Ventilated cladding systems: structural and drainability performance criteria

Revestimento não-aderido: critérios desempenho estrutural e drenabilidade

Abstract

Cladding systems have significant effect on the performance and durability of building façades, contributing to the building watertightness, property valuation, aesthetic finishing, and decoration. Non-adherent cladding, also named rainscreen cladding or ventilated cladding, is currently used in residential and commercial buildings, new constructions, or retrofit operations, and it is considered an efficient measure to improve the moisture safety of building envelopes. Therefore, the absence of Brazilian normalization to ventilated cladding systems is one of the difficulties limiting its increased local application. In Brazil, a technical standard, NBR 15575, parts 1-6, (2013), establish the general performance requirements and test methods to evaluate residential building systems including structure, wall, floor, coverage, and hydraulic installation. However, this standard cannot be integrally applied to the cladding systems because it was developed considering the vertical wall system as a whole. In this study, we propose the criteria and test methods for assessing ventilated cladding systems while taking into account the structural safety (wind loads resistance, hard and soft impact resistance) and drainability requirements. The following activities are performed: literature review, practical case study, and tests on prototypes for validation of the proposal. The tests allow verification of the feasibility of the criteria and tests methods proposed. In addition, the proposal makes it possible to guide design, construction, and maintenance needs, thereby inducing the growth of this technology in Brazil.

Keywords:
Ventilated cladding systems; Rainscreen claddings; Building Performance criteria; Moisture safety; Test methods

Resumo

O sistema de revestimento não-aderido (RNA) influencia o desempenho da fachada dos edifícios, pois impacta na durabilidade, estanqueidade à agua, estética e valorização do imóvel. O RNA, também denominado pelo mercado como fachada ventilada, é frequentemente utilizado em fachadas de edifícios residenciais, comerciais, novas construções, renovações ou retrofit, considerado também uma forma eficiente de reduzir os problemas de umidade da fachada. Entretanto, a ausência de normalização técnica específica limita o crescimento do uso desta tecnologia no Brasil. Além disso, no Brasil, existe a NBR 15575, partes 1-6 (2013), que estabelece critérios de desempenho, bem como os respectivos métodos de avaliação para avaliar os principais sistemas do edifício: estrutura, piso, vedações verticais, cobertura e instalações. Entretanto, esta norma pode somente ser parcialmente adotada para o RNA, pois a NBR apresenta critérios considerando toda a fachada e, não somente, o revestimento. No presente artigo são propostos critérios de desempenho e métodos de ensaio aplicados para RNA, particularmente abordando os requisitos de segurança estrutural (resistência a cargas de vento, e a impactos de corpo mole e corpo duro) e drenabilidade. Para este estudo, as seguintes atividades foram realizadas: revisão bibliográfica, estudo de caso e ensaios em protótipo para validar a proposta de critérios e métodos de ensaios.

Palavras-chave:
Fachada ventilada; Revestimento Não-Aderido; Critérios de desempenho; Resistencia a umidade; Métodos de Ensaio

Introduction

Façade systems are comprised of several layers such as a wall and cladding, of which the latter is the most exterior layer and it may or may not be bonded directly (adhered) to the substrate (wall).

According to some previously reported publications by Resende, Barros e Medeiros (2001)RESENDE, M. M.; BARROS, M. M. S. B.; MEDEIROS, J. S. A Influência da Manutenção na Durabilidade dos Revestimentos de Fachada de Edifícios. In: WORKSHOP SOBRE DURABILIDADE DAS CONSTRUÇÕES, 2., São José dos Campos, 2001. Anais... São José dos Campos, 2001., Ribeiro and Barros (2010)RIBEIRO, F. A.; BARROS, M. M. S. B. Juntas de Movimentação em Revestimentos Cerâmicos de Fachadas. São Paulo: PINI, 2010., and Becere (2007)BECERE O. H. Revestimentos de Ligantes Sintéticos: proposta de métodos de ensaios para avaliação de desempenho. São Paulo, 2007. Dissertação (Mestrado em Engenharia Civil) - Instituto de Pesquisas Tecnógicas, São Paulo, 2007., a cladding system has a significant influence on the performance and durability of a façade as it contributes to the building watertightness, valorization, aesthetic finishing, and decoration.

One of the cladding technologies currently being used in residential and commercial buildings, new construction, or retrofitting (Figure 1), is the non-adherent cladding system, also named as rainscreen cladding or ventilated cladding. In such a system, there is an air space between the cladding elements and external wall, and the air space is always drained and may be kept ventilated. Usually, the elements used as the external cladding include extruded ceramic tiles, porcelain tiles, fiber cement boards, aluminum composite panels, and phenolic boards.

Employing rainscreen and ventilated cladding is a common measure to improve the moisture safety of building envelopes, and in addition it serves as a capillary break and a drainage plane between the exterior climate and the inner group of structural elements and substrate (STRAUBE; FINCH, 2009STRAUBE, J.; FINCH, G. Ventilated Wall Claddings: review, field performance, and hygrothermal modeling. Research Report - 0906, 2009. Available on: <http://buildingscience.com>. Acess in: 15 apr. 2016.
http://buildingscience.com...
; LANGMANS; ROELS, 2015LANGMANS, J.; ROELS, S. Experimental Analysis of Cavity Ventilation Behind Rainscreen Cladding Systems: a comparison of four measuring techniques. Building and Environment, v. 87, fev, 2015.).

