A System Based on Artificial Neural Networks for Automatic Classification of Hydro-generator Stator Windings Partial Discharges

Abstract

Partial discharge (PD) monitoring is widely used in rotating machines to evaluate the condition of stator winding insulation, but its practice on a large scale requires the development of intelligent systems that automatically process these measurement data. In this paper, it is proposed a methodology of automatic PD classification in hydro-generator stator windings using neural networks. The database is formed from online PD measurements in hydro-generators in a real setting. Noise filtering techniques are applied to these data. Then, based on the concept of image projection, novel features are extracted from the filtered samples. These features are used as inputs for training several neural networks. The best performance network, obtained using statistical procedures, presents a recognition rate of 98%.

Index Terms
Artificial Intelligence; Condition Monitoring; Hydrogenerator; Neural Networks; Partial Discharge

I. INTRODUCTION

In electric power industry, it has been observed a growing interest towards predictive maintenance (condition monitoring) [1[1] G. Stone. A perspective on Online Partial Discharge Monitoring for Assessment of the Condition of Rotating Machine Stator Winding Insulation. IEEE Electrical Insulation Magazine, vol. 28, no. 5, pp. 8-13, 2012.] for obtaining shorter equipment downtime and hence lesser costs. An important predictive maintenance technique for rotating machines is the partial discharge (PD) monitoring and analysis, which allows for the evaluation of stator insulation condition [2[2] G. Stone. Partial Discharge Diagnostics and Electrical Equipment Insulation Condition Assessment. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 5, pp. 891-904, 2005.], [3[3] G. Stone and V. Warren. Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings. IEEE Transactions on Industry Applications, vol. 42, no. 1, pp. 195-200, 2006.].

Substantial PD levels are an important symptom of stator insulation aging in rotating machines, including hydro-generators [4[4] N. Malik and A. Al-Arainy and M. Qureshi. Electrical Insulation in Power Systems. Marcel Dekker, 1998.]. If not properly treated, PDs may progressively evolve to the point of disruptive failure in insulation [5[5] R. Bartnikas. Partial Discharges: Their Mechanism, Detection and Measurement. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 9, no. 5, pp. 763-808, 2002.], [2[2] G. Stone. Partial Discharge Diagnostics and Electrical Equipment Insulation Condition Assessment. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 5, pp. 891-904, 2005.], causing great losses.

PD monitoring is often performed online, mainly to avoid shutdown of the equipment [1[1] G. Stone. A perspective on Online Partial Discharge Monitoring for Assessment of the Condition of Rotating Machine Stator Winding Insulation. IEEE Electrical Insulation Magazine, vol. 28, no. 5, pp. 8-13, 2012.]. Manned inspection of the large quantity of data generated by these measurements is unfeasible [2[2] G. Stone. Partial Discharge Diagnostics and Electrical Equipment Insulation Condition Assessment. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 5, pp. 891-904, 2005.]. Thus, it is necessary to develop intelligent systems that automatically interpret these data. A key task for these systems is the identification of the kind of insulation defect causing the partial discharges. PD source diagnosis aids in planning appropriate maintenance measures for the examined apparatus, because each class of PD source has a particular evolution rate and imposes distinct risks to insulation [6[6] IEC TS 60034-27. Rotating electrical machines - Part 27: Off-line partial discharge measurements on the stator winding insulation of rotating electrical machines. International Electrotechnical Commission, 2006.], [7[7] C. Hudon and M. Bélec. Partial Discharge Signal Interpretation for Generator Diagnostics. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 2, pp. 297-319, 2005.].

In literature, great effort has been made for PD recognition. In [8[8] J. Tang and F. Liu and Q. Meng and X. Zhang and J. Tao. Partial Discharge Recognition through an Analysis of SF6 Decomposition Products Part 2: Feature Extraction and Decision Tree-based Pattern Recognition. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 19, no. 1, pp. 37-44, 2012.], four PD types are recognized in gas-insulated substations using decision trees, based on the relative concentrations of products of SF6 gas decomposition due to partial discharges. Ma et al. [9[9] H. Ma and J. Chan and T. Saha and C. Ekanayake. Pattern Recognition Techniques and Their Applications for Automatic Classification of Artificial Partial Discharge Sources. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 20, no. 2, pp. 468-478, 2013.] compare the recognition performances of different combinations of artificial intelligence algorithms and input features. They also propose a preliminary technique to recognize simultaneous PDs sources. Sinaga et al. [10[10] H. Sinaga and B. Phung and T. Blackburn. Recognition of single and multiple partial discharge sources in transformers based on ultra-high frequency signals. IET Generation, Transmission Distribution, vol. 8, no. 1, pp. 160-169, 2014.] describe a PD classification methodology in power transformers, based on ultra-high frequency (UHF) signals. Statistical properties extracted from wavelet decompositions of UHF signals are used as input features for training an artificial neural network. In these references, as well as in most papers in literature, artificial PDs are generated in laboratory conditions to train and test proposed algorithms. The lower levels of noise and lesser ambiguity (simultaneous existing classes of PD sources) certainly result in superior recognition rates compared to a real-world application. Moreover, few works are dedicated to hydro-generators, which are equipments of higher complexity.

