower value, around -7.5 N.m, while PCC has twice the value, around -15 N.m. This fact shows the good functioning of the torque control.
Another fact that can be noted is that there is a difference in the average value of the torque during the steady state of the three speeds. This occurred because, during this experiment, there was no change in the voltage imposed on the primary machine, and thus, there was no regulation of the mechanical torque, unlike the steady state results, in which this voltage was modified to adjust the electromagnetic torque to -2 N.m.
Figs. 10(e) and 10(f) show the rotor flux of PCC and PTC during the transient, respectively. A peak can be noted at the time of the speed decrease (in eleven seconds) that is quite high for PCC, around 1.8 Wb, and much lower for PTC, around 1.1 Wb.
Finally, the rotor and stator currents, during the transition, can be visualized in Figs. 10(g) and 10(h), together with the zoom in the second transition, for PCC and PTC, in that order. As for the rotor currents, it can be seen that the variation in speed caused their frequency to change for each steady state operation point. In PCC, as the synchronous speed is fixed in 314 rad/s, when the system operates in subsynchronous mode (first and third operation point) there is a sequence of current phases that differs from the sequence in supersynchronous mode (second operation point). This phenomenon becomes more noticeable when observing the zoom at the moment of the transition from 340 rad/s to 300 rad/s. Furthermore, the closer to synchronous speed, the lower the frequency, as can be seen for 300 rad/s.
In PTC, a frequency variation in rotor currents also occurs. Looking more closely, it can be seen that the first operation point presents a different sequence of phases than the other two. This indicates that the synchronous speed under these conditions is between 270 rad/s and 300 rad/s. Furthermore, a difference in the amplitude of the rotor currents is noted, which is due to the variation of the electromagnetic torque.
As for the stator current, PCC has the same frequency (50 Hz) for any speed value and its amplitude has a linear relationship with the torque, and thus, with the generated power. In PTC, the stator current varies slightly in frequency in each operation point. And as for amplitude, it is also linearly modified by the torque, as in PCC. It is worth to point out that there is a difference in the scale of the rotor current in Figure 10(g) and 10(h) which causes a visual difference between them.
C. Parametric variations
The machine's parameters are obtained by experimental tests designed for this purpose. However, these parameters may vary depending on the operation point and temperature. Therefore, it is important to verify the robustness of control techniques in case there are errors or variations in the machine estimated parameters. In this way, the system was also experimented for parametric variations of stator resistance (), rotor resistance () and magnetizing inductance (), where the parameter values used in the control algorithms were modified linearly with the purpose of verifying the behavior of the methods when the parameters had different values from the real ones present in the machine. The DC bus voltage used in these experiments was 250 V and the speed was 300 rad/s. PTC reference rotor flux was set at 0.93 Wb, PCC synchronous frequency was 50 Hz.
1) Stator resistance
The behavior of the system for the variation in stator resistance can be seen in Fig. 11. After the system reaches steady state, at the time of 12 seconds the value of the parameter begins to be altered in the control algorithm, as seen in Fig. 11(a).
Experimental results by varying . (a) Variation . (b) PCC machine speed. (c) PTC machine speed. (d) PCC torque. (e) PTC torque.
It is noted that when PCC is employed, despite the increase of torque amplitude with high values of stator resistance, Fig. 11(d), the system in general does not lose speed control for the considered parametric variation band, as illustrated in Fig. 11(b). However, for PTC, the system loses control when the stator resistance reaches values above 68Ω (350% above the estimated value), as can be seen in Fig. 11(c), although the torque remains controlled, Fig. 11(e). With this, it can be stated that PTC was robust up to 350% of the estimated stator resistance value, and that PCC can reach greater levels of variation without losing control of the system.
2) Rotor resistance
The system's response to variation in rotor resistance can be seen in Fig. 12. Similarly to the previous case, the value of the parameter begins to be altered in the control algorithm at the time of 12 seconds, as shown in Figs. 12(a).
Experimental results by varying rr. (a) Variation rr. (b) PCC machine speed. (c) PTC machine speed. (d) PCC torque. (e) PTC torque. (f) PCC rotor phase current. (g) PTC rotor phase current.