Presently, in Brazil, several companies are providing ventilated cladding systems and their use is increasing (ARCO, 2012ARCO. Fachadas Ventiladas no Mercado Brasileiro. Revista Finestra, v. 77, nov. 2012. Available on: <https://arcoweb.com.br/finestra/tecnologia/tecnologia---especial-fachadas-fachadas-ventiladas>. Acess in: 01 apr. 2016.
https://arcoweb.com.br/finestra/tecnolog...
). However, there are no technical standards or regulatory documents that specify and set guidelines to design, build, and maintain cladding systems, and neither there is a performance assessment concerning their safety, habitability, durability, serviceability, and maintainability.

Therefore, the lack of Brazilian normalization in reference to ventilated cladding systems is one of the difficulties in homogenizing their design, construction, and use while taking into account aspects related to safety, habitability, durability, and maintainability. Consequently, this impacts the decision-making phase in which the façade technology is selected.

In Brazil, NBR 15575 (ABNT, 2013ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 15575: edificações habitacionais: desempenho. Rio de Janeiro, 2013.), a general performance standard applied to residential buildings, sets the requirements and evaluation methods for the five most important building elements, namely, structure, wall, floor, coverage, and hydraulic installation. However, this standard cannot be adopted for the cladding system as it applies to the entire wall system. Among the national standards, NBR 10821 (ABNT, 2011aASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 10821: esquadrias para edificações: parte 2: esquadrias externas: requisitos e classificação. Rio de Janeiro, 2011a.) provides some of the requirements and evaluation methods for structural performance (wind loads) and durability that can be adopted for the ventilated cladding systems.

Among the foreign documents and standards, some items of the American Society for Testing and Materials (ASTM) can be used as a reference to perform the technical assessment of the cladding systems, for instance, these systems must provide airtightness (AMERICAN…, 2012AMERICAN SOCIETY FOR TESTING AND MATERIALS. ASTM E 283: standard test method for determining rate of air leakage through exterior Windows, curtain walls, and doors under specified pressure differences across the specimen. Philadelphia, 2012.), evenly distributed loads (AMERICAN…, 2014AMERICAN SOCIETY FOR TESTING AND MATERIALS. ASTM E 330: standard test method for structural performance of exterior Windows, doors, skylights and curtain walls by uniform static air pressure difference. Philadelphia, 2014.), and resistance to water pressure (AMERICAN…, 2009AMERICAN SOCIETY FOR TESTING AND MATERIALS. ASTM E 331: standard test method for water penetration of exterior Windows, skylights, doors, and curtain walls by uniform static air pressure difference. Philadelphia, 2009.).

The European Organization for Technical Assessment (EOTA) published, in June 2012, the European Technical Approval Guideline (ETAG 034) (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.) that is a regulatory document establishing the performance requirements and evaluation methods for cladding systems by considering their mechanical strength and stability, fire safety, safety in use, protection against noise, energy savings, thermal characteristic, and durability.

There are several studies regarding ventilated cladding systems, however, most of them are related to the improvement of the thermal and acoustic performance in buildings in countries such as Spain (SANJUAN et al., 2011SANJUAN, C. et al. Energy Performance of an Open-Joint Ventilated Façade Compared With a Conventional Sealed Cavity Façade. Solar Energy, v. 85, n. 9, p. 1851-1863, 2011.) and Italy (MARINOSCI; SEMPRINI; MORINI, 2014MARINOSCI, C.; SEMPRINI, G.; MORINI, G. L. Experimental Analysis of the Summer Thermal Performances of a Naturally Ventilated Rainscreen Façade Building. Energy and Buildings, v. 72, p. 280-287, 2014.). Although some of these studies have been conducted in countries with a climate similar to that of Brazil, many of these results cannot be adopted without a prior analysis and consideration of the Brazilian reality and context, such as the surroundings of the building, microclimate, and use.

Therefore, this paper proposes the performance criteria and tests methods for assessing ventilated cladding systems with a ventilated joint between the cladding elements (unsealed joint) while considering the structural (wind load resistance, hard and soft impact resistance) and drainability requirements. The results of the assessment will serve as a guide for designing, construction, and maintenance, and consequently, will increase the growth of this technology application in Brazil.

It is important to highlight that the proposed performance criteria and tests methods for assessing Brazilian ventilated cladding systems will be useful to other countries that like Brazil do not have a confident and abounding standardization for this product. Furthermore, though foreign standards or regulations such as ASTM and ETAG do exist, it is not possible to adopt them in the Brazilian context without appropriate adaptation.

Ventilated cladding systems with open joints do not have to be watertight. However, they must provide protection such that they reduce the water incidence into the substrate (wall), which is the rainscreen phenomenon (ROUSSEAU; POIRIER; BROWN, 1998ROUSSEAU, M. Z.; POIRIER, G. F.; BROWN, W. C. Pressure Equalization in Rainscreen Wall Systems. Construction Technology Updates no. 17. Institute for Research in Construction, National Research Concil of Canada, 1998.). This performance for reducing the water incidence into the substrate is known as the drainability requirement; it is the capacity of the cladding to drain out the water that penetrates into the air space or the condensed water, with the aim of reducing the moisture damage on the building façade.