In this paper, we propose a methodology for automatic PD recognition in hydro-generator stator bars. Actual partial discharge samples were obtained by means of online measurements in hydrogenerators, operating in a real setting. Noise filtering techniques are developed and proposed. Such features serve as inputs for training and testing several artificial neural networks. Statistical tests are carried out to assess the performance and to pick the best neural network for classifying the PDs.

The contributions of this work are the following: (i) novel input features, based on the concept of projection; (ii) new metric for evaluating recognition performance; (iii) to cover PD recognition in hydro-generators using real-world data, which is more complex than prior works in literature.

II. Theoretical Background

A. Partial Discharges

Partial discharges are small electrical discharges that can occur in deteriorated insulation materials [3[3] G. Stone and V. Warren. Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings. IEEE Transactions on Industry Applications, vol. 42, no. 1, pp. 195-200, 2006.], [11[11] IEC 60270. High-voltage test techniques - Partial discharge measurements. International Electrotechnical Commission, 2000.]. Insulation defects represent localized regions usually with lesser permittivity than the surrounding medium. Due to the smaller permittivity, electric field is more intense within imperfections, and it may cause localized breakdown of the medium even at operating voltage, resulting in PDs [4[4] N. Malik and A. Al-Arainy and M. Qureshi. Electrical Insulation in Power Systems. Marcel Dekker, 1998.]. These imperfections are caused mainly by manufacturing deficiencies, load cycling and excessive winding vibrations [2[2] G. Stone. Partial Discharge Diagnostics and Electrical Equipment Insulation Condition Assessment. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 5, pp. 891-904, 2005.].

Partial discharges manifest physically in the form of sound, light, electromagnetic radiation and current pulses [4[4] N. Malik and A. Al-Arainy and M. Qureshi. Electrical Insulation in Power Systems. Marcel Dekker, 1998.], and therefore can be detected in several ways. The electrical and electromagnetic signals, on which most measurement methods are based, are usually of high frequency and low amplitude. These factors, along with the typical low signal-to-noise ratios found in these circumstances, make PD measurement a challenging task.

PD signals are most commonly measured using the electric method [3[3] G. Stone and V. Warren. Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings. IEEE Transactions on Industry Applications, vol. 42, no. 1, pp. 195-200, 2006.], [11[11] IEC 60270. High-voltage test techniques - Partial discharge measurements. International Electrotechnical Commission, 2000.], which detects PDs from the associated current pulses. In short, a coupling circuit is electrically connected to a point of interest in the apparatus (generally stator windings of rotating machines) to convert the current pulses to voltage signals, which in turn is transmitted by cable (in analog or digital form) or digitally via optical link to a storage system [11[11] IEC 60270. High-voltage test techniques - Partial discharge measurements. International Electrotechnical Commission, 2000.]. If the signal is transmitted in analog form, it is digitalized prior to the storage process.

Fig. 1 shows a sketch of the measurement circuit based on the electric method. The coupling circuit is a high-pass RC filter, whose parameters should be tuned to increase sensitivity to PD signals. It filters the power signals and low frequency noise. The capacitor C1 is typically of 80 pF and the resistance R1 usually ranges from 500 Ω to 2000 Ω. The digital oscilloscope performs sampling and digitalization of signals and a server stores the digital data.

Fig. 1
Sketch of circuit for measuring and registering PD signals. The sensor is the capacitive coupler C1.

Other PD measurement methods have been developed in literature. The electromagnetic method, for instance, shows the following advantages over the electric method [12[12] V. Dmitriev and R. M. S. Oliveira and F. Brasil and P. Vilhena and J. Modesto and R. Zampolo. Analysis and Comparison of Sensors for Measurements of Partial Discharges in Hydrogenerator Stator Windings. Journal of Microwaves, Optoelectronics and Electromagnetic Applications, vol. 14, no. 2, pp. 197-218, 2015.]: it is non-invasive, robust to noise and wideband.

B. Artificial Neural Networks

Artificial neural networks (ANNs) are a collection of interconnected processing units which is capable of inferring (or “learning”) relations between inputs and outputs. Their design mimics the human brain [13[13] S. Haykin. Neural Networks - A comprehensive foundation. 2nd ed. Prentice Hall, 2004.].