It can be seen that the increase in rotor resistance from 6.22 Ω to 143 Ω (increase of 2300%) did not change the speed and torque provided by PCC, as shown in Figs. 12(b) and 12(d) respectively. The same is attested for PTC, as shown in Figs. 12(c) and 12(e).
Finally, the curves of the rotor currents were inserted exclusively in this scenario, Figs. 12(f) and 12(g) for PCC and PTC respectively, in order to prove that the system remains controlled, even with a high change in the parameter . However, it can be seen that the modification in the value of the rotor resistance increases the frequency of the rotor currents in PTC. This implies that the synchronous speed changes as a function of this variation. Therefore, it is concluded that the two control methods are robust to the parametric variation of the rotor resistance for the implemented system, but PCC presents the advantage that there is no change in any other parameter.
3) Magnetizing inductance
Fig. 13 shows the results for the variation of the system's magnetizing inductance for PCC and PTC. At the time of 12 seconds the value of the parameter begins to be altered in the control algorithm, as seen in Fig. 13(a) and 13(b) for PCC and PTC, respectively. Unlike the previous cases, in this test the parameter grows in different proportions in each strategy. The reason for this is that the two methods diverge at different times, and to illustrate this, this modification was necessary.
Experimental results by varying . (a) Variation PCC. (b) Variation PTC. (c) PCC machine speed. (d) PTC machine speed. (e) PCC torque. (f) PTC torque.
For PCC, with approximately 50% of variation above the estimated value, the system diverges as can be seen in Fig. 13(c) and 13(e), for the speed and electromagnetic torque, respectively. For PTC, the system diverges, as shown in Fig. 13(d) and 13(f), for the speed and electromagnetic torque, respectively, with an increase of of 300%, proving to be more robust when compared to PCC. Therefore, it is concluded that PTC is more robust as it can keep the system stable for higher magnetizing inductance parametric errors than PCC.
Table 6 summarizes the comparison between PCC and PTC performed across the paper.
VIII. CONCLUSIONS
A comparison between the predictive current control and predictive flux and torque control methods implemented in the DFIG-DC system was provided in this paper. Additionally, the operation and equations of PCC and PTC utilized in this system were explained in detail, also covering the speed control, and the selection of the switching states.
Considering the steady-state results obtained from simulations and experiments, the two control methods showed similar performance for different scenarios. The most notable differences in the simulation and experiment results were that PCC shows better current quality in both the rotor and stator, while PTC shows better results in rotor flux and electromagnetic torque, with lower ripple.
For speed transient analysis, both control methods demonstrate a good dynamic response. The most significant differences between them are observed in the lower variations in electromagnetic torque and rotor flux of PTC when the system is submitted to speed steps. Regarding the parametric variation of stator resistance, PCC is more robust compared to PTC. For rotor resistance, both methods maintain stability even with variations up to 2300% above the measured value. However, since PTC exhibits variations in rotor current frequency throughout the test, PCC is more robust in this situation. The variation in magnetizing inductance, on the other hand, causes the system to lose control with both strategies. Nevertheless, PTC proves to be more robust as it maintains control under larger variations compared to PCC.
Finally, PCC proves to be more advantageous than PTC mainly because it does not require voltage sensors, which reduces the cost of the system and presents a well-defined frequency and synchronous speed, making it simpler to determine the operating mode between subsynchronous and supersynchronous.
As future work, studies must be carried out to evaluate the robustness of DFIG-DC with FCS-MPC methods under open-phase and open-switch faults.
ACKNOWLEDGMENT
The authors would like to thank PPGEE-UFPB, DEE-UFPB, grant #2021/07 Paraiba State Research Foundation (FAPESQ), the Agencia Nacional de Investigación y Desarrollo (ANID) FONDECYT Regular grant number 1220556, the Research Project PINV01-743 of the Consejo Nacional de Ciencia y Tecnología (CONACYT), ENNOBLE-R02401, and IRCF project from the University of Nottingham for the financial support.