Moisture accumulation in the air space between the cladding and substrate can facilitate migration of water into the building over time, which can in turn generate condensed water for the useful life of the system and cause staining and dirt on the external surface of the cladding (TRECHSEL; BOMBERG, 2009TRECHSEL, H. R.; BOMBERG, M. T. Moisture Control in Buildings: the key factor in mold prevention. Baltimore, 2009.). Contribution of the ventilated cladding to the façade watertightness exhibited in the drainability assessment suggests conduction of a study to optimize the waterproof products applied to the substrate.

The requirements hereby discussed can be adopted by several configurations of ventilated claddings independently of the cladding elements or fixation devices. Therefore, we will not discuss the individual characteristics of each component that forms the cladding system.

This paper is divided into the following six parts:

  • (a) purpose and introduction;

  • (b) brief description of the ventilated cladding system;

  • (c) research method;

  • (d) proposed Performance Criteria;

  • (e) methods and test result (proposal validation); and

  • (f) conclusions.

In this paper, we have adopted the following terminology (from ETAG034 (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.)):

  • (a) air space: space between the cladding and substrate.

  • (b) cladding kit or cladding system: is a specific kit made of an external cladding and defined fixing devices.

  • (c) substrate: refers to a wall that meets the necessary airtightness and mechanical strength requirements (resistance to static and dynamic loads).

  • (d) subframe: an intermediate assembly of vertical and/or horizontal metal profiles, located between the cladding elements and the substrate.

  • (e) cladding element: sheet, tile, board, panel or cassette made of durable material applied at the external face of a wall such as: fiber cement, stone, ceramics, metal, plastics, brick slips, etc.

Figure 1
Façade before and after the retrofit as cited by Machado (2012)MACHADO, A. L. A. Diretrizes de Projeto Para Revestimentos Não Aderidos de Fachada Constituídos de Placas Cerâmicas Extrudadas. São Paulo, 2012. Dissertação (Mestrado em Engenharia Civil) - Instituto de Pesquisas Tecnológicas, São Paulo, 2012.

Brief description of the ventilated cladding system

Marble and granite associated with mechanical fixings were used in the Kaiser Franz Josef Project at the onset of the 20th century, which is one of the first records of a ventilated cladding application. A similar cladding was used during the construction of the São Leopoldo church in Steinhoff, Austria, between 1905 and 1909; marble claddings 20-mm thick was mechanically fixed to the substrate via copper anchors (PATÓN, 1995PATÓN, V. El Nascimiento de Uma Técnica. Tectónica Cerramientos Pesados: Aplacados y Panales - Envolventes (II). Barcelona, v. 2, p. 4-11, 1995.).

In the recent past, the Institute for Research and Coordination in Acoustics/Music (IRCAM), stands out as one of the first buildings in the 1970s to apply a ventilated cladding on its façade. Renzo Piano and Richard Rogers have designed the façade using ceramic claddings (PIANO, 2016PIANO, R. Fachada do IRCAM Institut de Recherche et Coordination Acoustique/Musique. Available: <http://www.rpbw.com/project/12/ircam>. Acess in: 23 nov. 2016.
http://www.rpbw.com/project/12/ircam...
).

Presently, there are several materials such as porcelain tiles, ceramics, fiber cement panels, stones, metal, resin mortar, and others chosen as cladding elements so that numerous architectural solutions are possible during the façade design.

Ventilated cladding is wrongly associated with ventilated façade, curtain walls, double skin façade, and other technologies with similar aspects (SIQUEIRA JÚNIOR, 2003SIQUEIRA JÚNIOR, A. A. Tecnologia de Fachada-Cortina Com Placas de Grês Porcelanato. São Paulo, 2003. Dissertação (Mestrado em Engenharia Civil) - Escola Politécnica, Universidade de São Paulo, São Paulo, 2003.). The ventilated cladding kit is the most external layer of the wall and it only has the cladding function contributing to the façade watertightness, valorization, aesthetic finishing, and decoration.

Therefore, the ventilated cladding kit is a specific kit made of an external cladding, defined for fixed devices that are normally, but not always, delivered together on site. The cladding is mechanically fixed to the wall (substrate) using a subframe. The space between the cladding element and wall is intended to be a ventilated air space (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.; VEDOVELLO, 2012VEDOVELLO, C. A. S. Gestão de Projetos de Fachadas. São Paulo, 2012. Dissertação (Mestrado em Engenharia Civil) - Escola Politécnica, Universidade de São Paulo, São Paulo, 2012.).

According to ETAG 034 (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.), external wall claddings are considered ventilated when the distance between the cladding elements and substrate (ventilation air space) is at least 20 mm. In addition, the ventilation openings are envisaged, as a minimum, at the building base point and at the roof edge with cross-sections of at least 50 cm2 per linear meter.

Cladding kits have different configurations based on their fixing devices and cladding elements as shown in Table 1 and Figure 2.

Table 1
Ventilated Cladding configurations

Figure 2
External claddings parts

The layout of the subframes varies according to the design, cladding elements, dimensions, substrate, and construction details.