ANN's basic processing unit is the artificial neuron, shown in Fig. 2. The neuron applies the following mathematical operations in the inputs xi to calculate the output y:

(1) y = φ ( i ( ω i x i ) + b ) ,

where ωί are the synaptic weights, b is the bias, which serves to increase or decrease the activation function input, and φ is the activation function, which limits the neuron output to a predetermined range [13[13] S. Haykin. Neural Networks - A comprehensive foundation. 2nd ed. Prentice Hall, 2004.].

Fig. 2
Mathematical model of artificial neuron.

In order to infer more complex relations between inputs and outputs, multiple neurons are connected in several architectures. The architecture of interest in this work is the Multilayer Feedforward [13[13] S. Haykin. Neural Networks - A comprehensive foundation. 2nd ed. Prentice Hall, 2004.], shown in Fig. 3.

Fig. 3
Generic multilayer feedforward neural network.

The neural network infers the relations between inputs and outputs by means of an iterative tuning of weights during training. In the supervised learning scheme, adopted in this work, the network is presented to input samples with known outputs during the training phase. Such a correspondence between inputs and outputs is generally obtained by hand labeling [13[13] S. Haykin. Neural Networks - A comprehensive foundation. 2nd ed. Prentice Hall, 2004.]. Once trained, a neural network can classify, with some level of error, any sample (set of inputs) consistent with any of the patterns to which it has been exposed during the training process. The goal is to automatically classify samples not present in the training data set.

C. K-fold cross-validation

Evaluating the classifier performance is of fundamental importance in Machine Learning science [14[14] I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques. 3rd ed. Morgan Kaufmann, 2011.]. K-fold cross-validation (CV) allows for comparing different classifiers (and various methods) and selecting the most suitable one for a given classification problem. In general terms, the best classifier is the one that better generalizes the problem. Generalization is the ability of correctly and reliably classifying samples that were not used in training. When database is limited, K-fold crossvalidation is the most used statistical technique to estimate classifier performance [14[14] I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques. 3rd ed. Morgan Kaufmann, 2011.].

In CV, illustrated in Fig. 4, the database is randomly divided into k mutually exclusive subsets (folds) using stratified sampling, that is, classes in each fold are represented in approximately the same proportion as in the data set. One fold is taken as the test set, while the others are used for training (or training and validation, depending on the training algorithm). The error over the test fold is calculated. This process is repeated k iterations, so that each fold has been used for testing once. The overall error estimate is the average of the k test errors [14[14] I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques. 3rd ed. Morgan Kaufmann, 2011.].

Fig. 4
K-fold cross-validation. E is the overall error estimate.

III. Data Set

The data set used in this work is formed from online PD measurements performed in hydrogenerators at the Power Plants Tucuruí and Coaracy Nunes, both located in Northern Brazil. Fig. 5 illustrates our measurement procedure on a hydro-generator at Tucuruí.

Fig. 5
Online partial discharge measurement in a hydro-generator at Tucuruí Power Plant. Inset highlights the terminal box.

Capacitive couplers are installed close to several stator windings of the studied hydro-generators. Employing a measurement circuit similar to that of Fig. 1, the output transient voltage signals were measured with the acquisition system called Instrumentation for Monitoring and Analysis of Partial Discharges (IMA-DP) [15[15] H. Amorim and A. Carvalho and O. Fo. and A. Levy and J. Sans. Instrumentation for Monitoring and Analysis of Partial Discharges Based on Modular Architecture, in International Conference on High Voltage Engineering and Application (ICHVE 2008), pp. 596-599, 2008.]. This system applies several proprietary filters to the measured signal, and stores the information about the peaks of the PD signal detected during acquisition. The rest of time-domain signal is discarded. From the stored peaks, IMA-DP builds PRPD (Phase-Resolved Partial Discharge) diagrams by dividing the amplitude and phase ranges in 256 windows each, resulting in 256×256 diagrams. Also referred to as φ-q-n diagrams, PRPDs are statistical maps relating the quantity of partial discharges to their magnitude and phase of the sinusoidal wave (60 Hz). PRPDs are considered one of the most powerful tools for PD identification [7[7] C. Hudon and M. Bélec. Partial Discharge Signal Interpretation for Generator Diagnostics. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 2, pp. 297-319, 2005.].