PLAGIARISM POLICY
REFERENCES
-
1 E. Rodriguez-Diaz, M. Savaghebi, J. C. Vasquez, J. M. Guerrero, “An overview of low voltage DC distribution systems for residential applications”, in 2015 IEEE 5th International Conference on Consumer Electronics Berlin (ICCE-Berlin), pp. 318–322, 2015, doi: 10.1109/ICCE-Berlin.2015.7391268.
» https://doi.org/10.1109/ICCE-Berlin.2015.7391268 -
2 T. Dragičević, X. Lu, J. C. Vasquez, J. M. Guerrero, “DC Microgrids—Part II: A Review of Power Architectures, Applications, and Standardization Issues”, IEEE Transactions on Power Electronics, vol. 31, no. 5, pp. 3528–3549, 2016, doi: 10.1109/TPEL.2015.2464277.
» https://doi.org/10.1109/TPEL.2015.2464277 -
3 N. K.K., J. N. S., V. Jadoun, “An overview of DC Microgrid with DC distribution system for DC loads”, Materials Today: Proceedings, vol. 51, 06 2021, doi: 10.1016/j.matpr.2021.06.093.
» https://doi.org/10.1016/j.matpr.2021.06.093 -
4 A. Akhbari, M. Rahimi, M. Khooban, “Direct current grid-based doubly-fed induction generator wind turbines: Real-time control and stability analysis”, IET Power Electronics, vol. 15, 09 2022, doi: 10.1049/pel2.12299.
» https://doi.org/10.1049/pel2.12299 -
5 T. Ahmed, K. Nishida, M. Nakaoka, “A Novel Stand-Alone Induction Generator System for AC and DC Power Applications”, Industry Applications, IEEE Transactions on, vol. 43, pp. 1465 – 1474, 12 2007, doi: 10.1109/TIA.2007.908210.
» https://doi.org/10.1109/TIA.2007.908210 - 6 M. Tazil, V. Kumar, R. C. Bansal, S. Kong, Z. Y. Dong, W. Freitas, H. D. Mathur, “Three-phase doubly fed induction generators: an overview”, Iet Electric Power Applications, vol. 4, pp. 75–89, 2010.
-
7 G. D. Marques, M. F. Iacchetti, “DFIG Topologies for DC Networks: A Review on Control and Design Features”, IEEE Transactions on Power Electronics, vol. 34, no. 2, pp. 1299–1316, 2019, doi: 10.1109/TPEL.2018.2829546.
» https://doi.org/10.1109/TPEL.2018.2829546 -
8 N. Holtsmark, H. J. Bahirat, M. Molinas, B. A. Mork, H. K. Hoidalen, “An All-DC Offshore Wind Farm With Series-Connected Turbines: An Alternative to the Classical Parallel AC Model?”, IEEE Transactions on Industrial Electronics, vol. 60, no. 6, pp. 2420–2428, 2013, doi: 10.1109/TIE.2012.2232255.
» https://doi.org/10.1109/TIE.2012.2232255 -
9 P. Karlsson, J. Svensson, “DC bus voltage control for a distributed power system”, IEEE Transactions on Power Electronics, vol. 18, no. 6, pp. 1405–1412, 2003, doi: 10.1109/TPEL.2003.818872.
» https://doi.org/10.1109/TPEL.2003.818872 -
10 T. Dragičević, X. Lu, J. C. Vasquez, J. M. Guerrero, “DC Microgrids—Part I: A Review of Control Strategies and Stabilization Techniques”, IEEE Transactions on Power Electronics, vol. 31, no. 7, pp. 4876–4891, 2016, doi: 10.1109/TPEL.2015.2478859.
» https://doi.org/10.1109/TPEL.2015.2478859 -
11 M. G. Jahromi, G. Mirzaeva, S. D. Mitchell, D. Gay, “Powering Mobile Mining Machines: DC Versus AC Power”, IEEE Industry Applications Magazine, vol. 22, no. 5, pp. 63–72, 2016, doi: 10.1109/MIAS.2015.2459082.
» https://doi.org/10.1109/MIAS.2015.2459082 -
12 B. Zahedi, L. E. Norum, “Modeling and Simulation of All-Electric Ships With Low-Voltage DC Hybrid Power Systems”, IEEE Transactions on Power Electronics, vol. 28, no. 10, pp. 4525–4537, 2013, doi: 10.1109/TPEL.2012.2231884.