Among the ventilated cladding kit alternatives, Machado (2012)MACHADO, A. L. A. Diretrizes de Projeto Para Revestimentos Não Aderidos de Fachada Constituídos de Placas Cerâmicas Extrudadas. São Paulo, 2012. Dissertação (Mestrado em Engenharia Civil) - Instituto de Pesquisas Tecnológicas, São Paulo, 2012. and Siqueira Junior (2003)SIQUEIRA JÚNIOR, A. A. Tecnologia de Fachada-Cortina Com Placas de Grês Porcelanato. São Paulo, 2003. Dissertação (Mestrado em Engenharia Civil) - Escola Politécnica, Universidade de São Paulo, São Paulo, 2003. explain that aluminum subframes anchored to the substrate are commonly used in Brazil.

Anchoring devices are responsible for fixing the subframe to the substrate and transferring the cladding loads to the building structure. The anchors can be classified into two groups. The first group includes cast-in-place anchors that are installed during concreting or other substrate execution. The second group is the post installation anchors that are fastened to the finished substrate.

Fixing devices are designed considering the material of the cladding elements. The fixings can be clips, screws, and nails, which respect the design solutions. The criteria and test methods we have proposed have the potential to assess the performance of all the cladding solutions (configurations illustrated in Table 1).

Research methods

The current work has been developed based on the the following activities:

  • (a) bibliographical review: information relating to ventilated cladding systems reviewed, for instance, manuscripts, theses, and national and international technical standards. The main bibliography is ETAG 034, the basis of the proposals set in this work;

  • (b) case study: design analyses and visits to a building with ventilated cladding kits were conducted. This study was performed in the city of São Paulo, Brazil. Analysis of the design and construction aspects of this case study allowed the development of an understanding of the on-site application of the system. The feasibility of meeting the performance criteria and ability to perform the respective tests methods was verified by conducting the tests on the prototypes (described later on item “c”) that were designed and executed taking into account the cladding kit of the case study; and

  • (c) tests on the prototypes for verification of the feasibility of the proposals: tests were performed to verify the structural and drainability performance taking into account the criteria and the proposed tests methods. For this purpose, prototypes were built in 2015 in the Laboratory of Constructive Systems and Components (LCSC) of the Institute for Technological Research of the State of São Paulo (IPT). The descriptions of the prototypes (specimens assembled in lab) are presented in item 5. The tests aim to verify the feasibility of the adoption of the proposed criteria and tests methods, and also evaluate the performance of the cladding system considered. For assembling the specimen, we adopted a cladding system similar to the building in the case study. The specimens were constructed to simulate the use conditions, including the air space and open joints.

Proposed performance criteria

Structural performance

The ventilated cladding system is not responsible for the stability and structural performance of the building. However, it is required to support its non-load bearing parts and transmit wind loads to the main structure without one of its parts falling and endangering the users.

Furthermore, the cladding kits must be stable to the combined stresses generated by the normal loads such as regular weight, temperature, humidity, and shrinkage, as well as movements of the substrate, direct impacts (soft and hard impacts), and wind forces (pressure and suction). Therefore, the following aspects must be considered to calculate and evaluate the structural performance:

  • (a) normal load resistance: the system should support its own weight without excessive deformation and shattering;

  • (b) impact load resistance: the system must be designed to maintain its stability when submitted to impacts caused by regular use. Accidents, maintenance activity, or vandalism actions caused by widespread impacts should not cause damage resulting in injuries to the users, such as those inflicted by sharp edges or the falling of components on the users. In addition, impact damage should not crash the system, thereby compromising the satisfaction of the performance requirements. In case of a rupture, the cladding elements cannot present sharp edges and their surface should not cause bodily harm to users or bystanders;

  • (c) wind resistance: the cladding system must exhibit an appropriate mechanical resistance to the forces of pressure, suction, and vibration owing to the wind; and

  • (d) hygrothermal variations resistance: the cladding system must withstand movements caused by humidity and temperature changes, except at the structural joint where special precautions have to be taken in the design.

Once the main loads that the cladding kits will be subjected to (items "a" to "d") are calculated, the subframe must be assigned dimensions according to the relevant technical standards. In the Brazilian context, the standards are NBR 8800 (ABNT, 2008ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 8800: projetos de estruturas de aço e de estruturas mistas de aço e concreto de edifícios. Rio de Janeiro, 2008.), NBR 6123 (ABNT, 1988ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6123: forças devidas ao vento em edificações: procedimento. Rio de Janeiro, 1988.), and NBR 14762 (ABNT, 2010ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 14762: dimensionamento de estruturas de aço constituídas por perfis formados a frio. Rio de Janeiro, 2010.).

The fixing devices (screw, anchors, and nails) must be evaluated according to NBR 14827 (ABNT, 2002aASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 14827: chumbadores instalados em elementos de concreto ou alvenaria: determinação da resistência à tração e ao cisalhamento. Rio de Janeiro, 2002a.) and NBR 14918 (ABNT, 2002bASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 14918: chumbadores mecânicos pós-instalados em concreto: avaliação de desempenho. Rio de Janeiro, 2002b.), whereas ETAGs 001 (EUROPEAN…, 2012bEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 001: metal anchors for use in concrete. Brussels, 2012b.), 020 (EUROPEAN…, 2012cEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 020: plastic anchors for multiple use in concrete and masonry for non-structural applications. Brussels, 2012c.), and 029 (EUROPEAN…, 2013EUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 029: metal injection anchors for use in masonry. Brussels, 2013.) are used to support the structural calculation of the subframe.

However, owing to the difficulty of determining the system while considering wind and impact loads, particularly in non-rectangular or non-uniform façades, tests must be conducted for verifying the assumptions set out for designing.