The whole data set contains 568 PRPDs measured in real hydro-generators (Fig. 5). The collected samples were manually labeled by a human specialist among five of the most common PD sources described in IEC 60034-27-2 [16[16] IEC 60034-27-2. Rotating electrical machines - Part 27-2: On-line partial discharge measurements on the stator winding insulation of rotating electrical machines. International Electrotechnical Commission, 2012.]: internal void, slot, corona, tracking and gap discharge (Fig. 6 and Fig. 7). Internal delamination was not considered because available samples available yielded a certain degree of classification uncertainty: they can be easily misclassified as internal void, even by the human expert. The delamination type, which takes place between conductor and insulation, was also ignored due to the few samples in the data set. Also, the samples of slot and corona were merged into a single class due to their similar PRPD characteristics [7[7] C. Hudon and M. Bélec. Partial Discharge Signal Interpretation for Generator Diagnostics. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 2, pp. 297-319, 2005.], reducing the problem complexity. Fig. 6 shows the distribution of PD sources in the data set. It is clearly observed an imbalance among the classes as a result of the predominance of certain PD types (classes) in the investigated machines.

Fig. 6
Distribution of PD sources in the data set.
Fig. 7
Examples of PRPDs from the data set. (a) Internal void. (b) Slot. (c) Corona. (d) Surface tracking. (e) Gap discharges.

The PRPDs in the data set present different degrees of difficulty for recognition. Some of the samples clearly belong to their respective classes, as shown in Fig. 7. Other samples are complex, i.e., show ambiguity between two classes, intense noise and/or multiple PD sources (Fig. 8). Automatic recognition of complex patterns is difficult [16[16] IEC 60034-27-2. Rotating electrical machines - Part 27-2: On-line partial discharge measurements on the stator winding insulation of rotating electrical machines. International Electrotechnical Commission, 2012.], and their presence is expected due to the occurrence of multiple simultaneous PDs sources (of different classes) in rotating machines, and due to the intense noise and interference from power systems themselves [2[2] G. Stone. Partial Discharge Diagnostics and Electrical Equipment Insulation Condition Assessment. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 5, pp. 891-904, 2005.].

Fig. 8
Examples of complex patterns from the data base: (a) gap discharges close to internal void clouds; (b) uncertainty between slot (triangular blue contour) and corona (rounded purple contour); (c) gap discharges superposed onto internal void, as well as strong noise.

IV. The Proposed Classification Methodology

With the methodology proposed in this work, one can perform automatic recognition of the primary (dominant) PD source using artificial neural networks. The complete flowchart of the methodology is shown by Fig. 9.

Fig. 9
Flowchart of the methodology.

Three stages are considered: training, validation and testing. In the training and validation stages, the objective is to find an optimized neural network for the PD recognition task. Specifically, during training the optimal weights and biases of a neural network are calculated based on a subset of data, whereas in validation the error over a second set acts as a stopping criterion of training in order to avoid overfitting [14[14] I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques. 3rd ed. Morgan Kaufmann, 2011.]. In the test stage, samples used neither in training nor in validation steps are presented to the trained classifier in order to estimate its performance on unseen data.

The data set is static: its samples have been previously labeled. In these conditions, it is plausible to treat the data with manual techniques in order to reduce the influence features from non-dominant (or not of interest) classes (in a given sample) and/or excessively contaminated with noise that may degrade classifier learning. Also, the time for training and validation is not critical. In all stages, the measured samples are subjected to the same preprocessing techniques for noise treatment and extraction of input features, producing the data effectively presented to the ANNs.

A. Manual Removal of Class Ambiguities

This data cleaning technique consists of manually removing class ambiguities, i.e., partial discharges relative to sources apart from the PD source of interest. For example, in Fig. 8(a), the source of interest can be considered to be internal void, while gap discharges can be judged to produce ambiguities. Removing this kind of ambiguity is necessary for the training process; otherwise the classifier would blend different classes, reducing the training effectiveness.

After carefully inspecting the data base, all ambiguities clearly separable from the clouds of interest have been removed. However, it is not possible to eliminate ambiguities superposed onto the main clouds, as doing so would distort the PD pattern of interest. Clouds in PRPDs with superposed ambiguities were kept unchanged in the data base as long as the ambiguities do not significantly change input features regarding the PD source of interest, such as shape and symmetry.

Each row of Fig. 10 contains the results of ambiguity removal applied to the patterns of Fig. 8(a) and Fig. 8(c), depending on which PD source is considered to be of interest. In Fig. 10(a), there is no overlapping between gap discharges and internal void clouds. Therefore, ambiguity removal of this kind of PRPD consists of completely removing the ambiguous PD source, as shown in Fig. 10(b) and Fig. 10(c). In the PRPD of Fig. 10(d), on the other hand, some gap discharges are superposed onto internal void. In this case, all ambiguities are removed except those superposed to the primary clouds, as shown by Fig. 10(e) and Fig.10(f). Notice that elimination of superposed PDs of different classes is not necessary for proper ANN training since they do not significantly affect main features of PD clouds of interest, as depicted by the filtered PRPDs of Figs. 10(e) and 10(f).