» https://doi.org/10.1109/TPEL.2012.2231884 -
13 A. Gundavarapu, H. Misra, A. K. Jain, “Direct Torque Control Scheme for DC Voltage Regulation of the Standalone DFIG-DC System”, IEEE Transactions on Industrial Electronics, vol. 64, no. 5, pp. 3502–3512, 2017, doi: 10.1109/TIE.2016.2644623.
» https://doi.org/10.1109/TIE.2016.2644623 -
14 G. Iwański, M. Piwek, G. Dauksha, “Doubly Fed Induction MachineBased DC Voltage Generator with Reduced Oscillations of Torque and Output Voltage”, Energies, vol. 16, no. 2, 2023, URL: https://www.mdpi.com/1996-1073/16/2/814
» https://www.mdpi.com/1996-1073/16/2/814 -
15 M. F. Iacchetti, G. D. Marques, R. Perini, “A Scheme for the Power Control in a DFIG Connected to a DC Bus via a Diode Rectifier”, IEEE Transactions on Power Electronics, vol. 30, no. 3, pp. 1286– 1296, 2015, doi: 10.1109/TPEL.2014.2317947.
» https://doi.org/10.1109/TPEL.2014.2317947 -
16 S. Kouro, P. Cortes, R. Vargas, U. Ammann, J. Rodriguez, “Model Predictive Control—A Simple and Powerful Method to Control Power Converters”, IEEE Transactions on Industrial Electronics, vol. 56, no. 6, pp. 1826–1838, 2009, doi: 10.1109/TIE.2008.2008349.
» https://doi.org/10.1109/TIE.2008.2008349 -
17 F. Wang, S. Li, X. Mei, W. Xie, J. Rodríguez, R. M. Kennel, “ModelBased Predictive Direct Control Strategies for Electrical Drives: An Experimental Evaluation of PTC and PCC Methods”, IEEE Transactions on Industrial Informatics, vol. 11, no. 3, pp. 671–681, 2015, doi: 10.1109/TII.2015.2423154.
» https://doi.org/10.1109/TII.2015.2423154 -
18 V. S. S. Pavan Kumar Hari, G. Narayanan, “Theoretical and Experimental Evaluation of Pulsating Torque Produced by Induction Motor Drives Controlled With Advanced Bus-Clamping Pulsewidth Modulation”, IEEE Transactions on Industrial Electronics, vol. 63, no. 3, pp. 1404–1413, 2016, doi: 10.1109/TIE.2015.2494530.
» https://doi.org/10.1109/TIE.2015.2494530 -
19 J. Song-Manguelle, S. Schröder, T. Geyer, G. Ekemb, J.-M. NyobeYome, “Prediction of Mechanical Shaft Failures Due to Pulsating Torques of Variable-Frequency Drives”, IEEE Transactions on Industry Applications, vol. 46, no. 5, pp. 1979–1988, 2010, doi: 10.1109/TIA.2010.2057397.
» https://doi.org/10.1109/TIA.2010.2057397 -
20 X. Han, A. B. Palazzolo, “VFD Machinery Vibration Fatigue Life and Multilevel Inverter Effect”, IEEE Transactions on Industry Applications, vol. 49, no. 6, pp. 2562–2575, 2013, doi: 10.1109/TIA.2013.2265871.
» https://doi.org/10.1109/TIA.2013.2265871 -
21 B. Zhu, K. Rajashekara, H. Kubo, “A Comparison between Current Based and Flux/Torque Based Model Predictive Control Methods for Open-End Winding Induction Motor Drives”, IET Electric Power Applications, vol. 11, 05 2017, doi: 10.1049/iet-epa.2016.0517.
» https://doi.org/10.1049/iet-epa.2016.0517 -
22 L. M. d. Oliveira, V. F. M. B. Melo, G. F. da Paz, F. V. Rocha, E. L. L. Fabricio, “Experimental Assessment of Predictive Current Control Applied to Induction Machine Drive Systems Operating Under Single-Phase Open-Circuit Fault”, Eletrônica de Potência, vol. 29, Mar. 2024, doi: 10.18618/REP.2024.1.0011.