Wind load resistance

Kumar, Stathopoulos and Wisse (2003)KUMAR, K. S., STATHOPOULOS, T., WISSE, J. A. Field Measurement Data of Wind Loads on Raincreen Walls. Journal of Wind Engineering and Industrial Aerodynamics, v. 91, p. 1401-1417, 2003. demonstrated the insufficiency of national and international wind codes and standards for developing ventilated cladding (rainscreen walls) designs, and thereby, highlighted the need for performing tests to study the diverse situations. In addition, the authors also estimated the impact of various design parameters on the wind loading on the rainscreen; however, they did not explain how to formulate a wind test that considers all the different situations. Currently, ETAG 034 (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.) is adopted as a reference for the wind load resistance evaluation of a ventilated cladding.

According to ETAG 034 (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.),

[…] both the tolerance due to manufacturing and/or installation and deformations due to temperature and humidity variations have to be taken into account and the most critical case shall be tested […].

Furthermore, it highlights that the test results are only valid for those fixing patterns that are tested. Therefore, ETAG 034 proposes that the results of the mechanical test to evaluate the wind resistance must generate the follow information:

  • (a) the load “Q” for which the test specimen fails (rupture load);

  • (b) the type of failure; and

  • (c) the value of deflection as a function of the load, given in a graphical form.

Failure is defined by one of the following events:

  • (a) cladding element breakage; and

  • (b) significant permanent deflection of a cladding element: failure of fixings: failure or detachment of the frame.

The tests proposed by ETAG necessitate reaching the rupture of the components without setting the deflection limit. In Brazil (because of the equipment limitation), it will not be possible to reach the rupture load in all situations. Therefore, this study proposes to conduct the wind load test in Brazil by considering the criteria in NBR 10821-2 (ABNT, 2011aASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 10821: esquadrias para edificações: parte 3: esquadrias externas e internas: métodos de ensaio. Rio de Janeiro, 2011b.) (standard for glass curtain wall), however, with a few adaptations as it is a standard applied to façade components. The loads (pressure or suction) are set considering the service and rupture loads. Thus, the cladding kit should not exhibit the following performance when submitted to service loads caused by the wind:

  • (a) total rupture or partial collapse of any of the components including the cladding element;

  • (b) maximum instant deflection of L/175, where “L” is the free length of the profile under consideration and is limited to 30 mm;

  • (c) residual deflection less than 0.4% of the free length of the profile, measured after 3 min of the shutdown of the test pressure; and

  • (d) failure of fixings.

For the rupture loads, the cladding kit cannot exhibit rupture, total or partial collapse of any of the components, including the cladding elements. In general, the rupture load is 1.4 or 1.5 times higher than the service load.

Impact resistance

According to ETAG 034 (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.), for setting the impact energy, the categories listed in Table 2 should be considered corresponding to the degree of use exposure. This table does not include any allowance for acts of vandalism.

Table 2
Definition of use categories (EUROPEAN…, 2012)

Table 3 presents the performance criteria relating to the hard and soft impact resistances set by ETAG 034, considering the use categories.

Table 3
Impact categories (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.)

According to ETAG 034 (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.),

[…] the approval body shall establish that the cladding product does not present sharp or cutting edges and its surfaces do not cause bodily injury, to the occupants or people nearby […].

Therefore, in the Brazilian context, we propose to include other points with these performance criteria (set on Table 4), which detail the rules and take into account the service and rupture loads, such as the wind resistance assessment, avoiding subjective analyses.

Table 4
Proposed Soft and Hard Impact Criteria

The cladding designer together with other stakeholders of the building production is responsible for deciding whether the cladding must also exhibit the impact performance in the upper floors (effects of hail storms, etc.). However, it is proposed that in regions predisposed to be submitted to impacts by objects thrown or kicked, such as in areas of public access, or on floors of public access, the test of impact of 300 J should be performed.

Drainability

The cladding kit must contribute to the watertighness of the external walls, reducing the penetration of rain inside the building. According to ETAG 034 (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.), the drainability of a cladding kit is generally assessed based on the design, taking into account the characteristics of the materials, geometry of external cladding, thickness of the air space, and joints among cladding elements. In addition, the drainability of water in the kit should be visually assessed.

Therefore, the drainability assessment aims to analyze the relationships of the volume of rainwater hitting the façade with the wind pressure and volume of water that penetrates into the air space and hits the wall (substrate). This enables verification of the eventual concentration of water in the profiles of the subframe cladding.

This assessment can be made via design analysis, verifying the air space thickness (EUROPEAN…, 2014EUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.). However, in non-regular façades with various geometric configurations or with different shapes than those contemplated by NBR 6123 (ABNT, 1988ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6123: forças devidas ao vento em edificações: procedimento. Rio de Janeiro, 1988.), a more detailed analysis is required to determine the amount of water that passes through the cladding and reaches the substrate (wall).

Thus, for drainability assessment, we propose calculating the relation between water sprinkled and water captured during the test, i.e., water that reaches the substrate and water collected (during and after the test). Such information will make it possible to analyze if waterproofing the substrate and the air space thickness specified in the design are suitable for promoting watertightness of the external wall (substrate + ventilated cladding). By means of the tests, it was possible to estimate that 5% is an appropriate relation between water sprinkled and water captured to promote the tightness of the façade.