Fig. 10
Results of ambiguity removal applied to two measured PRPDs (a and d), considering that the PD source of interest is internal void (b and e) or gap discharges (c and f).

Removal of ambiguities is the only manual step in the methodology. It is automatically performed in other works using algorithms to separate multiple simultaneous PD sources, such as clustering in time-frequency maps [6[6] IEC TS 60034-27. Rotating electrical machines - Part 27: Off-line partial discharge measurements on the stator winding insulation of rotating electrical machines. International Electrotechnical Commission, 2006.]. However, this is not possible with PRPD maps because they are based solely on PD peaks.

B. Removal of Sparse Partial Discharges

The patterns are then subjected to an automatic filtering by means of pixel submatrices, of which purpose is to remove isolated PDs. Here, PRPDs are treated as negative images, whose non-black pixels are non-zero PD counts (Fig. 11).

Fig. 11
PRPD (a) before and (b) after sparse PD removal by the pixel submatrix technique.

First, the neighborhood of each pixel is defined as the 5×5 submatrix centered in it. The filtering consists of removing pixels that are the only nonzero in their respective neighborhoods. Fig. 11 shows the results of such filtering applied to a PRPD from the data set.

The submatrix dimension was chosen empirically, in order to keep the algorithm conservative. With this submatrix size, the algorithm eliminates isolated PDs and preserves the main PD clouds, as one notices in Fig. 11.

C. Feature Extraction

PRPDs from the database are 256×256 matrices, totaling 65,536 elements. Using all PRPD points as input features would incur in a problem of very high dimensionality for ANNs. In this situation, many features are of minor relevance, and a single point contributes very little to differentiate among classes [14[14] I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques. 3rd ed. Morgan Kaufmann, 2011.]. Therefore, it is convenient to extract from the filtered samples a subset of features of more significance for performing the classification of the PD type.

The input features used in this work are novel. They are based on the projection of normalized PRPD counts onto the vertical (amplitude) and horizontal (phase) axes. The projections onto amplitude and phase were calculated for each polarity separately in order to properly characterize clouds of positive and negative PD amplitudes. This division is important to define, for example, the presence of symmetric or non-symmetric clouds or the shape of the clouds. These features can be determinant to properly perform PD classification [7[7] C. Hudon and M. Bélec. Partial Discharge Signal Interpretation for Generator Diagnostics. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 2, pp. 297-319, 2005.], [16[16] IEC 60034-27-2. Rotating electrical machines - Part 27-2: On-line partial discharge measurements on the stator winding insulation of rotating electrical machines. International Electrotechnical Commission, 2012.].

Given a PRPD map, the first step is to divide (normalize) all PD counts by the maximum counting found in the map, resulting in a m × n matrix M. Normalization is necessary because it eliminates the effect of random variables related to PD activity and measurement procedures, such as the severity of the insulation defect and its distance to the sensor, and time of acquisition. The projections onto the positive and negative amplitudes Pa+ and Pa-, and onto phase in positive and negative polarities Pf+ and Pf- are calculated using (2) and (3), respectively, which are given by

(2) P a + ( i ) = j = 1 n M ( i , j ) , i { 1 , 2 , , m 2 } P a ( i ) = j = 1 n M ( i + m 2 , j )

and

(3) P f + ( j ) = i = 1 m / 2 M ( i , j ) , j { 1 , 2 , , n } P f ( j ) = i = 1 m / 2 M ( i + m 2 , j ) .

In (2) and (3), M(i, j) is the normalized quantity of PDs at magnitude i and phase j.

The amplitude range containing the relevant PRPD information is not fixed across samples. In order to obtain this range, let i0 and i1 be the highest absolute positive and negative amplitudes. The amplitude ranges are bounded by max(i0, i1) and -max(i0, i1), as illustrated by Fig. 12. Next, 64 points are interpolated from both amplitude projections within the amplitude range, and 64 points are interpolated from the phase projections in both polarities over the 60 Hz phase cycle. Fig. 12 illustrates this feature extraction procedure.

Fig. 12
Feature extraction. Input features are red points. (a) PRPD. (b) Projections onto amplitude. (c) Projections onto phase. (d) PRPD surface representation in 3-D space along with the amplitude and phase projections, which are perceived to be analogous to shadows of the PRPD surface.

The 64 interpolated points from each of the four projections are the data effectively presented to ANNs, totaling in 256 input features. This represents a significant dimensionality reduction. Moreover, in Fig. 12 it can be observed that amplitude projections preserve the asymmetry between positive and negative PDs, while phase projections indicate the cloud shape and its positioning along the 60 Hz phase cycle. With the developed procedure, one can obtain features compatible with the PD characteristics mentioned in IEC 60034-27-2 [16[16] IEC 60034-27-2. Rotating electrical machines - Part 27-2: On-line partial discharge measurements on the stator winding insulation of rotating electrical machines. International Electrotechnical Commission, 2012.] to describe each PD type in qualitative terms, indicating that the selected input features can, in fact, be used to classify hydro-generator PDs.