» https://doi.org/10.18618/REP.2024.1.0011 -
23 F. Guedes, N. Rocha, A. Maciel, A. Sguarezi, “Finite-Set Model Predictive Direct Power Control for DFIG with Reduced Number of Voltage Vectors”, Eletrônica de Potência, vol. 28, pp. 1–11, 03 2023, doi: 10.18618/REP.2023.1.0025.
» https://doi.org/10.18618/REP.2023.1.0025 -
24 S. Bayhan, H. Abu-Rub, O. Ellabban, “Sensorless Model Predictive Control Scheme of Wind-Driven Doubly Fed Induction Generator in DC Microgrid”, IET Renewable Power Generation, 01 2016, doi: 10.1049/iet-rpg.2015.0347.
» https://doi.org/10.1049/iet-rpg.2015.0347 -
25 S. M. A. Cruz, G. D. Marques, P. F. C. Gonçalves, M. F. Iacchetti, “Predictive Torque and Rotor Flux Control of a DFIG-DC System for Torque Ripple Compensation and Loss Minimization”, IEEE Transactions on Industrial Electronics, vol. 65, pp. 9301–9310, 2018, doi: 10.1109/TIE.2018.2818667.
» https://doi.org/10.1109/TIE.2018.2818667 -
26 L. F. M. De Lucena, V. F. M. B. Melo, N. Rocha, R. Da Cruz Ferreira, “Comparison Between Predictive Current and Predictive Torque Control Applied to a Doubly-Fed Induction Generator System for Connection to DC Microgrids”, in 2023 IEEE 8th Southern Power Electronics Conference and 17th Brazilian Power Electronics Conference (SPEC/COBEP), pp. 1–6, 2023, doi: 10.1109/SPEC56436.2023.10408100.
» https://doi.org/10.1109/SPEC56436.2023.10408100 -
27 Y. Xiao, B. Fahimi, M. A. Rotea, Y. Li, “Multiple Reference FrameBased Torque Ripple Reduction in DFIG-DC System”, IEEE Transactions on Power Electronics, vol. 35, no. 5, pp. 4971–4983, 2020, doi: 10.1109/TPEL.2019.2941957.
» https://doi.org/10.1109/TPEL.2019.2941957 -
28 P. Cortes, J. Rodriguez, C. Silva, A. Flores, “Delay Compensation in Model Predictive Current Control of a Three-Phase Inverter”, IEEE Transactions on Industrial Electronics, vol. 59, no. 2, pp. 1323–1325, 2012, doi: 10.1109/TIE.2011.2157284.
» https://doi.org/10.1109/TIE.2011.2157284 -
29 C. Lascu, I. Boldea, F. Blaabjerg, W. Chen, “A class of flux observers for doubly-fed induction generators used in small power wind generation systems”, in 2013 IEEE Energy Conversion Congress and Exposition, pp. 2289–2295, 2013, doi: 10.1109/ECCE.2013.6646993.
» https://doi.org/10.1109/ECCE.2013.6646993 -
30 C. Wu, P. Cheng, H. Nian, F. Blaabjerg, “Rotor Current Oriented Control Method of DFIG-DC System Without Stator Side Sensors”, IEEE Transactions on Industrial Electronics, vol. PP, pp. 1–1, 12 2019, doi: 10.1109/TIE.2019.2956415.
» https://doi.org/10.1109/TIE.2019.2956415 -
31 C. Wu, P. Cheng, Y. Ye, F. Blaabjerg, “A Unified Power Control Method for Standalone and Grid-Connected DFIG-DC System”, IEEE Transactions on Power Electronics, vol. 35, no. 12, pp. 12663–12667, 2020, doi: 10.1109/TPEL.2020.2996267.
» https://doi.org/10.1109/TPEL.2020.2996267 -
32 V. Yaramasu, B. Wu, Model Predictive Control of Wind Energy Conversion System, chap. 3, pp. 91–116, John Wiley & Sons, Ltd, https://onlinelibrary.wiley.com/doi/abs/10.1002/9781119082989.ch3, 2017.
» https://onlinelibrary.wiley.com/doi/abs/10.1002/9781119082989.ch3