Methods and results of tests

This section describes the proposed test methods and the tests that were performed to demonstrate their feasibility and to show that the results can attain the proposed performance criteria.

Structural PERFORMANCE

Wind load resistance

The proposal for the wind load test is to adopt the criteria and test method provisioned in NBR 10821-2 (ABNT, 2011aASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 10821: esquadrias para edificações: parte 3: esquadrias externas e internas: métodos de ensaio. Rio de Janeiro, 2011b.), which considers the height of the building and Brazilian regions relating to wind speed classification and considers the need for having one substrate that is not air-tight (particular condition to evaluate ventilated cladding systems).

The specimen to be tested must represent at least one floor with all adjacent joints from the neighboring floors (vertical and horizontal). Then, the minimum height must be that of a floor with the horizontal joints and the minimum length is 2.0 m. The air space must not be air tight and is represented by the substrate that allows the air flow from the inside to the outside of the specimen, to reproduce the air flow in a ventilated cladding system (air space chamber). The substrate can be composed of a polycarbonate plate, whose thickness must be calculated in the function of the vent load. The open joints between the polycarbonate plate and metal profiles also contribute to the air flow. The outer face of the specimen must be placed in front of the test chamber where the loads will be applied. Figure 3 shows a generic specimen scheme to be assembled in wind load test equipment.

Figure 3
Generic specimen scheme in the plant to be assembled in the wind load test equipment

The specimen tested was designed and executed taking into account the cladding kit of the case study, which is formed with ceramic elements mechanically fastened to the subframe fixed to the main building structure and wall (substrate) through anchors.

The cladding elements of the specimen constitute ceramic plates that have variable widths (150 mm to 300 m) and lengths (1185 mm to 1415 mm). The subframe is made of aluminum profiles with the following dimensions: 50 × 73 × 50 × 73 × 4. 76 mm. The fixing devices are also made of aluminum according to the design specifications. EPDM profiles are placed between the metal parts and ceramic to absorb possible differences of motion/vibration between them. The substrate specimen is composed of a 10-mm thick polycarbonate plate structured by metal profiles. Figure 4 illustrates the specimen assembled for testing the wind load resistance and drainability.

Figure 4
Back area of specimen 1 (specimen placed to the wind pressure equipment)

Next, the test was performed considering 2210 Pa as rupture load, 1480 Pa as service load, pressure, and suction, and one building of 90 m height situated in the city of São Paulo (Class IV, according to NBR 6123 (ABNT, 1988ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6123: forças devidas ao vento em edificações: procedimento. Rio de Janeiro, 1988.)). Table 5 lists the test results for pressure loads and Table 6 presents those for the suction loads.

Table 5
Wind pressure test results
Table 6
Wind suction test results

From the analysis of the test procedure and results, it can be concluded that the method proposed is adequate and feasible to perform, highlighting that the specimen was assembled simulating the reality and tests were also performed to simulate real loads, in the case, considering the Brazilian wind load standard, NBR 6123 (ABNT, 1988ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6123: forças devidas ao vento em edificações: procedimento. Rio de Janeiro, 1988.). The test results of this specimen were satisfactory because no fault (e.g. excessive deflection, cracks or breaks) was observed.

Soft impact resistance (60 J and 400 J)

The criteria to evaluate the tests are based on Table 4.

The specimen must be mounted at one-floor height and at least 3.0 m length.

The substrate is the main difference between the wind test specimen and impact test specimen, which is formed by the wall (masonry or other, depends on the real project). Figure 5 shows a generic specimen scheme to be assembled for performing impact load test.

Figure 5
Generic specimen scheme in the plant to be assembled for performing impact load tests

The impact energies (300 J and 400 J) are carried out with a bag weighing 40 kg, from a height of 0.75 m to 1.0 m. Such tests must be carried out in those regions where the cladding is installed at ground level or where there is easy access to the public. This test must be carried out in two points on the cladding kit: point 1 - between the vertical joints, point 2 - in the horizontal joint, in the region where the four cladding elements join each other (Figure 6).

Figure 6
Soft impact localization (400 J)

The impacts of 60 J must be assessed at three points on the cladding element: point 1 - on the bottom edge, near to vertical joints, point 2 - on the center of the cladding element; and point 3- on the top edge of the cladding elements (Figure 7).

Figure 7
Soft impact localization (60 J)

The specimen to be tested was formed by fixing the cladding elements to a substrate made with masonry, which was reinforced in the regions of the anchors. The cladding elements of the specimen and their reinforcements are the same as those used on the ground floor of the case study building. These elements were reinforced with aluminum composite plates, 6-mm in thickness, and fixed to the back of the ceramic with a structural sealant. Figures 7 and 9 illustrates the specimen assembled for testing the impact resistance.

Figure 8
Front of the specimen 2 (cladding system) fixed to masonry

Figure 9
Back of the specimen 2 (reinforced ceramic plates)

Tables 7 and 8 summarize the test results of the soft body impact of 400 J and 60 J. Both tests were performed considering the cladding on the ground floor, with reinforcement of aluminum plate on the back of ceramic plates.

Table 7
Test results of soft body impact - 400 J
Table 8
Test results of soft body impact - 60 J

By analyzing the test procedure and results, it is possible to conclude that the method proposed is adequate and feasible to perform, and the impact resistance criteria proposed can be possibly reached. In addition, the tests results are satisfactory because the occurrences did not affect the cladding performance, according to Table 3.