D. Training and Validation of Neural Networks

Neural networks were trained in such a way to reduce the influence of ANN topology and of the following random variables: data sampling and initial weights. The topology (number of hidden layers and number of neurons per hidden layer) is a free parameter of neural networks, and its optimal configuration is not known beforehand. For this reason, ANNs of several topologies were trained. In order to mitigate potential performance inclinations due to the particular distribution of data that compose the training, validation and test sets, each topology was trained with several partitions of the data, using the strategy of stratified 4-fold cross-validation (CV) [14[14] I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques. 3rd ed. Morgan Kaufmann, 2011.], repeated 10 times. Each CV partition consists of selecting two folds to form the training set, one for validation and the other for testing. The 12 possible partitions are considered for each repetition of cross-validation.

In a given partition, the training samples are presented to the ANN, and its weights and biases are updated iteratively in this work by means of the Scaled Conjugate Gradient Backpropagation algorithm (SCG) [17[17] M. MØller. A Scaled Conjugate Gradient Algorithm for Fast Supervised Learning. Neural Networks, vol. 6, no. 4, pp. 525-533, 1993.]. The validation error is calculated. In order to avoid overfitting [14[14] I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques. 3rd ed. Morgan Kaufmann, 2011.], this process is repeated until the validation error starts to increase. Once trained, the neural network classifies the test set, and the resulting error is used to estimate the error over unknown samples (see Section V).

Initial weights have a major influence on training. The training of neural networks is a complex optimization problem. The goal is to find the combination of weights/biases (solution) that minimizes the difference (error function) between the ANN output and target classes. From a random guess, the SCG algorithm moves the solution iteratively in the direction of the negative of the error function gradient, converging to the closest point with zero gradient. Since the error function is generally nonconvex and multimodal [13[13] S. Haykin. Neural Networks - A comprehensive foundation. 2nd ed. Prentice Hall, 2004.], gradient-based algorithms tend to get “stuck” at the closest local minimum. Initial solutions are totally random parameters, and the convergence to local optima is a characteristic of the training algorithm.

In order to mitigate the mentioned influence of the initial values of network weights on training, for each topology, 50 ANNs of different initial weights (defined randomly) were trained in each CV partition. Moreover, all ANNs have 256 input neurons, 4 output neurons, hyperbolic tangent activation function in hidden layers and softmax function in output layer.

V. Results and Discussion

A. Analysis of ANN recognition performances

Considering the training and validation stages, as described in Section IV (Fig. 9), the patterns were noise-filtered and its features extracted. Then, such features were used as inputs of neural networks.

All the trained ANNs were evaluated one by one in the following way. Each ANN is executed over the test fold relative to the CV partition in which it was trained. For each of the C classes, it is calculated the true positive rate per class (TS), which is equal to the rate of samples of a given class that were correctly classified. Mathematically, for class i, we have

(4) T s i = n i , i j = 1 C n i , j ,

where ni,j is the number of samples known to be of class i but predicted to be of class j. Then, we calculate the average μTs and standard deviation σTs of the C true positive rates per class:

(5) μ T s = 1 C i = 1 C T S i

and

(6) σ T s = 1 C i = 1 C ( T S i μ T s ) 2 .

The recognition performance of each ANN is quantified by the novel metric δ, defined as:

(7) δ = μ T s + 1 1 + σ T s .

As observed in Equation (7), δ has two contributions: one increases with μTs and the other decreases with σTs. The first term is associated to the classifier's average performance across classes. The second term accounts for the variability of true positive rates per class. It distinguishes classifiers with similar μTs by ranking higher those with more uniform success rates across classes (less biased). The idea of δ is to appropriately rank classifiers that perform similarly well at recognizing samples of different classes. Thus, a desirable classifier is that with high recognition rates for any class (high μTs), with rates that do not differ much from one another (low σTs).

Global success rate (rate of correctly classified samples relative to the size of the data set), a typically used criterion for evaluating classifiers [14[14] I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques. 3rd ed. Morgan Kaufmann, 2011.], is not suitable for problems with imbalanced data sets because it is biased towards the classes with most samples. Also, since δ is calculated over samples not used in training (test set), it estimates a classifier's generalization capabilities. It is worth mentioning that δ is a generic metric; it can be used to evaluate any classifier in any Machine Learning application involving the recognition of a single class per sample.

In the following results, the neural network topology is expressed as the number of hidden neurons separated by dashes. NHL is the topology with no hidden layers: inputs are directly connected to output neurons. In addition, due to the fact that the initial weights are not related to the classification problem itself (Section IV.D), their influences are minimized by showing results for the 25% best neural networks of each topology.