For others floors, the tests were not performed without reinforcing the ceramic elements, and so it was not possible to affirm that the cladding supported the soft impact resistance, even for 60 J.

Hard impact

The specimen used in the hard body impact test is the same as that used in soft body tests. The hard body impact is to evaluate mostly the surface resistance of the cladding element. The element is submitted to impacts in five distinct regions (Figure 10). The points are defined according to ETAG 034 (EUROPEAN…, 2012aEUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.) relating to the minimum distance of the edge.

Figure 10
Localization of the hard impact points (10 J)

The impact energy (10 J) is carried out with a steel ball weighing 1 kg and from a height of 1.0 m.

Table 9 summarizes the hard body impact test results. This test was also executed considering the cladding on the ground floor with reinforcement of aluminum plate on the back of the ceramic.

Table 9
Test results of hard body impact - 10J

Therefore, it is proper to assume the same conclusion for the soft and hard body tests, relating to the test procedure and results.

Drainability

The drainability test must be performed according to the watertightness test of NBR 10821-3 (ABNT, 2011bASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 10821: esquadrias para edificações: parte 3: esquadrias externas e internas: métodos de ensaio. Rio de Janeiro, 2011b.), considering the water pressure to be compatible with the classification of wind speed (according to NBR 6123, 1988) and with the height of the building. The specimen tested are the same as those used in the wind load tests. The aim of this test is to measure the water that reaches the substrate or remains in the cladding inner, i.e., to quantify the water that was not drained out. Next, two moments were measured:

  • (a) immediately after the end of the test; and

  • (b) 24 h after the end of the test, allowing the capture of the residual water remaining on the substrate or in other localizations.

It was also necessary to mount a device to capture the water that reaches the substrate (polycarbonate, in this case). The device consisted of troughs positioned in the metal structure of the specimen, hoses, a pipe collector, and a container for measuring the amount of water, as shown in Figure 11.

Figure 11
Device for collecting water in the drainability test

Then, for the test conducted on the specimen, a pressure of 296 Pa (20% of the service load pressure) was considered at 90 m height of the building situated at São Paulo (Class IV, according to NBR 6123 (ABNT, 1988ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6123: forças devidas ao vento em edificações: procedimento. Rio de Janeiro, 1988.)). Table 10 summarizes the drainability test results.

Table 10
Drainability test results

The content of water that reaches the substrate is low in relation to the total water sprinkled, suggesting that if the design considers the ETAG considerations (minimum 20-mm thick air space and ventilation openings at the base point and a roof edge with cross-sections of at least 50 cm2 per linear meter), there exists a possibility of performing drainability analysis based on the design, even in Brazil. However, it is considered necessary that the largest database of drainability test results be used for validating this hypothesis.

Conclusions

The ventilated cladding system has the potential to contribute to the façade watertightness, although this criterion must be satisfied by the entire façade and not just by the cladding system. However, the cladding has specific performance requirements and criteria to comply with, which justify this research work.

The proposed criteria and tests methods were feasible on the basis of the tests performed and obtained results. However, while conducting the tests, reproducibility of the cladding specimen must be analyzed corresponding to real design to avoid false analysis and inaccurate results. The specimen must be so assembled to always simulate the reality and the tests must be performed for simulating the real loads.

In future studies, we recommend performing soft-body and hard-body tests in reference to the cladding elements without reinforcements (in this study aluminum plates were glued to the ceramic plates) and drainability tests while varying the thickness of the air space.

In regard to the drainability tests, to consolidate the test methods, the rate of 5% must be sustained in all the performed tests considering air space variation in cladding and fixing devices. Drainability performance contributes to the specification of the waterproof products used on the substrate (wall). Other tests, such as protection against noise, safety in case of fire, and aspects of durability and serviceability shall be performed in future studies.

Considering the durability of the required systems, tests categorized as accelerated aging, natural aging, moisture chamber, and salt spray may be performed to estimate the cladding elements, subframe, and fixings performances. The data so obtained will provide guidance to formulate preventive maintenance activities of the cladding system.