Fig. 13 contains the average μ(δ) and standard deviation σ(δ) of δ performances of all ANNs of each topology. Fig. 14 shows these statistics for the 25% best ANNs of each topology. These data measure the influence of topology on performance, after varying initial weights and CV partitions.

Fig. 13
Average (line) and standard deviation (vertical bars) of δ performances of all networks for each topology. Vertical bars are the size of two standard deviations.
Fig. 14
Average (line) and standard deviation (vertical bars) of δ performances of the 25% best networks of each topology. Vertical bars are the size of two standard deviations.

Similar interpretation of δ is used to rank the different topologies: the best topologies are those whose networks present high average performances (high μ(δ)) and low standard deviation (σ(δ)) for the obtained values of δ. It is worth mentioning that μ(δ) and σ(δ) are different than μTs and σTs from (5) and (6), respectively. The latter two indicate the variation of performance across classes, and are calculated for each network in order to calculate its performance δ. The former two, on the other hand, express the variation of δ performances of several networks for a given topology, and are used to select the most suitable topology (which is a free parameter of ANNs) for the problem at hand.

In Fig. 14, due to the reduced influence of random initialization of weights, one can observe that the average and standard deviation of δ are relatively constant over the range between topologies 50 and 256-5. Topologies 10, 20 and 40 presented larger μ(δ) and similar σ(δ). The worst performance was observed for NHL (low average and large standard deviation of δs), indicating that the use of hidden layers is important to capture the non-linear relations between inputs and outputs. Similar observation was made in [9[9] H. Ma and J. Chan and T. Saha and C. Ekanayake. Pattern Recognition Techniques and Their Applications for Automatic Classification of Artificial Partial Discharge Sources. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 20, no. 2, pp. 468-478, 2013.]. Bad results were also obtained for topology 256-256, probably because the number of samples was insufficient to train a network with so many weights and biases. Topology 10 is considered to be the most favorable on average, because it is the simplest configuration (low number of weights) of which most networks presented good generalization (high average and low dispersion of values of δ).

The curve in Fig. 13 presents higher variation in average δ across topologies, as well as much higher standard deviation due to random weight initialization influence. The poorer results are due to networks trained from inappropriate initial weights. Even with those differences, the best and worst topologies are the same as those mentioned above for Fig. 14, showing the representativeness of the 25% best networks in relation to all networks.

The next results are relative to the most favorable topology 10, and are illustrated by means of confusion matrices. A confusion matrix shows classification results intuitively [14[14] I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques. 3rd ed. Morgan Kaufmann, 2011.]. Rows and columns are relative to true and predicted classes, respectively. Element (i,j) is equal to the number of samples known to be of class i classified as being of class j. Evidently, the correct classifications are evaluated by the elements in main diagonal.

To obtain a picture of average performance of all networks of topology 10, their confusion matrices over the test set were summed element-wise. Each element was calculated as the percent ratio relative to the sum in the respective row, resulting in the matrix shown in Fig. 15.

Fig. 15
Element-wise average confusion matrix of all ANNs of topology 10 over the test set.

The same is performed in Fig. 16 for the 25% best networks of topology 10. In Fig. 16, the interpretation for element (1,3), for example, is that 6.20% of internal void samples were misclassified as tracking by the best networks, on average. The classes with the highest success rates were slot/corona and gap discharges, probably because these are the classes with the highest number of samples (Fig. 6). Smaller success rates were obtained for the other classes, indicating that the methodology can be worse at recognizing internal void and tracking patterns. Tracking samples are primarily misclassified as gap, while the inverse happens in a reduced degree. Confusion between tracking and gap discharges is reasonable, as these are the only classes formed by clouds of discharges far from the central region of PRPD. The same conclusions can be drawn from Fig. 15. The differences between these two Figures - also caused by suboptimal initial weights - are lower recognition rates and consequently more frequent misclassifications.

Fig. 16
Element-wise average confusion matrix of the 25% best ANNs of topology 10 over the test set.

The primary goal is to find an optimized network for trustworthy classifying PDs. Fig. 17 shows the confusion matrix of the best neural network (largest δ) of topology 10 over the test set. High recognition rates (of at least 94%) were obtained for all classes.

Fig. 17
Confusion matrix of the best ANN of topology 10 over the test set.

B. Graphical User Interface

A graphical user interface (GUI) was developed in order to display in an interactive way the results of PD classification and to automate the classification process. The classification is performed by a previously trained ANN by executing the test stage shown in Fig. 9.