References

  • AMERICAN SOCIETY FOR TESTING AND MATERIALS. ASTM E 283: standard test method for determining rate of air leakage through exterior Windows, curtain walls, and doors under specified pressure differences across the specimen. Philadelphia, 2012.
  • AMERICAN SOCIETY FOR TESTING AND MATERIALS. ASTM E 330: standard test method for structural performance of exterior Windows, doors, skylights and curtain walls by uniform static air pressure difference. Philadelphia, 2014.
  • AMERICAN SOCIETY FOR TESTING AND MATERIALS. ASTM E 331: standard test method for water penetration of exterior Windows, skylights, doors, and curtain walls by uniform static air pressure difference. Philadelphia, 2009.
  • ARCO. Fachadas Ventiladas no Mercado Brasileiro. Revista Finestra, v. 77, nov. 2012. Available on: <https://arcoweb.com.br/finestra/tecnologia/tecnologia---especial-fachadas-fachadas-ventiladas>. Acess in: 01 apr. 2016.
    » https://arcoweb.com.br/finestra/tecnologia/tecnologia---especial-fachadas-fachadas-ventiladas
  • ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 10821: esquadrias para edificações: parte 2: esquadrias externas: requisitos e classificação. Rio de Janeiro, 2011a.
  • ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 10821: esquadrias para edificações: parte 3: esquadrias externas e internas: métodos de ensaio. Rio de Janeiro, 2011b.
  • ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 14762: dimensionamento de estruturas de aço constituídas por perfis formados a frio. Rio de Janeiro, 2010.
  • ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 14827: chumbadores instalados em elementos de concreto ou alvenaria: determinação da resistência à tração e ao cisalhamento. Rio de Janeiro, 2002a.
  • ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 14918: chumbadores mecânicos pós-instalados em concreto: avaliação de desempenho. Rio de Janeiro, 2002b.
  • ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 15575: edificações habitacionais: desempenho. Rio de Janeiro, 2013.
  • ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 6123: forças devidas ao vento em edificações: procedimento. Rio de Janeiro, 1988.
  • ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 8800: projetos de estruturas de aço e de estruturas mistas de aço e concreto de edifícios. Rio de Janeiro, 2008.
  • BECERE O. H. Revestimentos de Ligantes Sintéticos: proposta de métodos de ensaios para avaliação de desempenho. São Paulo, 2007. Dissertação (Mestrado em Engenharia Civil) - Instituto de Pesquisas Tecnógicas, São Paulo, 2007.
  • EUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 001: metal anchors for use in concrete. Brussels, 2012b.
  • EUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 020: plastic anchors for multiple use in concrete and masonry for non-structural applications. Brussels, 2012c.
  • EUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 029: metal injection anchors for use in masonry. Brussels, 2013.
  • EUROPEAN TECHNICAL APPROVAL GUIDELINES. ETAG 034: ventilated cladding kits comprising cladding components and associated fixings. Brussels, 2012a.
  • EUROPEAN TECHNICAL ASSESSMENT. ETA 14/041: external wall claddings in ventilated façade. Barcelona, 2014.
  • KUMAR, K. S., STATHOPOULOS, T., WISSE, J. A. Field Measurement Data of Wind Loads on Raincreen Walls. Journal of Wind Engineering and Industrial Aerodynamics, v. 91, p. 1401-1417, 2003.
  • LANGMANS, J.; ROELS, S. Experimental Analysis of Cavity Ventilation Behind Rainscreen Cladding Systems: a comparison of four measuring techniques. Building and Environment, v. 87, fev, 2015.
  • MACHADO, A. L. A. Diretrizes de Projeto Para Revestimentos Não Aderidos de Fachada Constituídos de Placas Cerâmicas Extrudadas São Paulo, 2012. Dissertação (Mestrado em Engenharia Civil) - Instituto de Pesquisas Tecnológicas, São Paulo, 2012.
  • MARINOSCI, C.; SEMPRINI, G.; MORINI, G. L. Experimental Analysis of the Summer Thermal Performances of a Naturally Ventilated Rainscreen Façade Building. Energy and Buildings, v. 72, p. 280-287, 2014.
  • PATÓN, V. El Nascimiento de Uma Técnica. Tectónica Cerramientos Pesados: Aplacados y Panales - Envolventes (II). Barcelona, v. 2, p. 4-11, 1995.
  • PIANO, R. Fachada do IRCAM Institut de Recherche et Coordination Acoustique/Musique. Available: <http://www.rpbw.com/project/12/ircam>. Acess in: 23 nov. 2016.
    » http://www.rpbw.com/project/12/ircam
  • RESENDE, M. M.; BARROS, M. M. S. B.; MEDEIROS, J. S. A Influência da Manutenção na Durabilidade dos Revestimentos de Fachada de Edifícios. In: WORKSHOP SOBRE DURABILIDADE DAS CONSTRUÇÕES, 2., São José dos Campos, 2001. Anais... São José dos Campos, 2001.
  • RIBEIRO, F. A.; BARROS, M. M. S. B. Juntas de Movimentação em Revestimentos Cerâmicos de Fachadas São Paulo: PINI, 2010.
  • ROUSSEAU, M. Z.; POIRIER, G. F.; BROWN, W. C. Pressure Equalization in Rainscreen Wall Systems. Construction Technology Updates no. 17 Institute for Research in Construction, National Research Concil of Canada, 1998.
  • SANJUAN, C. et al Energy Performance of an Open-Joint Ventilated Façade Compared With a Conventional Sealed Cavity Façade. Solar Energy, v. 85, n. 9, p. 1851-1863, 2011.
  • SIQUEIRA JÚNIOR, A. A. Tecnologia de Fachada-Cortina Com Placas de Grês Porcelanato São Paulo, 2003. Dissertação (Mestrado em Engenharia Civil) - Escola Politécnica, Universidade de São Paulo, São Paulo, 2003.
  • STRAUBE, J.; FINCH, G. Ventilated Wall Claddings: review, field performance, and hygrothermal modeling. Research Report - 0906, 2009. Available on: <http://buildingscience.com>. Acess in: 15 apr. 2016.
    » http://buildingscience.com
  • TRECHSEL, H. R.; BOMBERG, M. T. Moisture Control in Buildings: the key factor in mold prevention. Baltimore, 2009.
  • VEDOVELLO, C. A. S. Gestão de Projetos de Fachadas São Paulo, 2012. Dissertação (Mestrado em Engenharia Civil) - Escola Politécnica, Universidade de São Paulo, São Paulo, 2012.