The developed interface is shown in Fig. 18. It displays, from left to right, the PRPD of current sample, amplitude and phase projections, and pertinence probabilities of the current sample to the different classes. Pertinence probabilities are proportional to the ANN outputs. The final PD classification - the class with the highest pertinence - is shown in the lower right corner.

Fig. 18
The graphical user interface (GUI) developed in this work to aid in decision making. Pattern was correctly classified as internal void.

Understanding the interface's intuitive indications does not require specialized operators, reducing training and operational costs and facilitating the application of the methodology in a real monitoring system by non-specialized human operators.

VI. Final Remarks

In this work, a methodology for automatic partial discharge classification using neural networks is presented. The neural networks were trained to classify a single PD source using novel features extracted from PRPD maps.

Several networks were trained, and their performances were assessed and compared statistically. Topology with 1 hidden layer and 10 hidden neurons was found to be the most favorable on average. The best network obtained presented very good performance. PD sources slot/corona and gap discharge were the classes most correctly classified among the networks.

For future works, the authors suggest investigating PD separation algorithms for detecting and classifying multiple PD sources. Considering all PD sources described in standards and solving the issues of similarities between slot and corona are problems of great interest.

REFERENCES

  • [1]
    G. Stone. A perspective on Online Partial Discharge Monitoring for Assessment of the Condition of Rotating Machine Stator Winding Insulation. IEEE Electrical Insulation Magazine, vol. 28, no. 5, pp. 8-13, 2012.
  • [2]
    G. Stone. Partial Discharge Diagnostics and Electrical Equipment Insulation Condition Assessment. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 5, pp. 891-904, 2005.
  • [3]
    G. Stone and V. Warren. Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings. IEEE Transactions on Industry Applications, vol. 42, no. 1, pp. 195-200, 2006.
  • [4]
    N. Malik and A. Al-Arainy and M. Qureshi. Electrical Insulation in Power Systems. Marcel Dekker, 1998.
  • [5]
    R. Bartnikas. Partial Discharges: Their Mechanism, Detection and Measurement. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 9, no. 5, pp. 763-808, 2002.
  • [6]
    IEC TS 60034-27. Rotating electrical machines - Part 27: Off-line partial discharge measurements on the stator winding insulation of rotating electrical machines. International Electrotechnical Commission, 2006.
  • [7]
    C. Hudon and M. Bélec. Partial Discharge Signal Interpretation for Generator Diagnostics. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 12, no. 2, pp. 297-319, 2005.
  • [8]
    J. Tang and F. Liu and Q. Meng and X. Zhang and J. Tao. Partial Discharge Recognition through an Analysis of SF6 Decomposition Products Part 2: Feature Extraction and Decision Tree-based Pattern Recognition. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 19, no. 1, pp. 37-44, 2012.
  • [9]
    H. Ma and J. Chan and T. Saha and C. Ekanayake. Pattern Recognition Techniques and Their Applications for Automatic Classification of Artificial Partial Discharge Sources. IEEE Transactions on Dielectrics and Electrical Insulation, vol. 20, no. 2, pp. 468-478, 2013.
  • [10]
    H. Sinaga and B. Phung and T. Blackburn. Recognition of single and multiple partial discharge sources in transformers based on ultra-high frequency signals. IET Generation, Transmission Distribution, vol. 8, no. 1, pp. 160-169, 2014.
  • [11]
    IEC 60270. High-voltage test techniques - Partial discharge measurements. International Electrotechnical Commission, 2000.
  • [12]
    V. Dmitriev and R. M. S. Oliveira and F. Brasil and P. Vilhena and J. Modesto and R. Zampolo. Analysis and Comparison of Sensors for Measurements of Partial Discharges in Hydrogenerator Stator Windings. Journal of Microwaves, Optoelectronics and Electromagnetic Applications, vol. 14, no. 2, pp. 197-218, 2015.
  • [13]
    S. Haykin. Neural Networks - A comprehensive foundation. 2nd ed. Prentice Hall, 2004.
  • [14]
    I. Witten and E. Frank and M. Hall. Data Mining: Practical Machine Learning Tools and Techniques 3rd ed. Morgan Kaufmann, 2011.
  • [15]
    H. Amorim and A. Carvalho and O. Fo. and A. Levy and J. Sans. Instrumentation for Monitoring and Analysis of Partial Discharges Based on Modular Architecture, in International Conference on High Voltage Engineering and Application (ICHVE 2008), pp. 596-599, 2008.
  • [16]
    IEC 60034-27-2. Rotating electrical machines - Part 27-2: On-line partial discharge measurements on the stator winding insulation of rotating electrical machines. International Electrotechnical Commission, 2012.
  • [17]
    M. MØller. A Scaled Conjugate Gradient Algorithm for Fast Supervised Learning. Neural Networks, vol. 6, no. 4, pp. 525-533, 1993.